Install Instructions

4
Wiring Diagram Legends
1. Bold lines indicate action to be taken
in Step shown.
2. Grey lines indicate existing wiring.
PS-802-24
LWCO
HNB
UNI-MATCH
WATER FEEDER
WFE-24
Factory
Jumper
Bar
NHCWB
WNH
Connect wire from terminal 'N' of water
feeder to terminal ''N' on LWCO.
Connect wire from terminal 'H' of water
feeder to terminal 'H' on LWCO.
Connect wire from terminal 'W' of water
feeder to terminal 'W' on LWCO.
Diagram 1
WFE-24 / PS-802-LWCO
WNH
PS-801-120
LWCO
UNI-MATCH
WATER FEEDER
WFE-120
Field or
Factory
Jumper
Wire
P123 45
Connect wire from terminal 'N' of
water feeder to terminal '2' on LWCO.
Connect wire from terminal 'H' of
water feeder to terminal '1' on LWCO.
Connect wire from terminal 'W' of
water feeder to terminal '4' on LWCO.
Diagram 2
WFE-120 / PS-801-LWCO with numbered terminals
PS-801-120
LWCO
UNI-MATCH
WATER FEEDER
WFE-120
NHCWB
WNH
Factory
Jumper
Bar
Connect wire from terminal 'N' of
water feeder to terminal 'N' on LWCO.
Connect wire from terminal 'H' of
water feeder to terminal 'H' on LWCO.
Connect wire from terminal 'W' of
water feeder to terminal 'W' on LWCO.
Diagram 3
WFE-120 / PS-801-LWCO with lettered terminals
WNH
BURNER
12
34
NEUTRAL
24 VAC
HOT
UNI-MATCH
WATER FEEDER
WFE-24
SERIES 67
LOW WATER
CUT-OFF
Connect wire from terminal 'N' of
water feeder to 'Neutral' wire of
burner circuit.
Connect wire from terminal 'H' of
water feeder to terminal '2' on
LWCO.
Connect jumper wire connecting
terminals '2' and '3' of LWCO.
Connect wire from terminal 'W' of
water feeder to terminal '4' on LWCO.
Diagram 4
WFE-24 / 67 with 24 volt burner circuit
WNH
BURNER
12
34
NEUTRAL
120 VAC
HOT
UNI-MATCH
WATER FEEDER
WFE-120
SERIES 67
LOW WATER
CUT-OFF
Connect wire from terminal 'N' of water
feeder to 'Neutral' wire of burner circuit.
Connect wire from terminal 'H' of water
feeder to terminal '2' on LWCO.
Connect jumper wire connecting terminals
'2' and '3' of LWCO.
Connect wire from terminal 'W' of
water feeder to terminal '4' on LWCO.
Diagram 5
WFE-120 / 67 with 120 volt burner circuit
WNH
BURNER
24V
TRANSFORMER
12
3 4
NEUTRAL
120 VAC
120 VAC
SUPPLY
HOT
UNI-MATCH
WATER FEEDER
WFE-24
SERIES 67
LOW WATER
CUT-OFF
Install wire from burner circuit 'Neutral' wire to the trans
former input 'Neutral' terminal.
Install wire from burner circuit 'Hot' wire to the transformer
input 'Hot' terminal.
Install wire from transformer output 'Neutral' terminal
to terminal 'N' on the water feeder.
Install wire from terminal 'W' on the water feeder to terminal
'4' on the low water cut-off.
Install wire from transformer output 'Hot' terminal to terminal
'H' on water feeder and terminal '3' on low water cut-off.
NOTE: Transformer provided by others.
Diagram 6
WFE-24 / 67 with 120 volt burner circuit
WNH
BURNER
24V
TRANSFORMER
12
34
NEUTRAL
120V
HOT
UNI-MATCH
WATER FEEDER
WFE-120
SERIES 67
LOW WATER
CUT-OFF
Install wire from burner circuit 'Neutral' wire to terminal 'N'
on water feeder.
Install wire from burner circuit 'Hot' wire to terminal 'H' on
water feeder and terminal '3' on low water cut-off.
Install wire from terminal 'W' on the water feeder
to terminal '4' on the low water cut-off.
Diagram 7
WFE-120 / 67 with 24 volt burner circuit