Install Instructions

6
UNI-MATCH
WATER FEEDER
WFE-120
21P1 P2 A
BURNER
LOW
LIMIT
THERMOSTAT
WNH
Factory
Jumper
Bar
HYDROLEVEL CGT450
Connect wire from terminal 'N' of water feeder
to terminal '2' on LWCO.
Connect wire from terminal 'H' of water feeder
to terminal '1' on LWCO.
Connect wire from terminal 'W' of water feeder
to terminal 'A' on LWCO.
Diagram 14
WFE-120 / Hydrolevel CGT450
HONEYWELL LWCO
24 VOLT
UNI-MATCH
WATER FEEDER
MODEL
WFE-24
T1 A B
T2 A B
WNH
Connect wire from terminal 'N' of water feeder
to terminal 'T2' on LWCO.
Connect wire from terminal 'H' of water feeder
to terminal 'T1' on LWCO.
Connect jumper wire from terminal 'T1' to
terminal 'A' on the low water cut-off.
Connect wire from terminal 'W' of water feeder
to terminal 'A' on LWCO.
Diagram 15
WFE-24 / Honeywell LWCO (24 volt)
HONEYWELL LWCO
120 VOLT
UNI-MATCH
WATER FEEDER
WF2-U-120
L1 A B
L2 A B
WNH
Connect wire from terminal 'N' of water feeder
to terminal 'L2' on LWCO.
Connect wire from terminal 'H' of water feeder
to terminal 'L1' on LWCO.
Connect jumper wire from terminal 'L1' to
terminal 'A' on the low water cut-off.
Connect wire from terminal 'W' of water feeder
to terminal 'A' on LWCO.
Diagram 16
WF2-U-120 / Honeywell LWCO (120 volt)
NC COM NO L N GND P
WNH
TACO LWCO
120 VOLT
Field or
Factory
Installed
Jumper
Wire
UNI-MATCH
WATER FEEDER
MODEL
WFE-120
Connect wire from terminal 'N' of water feeder
to terminal 'N' on LWCO.
Connect wire from terminal 'H' of water feeder
to terminal 'L' on LWCO.
Connect wire from terminal 'W' of water feeder
to terminal 'NO' on LWCO.
Diagram 17
WFE-120 / TACO LWCO (120 volt)
UNI-MATCH
WATER FEEDER
MODEL
WFE-24
NC COM NO L N GND P
WNH
TACO LWCO
24 VOLT
Field or
Factory
Installed
Jumper
Wire
Connect wire from terminal 'N' of water feeder
to terminal 'N' on LWCO.
Connect wire from terminal 'H' of water feeder
to terminal 'L' on LWCO.
Connect wire from terminal 'W' of water feeder
to terminal 'NO' on LWCO.
Diagram 18
WFE-24 / TACO LWCO (24 volt)