Install Instructions
5
e. Electrical Conduit Connection
• Connect electric conduit using knockouts
provided.
• Follow accepted electrical practices when
installing fittings and making connections.
• Refer to and follow codes and standards
when selecting the types of electrical
fittings and conduit.
b . Using a flatblade screw d ri ve r, loosen the probe
mounting screws (F) 1/8" (3mm) about 1-1/2 turn s
and slip the control housing (G) over these two
s c r ews at a 20˚ angle.
a . Push out the probe knockouts and remove
completely from the control housing.
c . Rotate the control housing (G) 20˚ counterclock w i s e
so that the slots in the control base are firmly under
the screw heads. Tighten the mounting screws (F)
to approximately 2 ft•lb (2.6 N•m).
d . R e m o ve wingnut from probe and position ring
t e r minal of probe wire on threaded probe rod.
Secure with wingnu t .