Specifications
1198
Thermal Management: Heat Exchangers
Heat Exchangers
PH (763) 422-2211 • FX (763) 422-2600 • homanonline.com
Subject to change without notice © 2011 Pentair Technical Products
XR Series Compact and Mid-Size Heat Exchanger
Industry Standards
Maintains UL/cUL Type 12 rating when properly installed on a UL/cUL
Type 12 enclosure.
Maintains Type 3R rating when mounted externally and in a vertical
position on a UL/cUL Type 3R enclosure.
XR200416012 and XR200426012 do not carry Type 3R rating.
UL/cUL Listed; File No. SA7402
CE
Application
Available in several sizes, these high-eciency, streamlined heat
exchangers are designed for use on narrow or shallow enclosures.
Application Tip
Locate heat-sensitive components in line with the “Air Out” opening
of the heat exchanger.
Features
•
Unique cores include modied heat pipe core on XR20 and XR2908
and counterow aluminum core on XR2918, XR47 and XR60
• Top-quality ball-bearing fans
• Streamlined aesthetics with no visible mounting rails or fasteners
• Front cover hinges
• Filterless design; the core slides out for easy cleaning
• Mounts vertically or horizontally on front, side or top of enclosure,
inside or outside of enclosure
• Mounting gaskets and instruction manual furnished
• DC voltage available if required. Please contact Homan.
Service cord provided includes appropriate plug:
- NEMA 5-15P for 115V units
- NEMA 6-15P for 230V units
Finish
Coated with RAL 7035 polyester powder paint inside and out
Notes
Homan XR units are directly interchangeable with ProAir models.
Bulletin: MCLHE
Standard Product
Catalog Number
AxBxC in. AxBxC mm Voltage Hz Phase
Full
Load
Amps
Max Amb.
Temp. (°F)
Max Amb.
Temp. (°C)
Enclosure
Air In
(W/°F)
Enclosure
Air In
(W/K)
Enclosure
Air Out
( W/°F)
Enclosure
Air Out
(W/K)
Ship
Wt. (lb.)
Ship
Wt. (kg)
XR200416012 20.00 x 7.50 x 3.00 508 x 191 x 76 115 50/60 1 0.6 140 60 4 7 9 16 16 7
XR200426012 20.00 x 7.50 x 3.00 508 x 191 x 76 230 50/60 1 0.3 140 60 4 7 9 16 16 7
XR290816012 29.50 x 10.00 x 3.09 749 x 254 x 78 115 50/60 1 0.6 140 60 8 14 30 54 27 12
XR290826012 29.50 x 10.00 x 3.09 749 x 254 x 78 230 50/60 1 0.3 140 60 8 14 30 54 27 12
XR291816012 29.66 x 10.24 x 5.92 753 x 260 x 150 115 50/60 1 1.0 140 60 18 32 34 61 34 16
XR291826012 29.66 x 10.24 x 5.92 753 x 260 x 150 230 50/60 1 0.6 140 60 18 32 34 61 34 16
XR472416012 47.16 x 10.24 x 5.92 1198 x 260 x 150 115 50/60 1 1.5 140 60 24 43 44 79 51 24
XR472426012 47.16 x 10.24 x 5.92 1198 x 260 x 150 230 50/60 1 0.8 140 60 24 43 44 79 51 24
XR473516012 47.16 x 15.24 x 5.92 1198 x 387 x 150 115 50/60 1 1.5 140 60 35 63 77 139 63 29
XR473526012 47.16 x 15.24 x 5.92 1198 x 387 x 150 230 50/60 1 0.8 140 60 35 63 77 139 63 29
XR605516012 59.66 x 15.24 x 5.92 1515 x 387 x 150 115 50/60 1 6.7 140 60 55 99 138 248 91 42
XR605526012 59.66 x 15.24 x 5.92 1515 x 387 x 150 230 50/60 1 3.4 140 60 55 99 138 248 91 42
XR608416012 59.66 x 15.24 x 9.92 1515 x 387 x 252 115 50/60 1 6.7 140 60 84 151 210 378 115 53
XR608426012 59.66 x 15.24 x 9.92 1515 x 387 x 252 230 50/60 1 3.4 140 60 84 151 210 378 115 53
The “enclosure air in” eciency rating is based on air entering the heat exchanger from the enclosure. The “enclosure air out” eciency rating is based on air exiting the heat exchanger into the enclosure. All XR exchanger
units are rated at 100 F/38 C ambient temperatures with 1500 W internal heat load. Heat exchanger eciency will decrease as ambient temperature and/or internal heat load decreases.