Unit installation
120 ACZ / AGZ-BM IOMM ACZ/AGZ-3
SET UNIT SPs (4)
CLOCK
dd/mm/yyyy
hh:mm weekday
SET UNIT SPs (5)
Units = °
°°
°F/psi
Lang = ENGLISH
Units settings are only °F/psi at the present time. °C/kPa will be available later.
Lang (Language) settings can be only ENGLISH at present.
SET UNIT SPs (6)
Protocol = Modbus
Ident Number=001
Baud Rate=9600
Ident Number and Baud Rate are in effect when BAS is selected in the SET screen (Modbus only).
SET UNIT SPs (7)
Evap Pressure Sensor
Cir1 Offset= XX.Xpsi
Cir2 Offset= XX.Xpsi
SET UNIT SPs (8)
Cond Pressure Sensor
Cir1 Offset= XX.Xpsi
Cir2 Offset= XX.Xpsi
SET UNIT SPs (9)
Outside Ambient
Temperature Sensor
Offset= XX.X
o
F
The pressure offsets on menus 7 and 8 and the temperature offsets on menus 9 correct the
controller's display of the parameters. The sensors used in these units have a high degree of
repeatability but may need initial correction (offset). An accurate pressure gauge or thermometer is
used to determine the correct temperature or pressure. A positive or negative offset value is then
entered to make the controller reading agree with the measured value.
SET UNIT SPs (10)
ENTER PASSWORD: XXXX
Active Password
Level: None
Set Compressor Setpoints
SET COMP SPs (1)
# of Compressors=X
Stop-Start =XXmin
Start-Start =XXmin
This menu sets the anti-recycle timers. Stop-Start is the time required before starting a compressor
after it has stopped. Start-Start is the time required before starting a compressor after the last time it
has started. It is recommended that these default values not be changed.