Unit installation

IOMM ACZ/AGZ-3 ACZ / AGZ-BM 31
Electrical Data Standard Ambient
Table 20, ACZ BC & AGZ BM Electrical Data, Single Point (105°F & below)
Power Supply
Field Wire
ACZ
Unit
Size
AGZ
Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
75C
Recomm’d.
Fuse
Or HACR
Breaker
Size
Max. Fuse
Or HACR
Breaker
Size
208
133
3
1/0
150
150
230 126 3 #1 150 150
380 80 3 #4 90 90
460 68 3 #4 80 80
030B 026B
575 52 3 #6 60 60
208
146
3
1/0
175
175
230 143 3 1/0 175 175
380 88 3 #3 100 100
460 74 3 #4 80 90
035B 030B
575 58 3 #6 70 70
208
158
3
2/0
175
175
230 150 3 1/0 175 175
380 96 3 #3 110 110
460 79 3 #4 90 90
040B 035B
575 64 3 #6 70 70
208
167
3
2/0
200
200
230 167 3 2/0 200 200
380 113 3 #2 125 125
460 81 3 #4 90 90
045B 040B
575 70 3 #4 80 80
208
184
3
3/0
225
225
230 184 3 3/0 225 225
380 121 3 #1 125 125
460 94 3 #3 110 110
050B 045B
575 78 3 #4 90 90
208
199
3
3/0
225
225
230 199 3 3/0 225 225
380 127 3 #1 150 150
460 104 3 #2 125 125
055B 050B
575 86 3 #3 100 100
208
221
3
4/0
250
250
230 214 3 4/0 250 250
380 145 3 1/0 175 175
460 108 3 #2 125 125
060B 055B
575 96 3 #3 110 110
208
248
3
250
300
300
230 228 3 4/0 250 250
380 156 3 2/0 175 175
460 112 3 #2 150 150
065B 060B
575 105 3 #2 125 125
208
281
3
300
350
350
230 281 3 300 350 350
380 162 3 2/0 200 200
460 124 3 #1 150 150
070B 065B
575 109 3 #2 125 125
208
301
3
350
350
350
230 301 3 350 350 350
380 168 3 2/0 200 200
460 130 3 #1 150 150
080B 070B
575 112 3 #2 125 125
NOTES:
1. Units operating in ambient temperatures of 95°F (35°C) and above must use the Maximum Fuse or HACR
Breaker size.
2. All Electrical Data notes are on page 47.
3. Conduit hubs are not provided.