Unit installation

46 ACZ / AGZ-BM IOMM ACZ/AGZ-3
Table 35, ACZ BC & AGZ BM Electrical Data, Multi-Point (106°F)
Electrical Circuit #1 Electrical Circuit #2
Power
Supply
Power
Supply
Field Wire Field Wire
ACZ
Unit
Size
AGZ
Unit
Size
V
olts
Minimum
Circuit
Ampacity
(MCA)
Qty
Wire
Gauge
75C
Recomm’d
Fuse
or HACR
Breaker
Size
Max. Fuse
or HACR
Breaker
Size
Minimum
Circuit
Ampacity
(MCA)
Qty
Wire
Gauge
75C
Recomm’d
Fuse
or HACR
Breaker
Size
Max.
Fuse
or HACR
Breaker
Size
208
199
3
3/0
225
250
199
3
3/0
225
250
230 190 3 3/0 225 250 190 3 3/0 225 250
380 102 3 #2 125 125 102 3 #2 125 125
460 99 3 #3 110 125 99 3 #3 110 125
090B 075B
575 76 3 #4 90 100 76 3 #4 90 100
208
199
3
3/0
225
250
219
3
4/0
250
300
230 190 3 3/0 225 250 211 3 4/0 250 250
380 102 3 #2 125 125 142 3 1/0 175 175
460 99 3 #3 110 125 111 3 #2 125 150
100B 085B
575 76 3 #4 90 100 83 3 #3 100 110
208
219
3
4/0
250
300
219
3
4/0
250
300
230 211 3 4/0 250 250 211 3 4/0 250 250
380 142 3 1/0 175 175 142 3 1/0 175 175
460 111 3 #2 125 150 111 3 #2 125 150
110B 090B
575 83 3 #3 100 110 83 3 #3 100 110
208
220
3
4/0
250
250
317
3
400
350
400
230 203 3 4/0 225 250 272 3 300 300 300
380 123 3 #1 150 150 159 3 2/0 175 200
460 101 3 #2 110 125 136 3 1/0 150 175
120B 100B
575 83 3 #4 100 100 109 3 #2 125 125
208
317
3
400
350
400
317
3
400
350
400
230 272 3 300 300 300 272 3 300 300 300
380 159 3 2/0 175 200 159 3 2/0 175 200
460 136 3 1/0 150 175 136 3 1/0 150 175
130B 110B
575 109 3 #2 125 125 109 3 #2 125 125
208
317
3
400
400
400
317
3
400
400
400
230 272 3 300 300 300 317 3 400 400 400
380 159 3 2/0 200 200 204 3 4/0 250 250
460 136 3 1/0 175 175 159 3 2/0 200 200
140B 120B
575 109 3 #2 125 125 118 3 #1 150 150
208
317
3
400
400
400
317
3
400
400
400
230 317 3 400 400 400 317 3 400 400 400
380 204 3 4/0 250 250 204 3 4/0 250 250
460 159 3 2/0 200 200 159 3 2/0 200 200
155B 130B
575 118 3 #1 150 150 118 3 #1 150 150
NOTES:
1. All Electrical Data notes are on page 47.
2. Conduit hubs are not supplied.