Unit installation
66 ACZ / AGZ-BM IOMM ACZ/AGZ-3
Ice timer status (12 hours between starts)
Stage Up
For 2 compressors/circuit:
Control band = Evap Delta T x .3
For 3 compressors/circuit:
Control band = Evap Delta T x .2
IF
[LWT Error > Startup_Delta_T_SP + 0.5(Control band)
AND Number Comps Running = 0
AND Ice Timer Expired]
THEN Stage_Up_Now = YES
ELSE IF
[LWT Error > 0
AND Number Comps Running > 0
AND Stage Up Timer Expired]
THEN Stage_Up_Now = YES
Stage Down
IF LWT Error < 0
THEN Stage_Down_Now = YES
Leaving Water Reset
The leaving water reset input uses a 4-20mA signal to reset the leaving water setpoint to a higher
value. The adjustment varies linearly from 0 degrees F to 10 degrees F, with a reset of 0 for a 4mA
signal and a reset of 10 for a 20mA signal.
At all times, the active leaving water setpoint is limited to a maximum of 60°F. The reset remains
proportional within the 10 degree band, but the setpoint will simply stop resetting when it reaches
the maximum.
Circuit Capacity Overrides – Limits of Operation
The following conditions override the automatic capacity control when the chiller is in COOL mode
or ICE mode. These overrides keep a circuit from entering a condition in which it is not designed to
run.
Low Evaporator Pressure
If a circuit is running, and the evaporator pressure drops below the Low Evaporator Pressure-Hold
setpoint, no more compressors will be allowed to start on that circuit. This limit is active until the
evaporator pressure reaches the hold setpoint plus 8 psi.
If a circuit is running with two or three compressors on, and the evaporator pressure drops below the
Low Evaporator Pressure-Unload setpoint, the circuit will begin reducing capacity. If two
compressors are running, one of the running compressors will be stopped. If three compressors are
running, then one compressor will be stopped initially. Ten seconds later, if the pressure has not