Troubleshooting Tips
The table below lists typical symptoms and the corresponding solution(s).
Symptom Condition Probable Cause Solution
Is the frequency command source A_01 parameter
setting correct?
Is the Run command source A-02 parameter setting
correct?
Make sure the parameter setting A-01 is correct.
Make sure the parameter setting A-02 is correct.
Is power being supplied to terminals [L1], [L2], and
[L3/N]? If so, the POWER lamp should be ON.
Check terminals [L1], [L2], and [L3/N], then [U/T1],
[V/T2], and [W/T3].
Turn ON the power supply or check fuses.
Is there an error code E X X displayed? Press the Func. key and determine the error type.
Eliminate the error cause, then clear the error
(Reset).
Are the signals to the intelligent input terminals
correct?
Is the Run Command active?
Is the {FW] terminal (or [RV]) connected to [P24] (via
switch, etc.)
Verify the terminal functions for C_01 – C_05 are
correct.
Turn ON Run Command enable.
Supply 24V to {FW] or [RV] terminal, if configured.
Has the frequency setting for F_01 been set greater
than zero?
Are the control circuit terminals [H], [O], and [L]
connected to the potentiometer?
Set the parameter for F_01 to a safe, non-zero
value.
If the potentiometer is the frequency setting source,
verify voltage at [O] > 0V.
The inverter
outputs [U], [V],
[W] are not
supplying voltage.
Is the RS (reset) function or FRS (free-run stop)
function ON?
Turn OFF the command(s).
Inverter outputs
[U], [V], [W] are
supplying voltage.
Is the motor load too heavy? Reduce load, and test the motor independently.
The motor
will not run.
The optional
remote operator is
used (SRW).
Are the operational settings between the remote
operator and the inverter unit correct?
Check the operator type setting.
Are the connections of output terminals [U/T1], [V/T2],
and [W/T3] correct?
Is the phase sequence of the motor forward or
reverse with respect to [U/T1], [V/T2], and [W/T3]?
Make connections according to the phase sequence
of the motor. In general:
FWD = U-V-W, and
REV = U-W-V.
The direction of the motor is
reversed.
Are the control terminals [FW] and [RW] wired
correctly?
Is parameter F_04 properly set?
Use terminal [FW] for forward, and [RV] for reverse.
Set motor direction in F_04.
If using the analog input, is the current or voltage at
[O] or [OI]?
Reduce the load.
Heavy loads activate the overload restriction feature
(reduces output as needed).
Is the load too heavy? Reduce the load
Heavy loads activate the overload restriction feature
(reduces output as needed).
The motor speed will not reach
the target frequency (desired
speed).
Is the inverter internally limiting the output frequency? Check max frequency setting (A_04).
Check frequency upper limit setting (A_61).
The RPM of the motor does not
match the inverter output
frequency setting.
Is the maximum frequency setting A_04 correct?
Does the monitor function D_01 display the expected
output frequency?
Verify the V/f settings match motor specification.
Make sure all scaling (such as A_11 to A_14) is
properly set.
Was power turned OFF after a parameter edit but
before pressing the Store key?
Edit the data and press the Store key once.
No downloads
have occurred.
Edits to data are permanently stores at power down.
Was the time from power OFF to power ON less than
six seconds?
Wait six seconds or more before turning power OFF
after editing data.
Inverter data
is not correct.
A download to
the inverter was
attempted.
Was the power turned OFF within six seconds after
the display changed from REMT to INV?
Copy data to the inverter again, and keep power ON
for six seconds or more after copying.
True for certain
parameters.
Is the inverter in Run Mode? Some parameters
cannot be edited during Run Mode.
Put inverter in Stop Mode (press the Stop/reset
key). Then edit the parameter.
A parameter
will not
change after
an edit
(reverts to old
setting).
True for all
parameters.
If you’re using the [SFT] intelligent input (software lock
function)is the [SFT] input ON?
Change the state of the SFT input, and check the
B_31 parameter (SFT mode).