Unit installation

IOMM ACZ/AGZ-3 ACZ / AGZ-BM 9
Case 3, Three or More Units Side By Side
When three or more units are side by side, the outside units (1 and 3 in this case) are influenced by the
middle unit only on their inside circuits. Their adjustment factors will be the same as Case 2. All inside
units (only number 2 in this case) are influenced on both sides and must be adjusted by the factors shown
below.
Figure 9, Three or More Units
Chiller 1 Chiller 2 Chiller 3
Figure 10, Adjustment Factor
4.0
3.0
2.0
0
1.0
8.0
6.0
4.0
0
2.0
A
GZ 075-130
A
CZ 090-155
A
GZ 026-070
A
CZ 030-080
15
(4.6)
11
(3.3)
16
(4.9)
12
(3.7)
17
(5.2)
13
(4.0)
18
(5.5)
14
(4.3)
15
(4.6)
11
(3.3)
16
(4.9)
12
(3.7)
17
(5.2)
13
(4.0)
18
(5.5)
14
(4.3)
A
GZ 075-130
A
CZ 090-155
A
GZ 026-070
A
CZ 030-080