Product manual

12 IOMM ACR/AGR-1
Figure 7, Pressure Drop Curve
NOMINAL MAXIMUM MINIMUM
PD Flow PD Flow PD Flow
CDE
Size
AGR
Unit
Size
ft of Water gpm lps ft of Water gpm lps ft of Water gpm lps
1204-1 070 AM 11.2 162 10.22 28.1 270 17.03 4.8 101 6.39
1255-1 075 AM 8.9 172 10.85 22.5 287 18.09 3.8 108 6.78
- 080 AM 10.3 187 11.80 25.9 312 19.66 4.4 117 7.37
- 085 AM 11.8 202 12.74 29.7 337 21.24 5.0 126 7.97
1455-1 090 AM 10.5 208 13.12 26.3 347 21.87 4.5 130 8.20
- 095 AM 12.0 224 14.13 30.0 373 23.55 5.2 140 8.83
- 100 AM 13.4 238 15.02 33.6 397 25.02 5.7 149 9.38
Minimum and maximum flows are to ensure the Delta-T for each unit size falls within the 6 - 16°F range for proper unit control.