Specifications

39
Troubleshooting TM-M5LCY-I-2011
Unit Running Parameter
Parameter
Number
Parameter Description Unit/ range
00 Compressor Actual Rotation r/s
01 Compressor Target Rotation r/s
02 DC Bus Voltage VDC
03 Total Current (÷10) A
04 Outdoor Air Temperature °C
05 Outdoor Heat Exchanger Temperature °C
06 Compressor Discharge Temperature °C
07 Outdoor Heatsink Temperature °C
08 Indoor Air Temperature °C
09 Indoor Heat exchanger Temperature °C
10 EXV Opening Pulse
11 Outdoor fan speed W0 ~ W6
12 Horse power 15: 1.5hp
13 Software version (Production)
14 Software version (Development)
15 3 minutes count up stop timer
16 Communication stage 0~3
17 Indoor On/Off 0- Off, 1-ON
18 Delta D
19 Running mode 0-Fan, 1- Heat, 2-Cool
20 Startup up timer
21 Comp initial control ag ok
22 Fuzzy control Delta H
23 Comp freq set pointer
24 Comp stop pointer
25 Comp limit pointer
26 Comp limit speed Max r/s
27 Discharge high temp zone 0-Normal, Other-Active
28 High pressure zone 0-Normal, Other-Active
29 Current control zone 0-Normal, Other-Active
30 Oil return status 0-Normal, Other-Active
31 De-ice setting 0-Normal, Other-Active
32 Dew drop setting 0-Normal, Other-Active
33 Heatsink protection zone 0-Normal, Other-Active
34 Turbo setting 0-Normal, Other-Active
35 Silent setting 0-Normal, Other-Active
36 Low ambient zone 0-Normal, Other-Active
37 Defrost status 0-Normal, Other-Active
38 Pump down status 0-Normal, Other-Active
39 O/D capacity ag 0- Comp off, 1- Comp On
40 O/D output capacity In %
41 Target discharge temp
42 EXV control status 0-Initial , 1- Feedback
43 Indoor fan tap