Specifications
IM 1059-1 / Page 25 of 36
Figure 30: Temperature Sensor Wiring to MicroTech
III Unit Controller (669529001)
2-Way Motorized Isolation Valve
Figure 31: 2-Way Motorized Isolation Valve
Used in variable pumping type applications, the valve is
typically piped in the return water line. On a call for heat-
ing or cooling, the valve will open prior to the compressor
starting. The 24VAC valve actuator must be wired directly to
terminal block H8 on the MicroTech III controller. Seegure
23 on page 23 for wiring details.
The valve is rated for 300
psig (2070 kPa).
Figure 32: Normally Closed, Power Open Motorized
Valve
Figure 28: MicroTech
®
III Wall Sensor Details
.
Specifications
Thermistorresistance(10kΩ)
(Conforms to advance thermal products curve 2)
Ambient Temperature Limits:
Shipping and Storage: 40°F to 160°F (–40°C to 71°C)
Operating: 40°F to 140°F (4°C to 60°C)
Humidity: 5 to 95% RH, non-condensing
Locations: NEMA Type 1, Indoor only
Connections: Color Coded Leads
Wiring Sensors to the MicroTech III Controller
Figure 29: Temperature Sensor Wiring to MicroTech
III Unit Controller (Kit Part No.s 669529101,
669529201)
Fan Control
Slide Switch
Mode Control
Slide Switch
Status LED
(Green)
0 to 10 K ohm
Potentiometer
Tenant Override
Momentary Push Button Switch
4
.59"
Temperature
Sensor Terminals
MicroTech III Unit
Controller TB1 Terminals
MicroTech III Unit
Controller TB1 Terminals
Temperature
Sensor Terminals