Specifications

Page 12 of 32 / IM 1060-3
Additional Information For Initial Start-up
Standard Range units CCH
Units are designed to start-up in an ambient of 50°F (10°C),
with entering air at 50°F (10°C), with entering water at 70°F
(21°C),withbothairandwaterowratesusedintheISO
13256-1 rating test, for initial start-up in winter.
Note: This is not a normal or continuous operating
condition. It is assumed that such a start-up is for
the purpose of bringing the building space up to
occupancy temperature.
Geothermal Range units CCW
Geothermal heat pump units are designed to start-up in an
ambient of 40°F (5°C), with entering air at 40°F (5°C), with
enteringwaterat25°F(-4°C),withbothairandwateratow
rates used in the ISO 13256-1 rating test, for initial start-up
in winter.
Note: This is not a normal or continuous operating
condition. It is assumed that such a start-up is for
the purpose of bringing the building space up to
occupancy temperature.
Operating Voltages
115-60-1 ..................104 volts min.; 127 volts max.
208/230-60-1
...........197 volts min.; 253 volts max.
265-60-1
..................238 volts min.; 292 volts max.
230-50-1 ..................197 volts min.; 253 volts max.
460-60-3 ..................414 volts min.; 506 volts max.
380-50-3 ..................342 volts min.; 418 volts max.
575-60-3
..................515 volts min.; 632 volts max.
Note: Voltages listed are to show voltage range. However,
units operating with overvoltage and undervoltage for
extended periods of time will experience premature
component failure. Three phase system unbalance
should not exceed 2%.
Antifreeze Correction Factors
Table 1: Ethylene Glycol
10% 20% 30% 40% 50%
Cooling Capacity 0.9950 0.9920 0.9870 0.9830 0.9790
Heating Capacity 0.9910 0.9820 0.9770 0.9690 0.9610
Pressure Drop 1.0700 1.1300 1.1800 1.2600 1.2800
Table 2: Propylene Glycol
10% 20% 30% 40% 50%
Cooling Capacity 0.9900 0.9800 0.9700 0.9600 0.9500
Heating Capacity 0.9870 0.9750 0.9620 0.9420 0.9300
Pressure Drop 1.0700 1.1500 1.2500 1.3700 1.4200
Table 3: Methanol
10% 20% 30% 40% 50%
Cooling Capacity 0.9980 0.9720
Heating Capacity 0.9950 0.9700
Pressure Drop 1.0230 1.0570
Table 4: Ethanol
10% 20% 30% 40% 50%
Cooling Capacity 0.9910 0.9510
Heating Capacity 0.9950 0.9600
Pressure Drop 1.0350 0.9600