Specifications
Page 18 of 32 / IM 1060-3
Note:
  A random start delay time between 180 and 240 
seconds is generated at power up.
Figure 14: MicroTech III unit controller terminal locations
The IV/PR(H8) terminals of the 
MicroTech III unit controller are 
used for motorized valve / pump 
restart. This terminal passes a 
voltage signal whenever the 
unit compressor is turned on. 
This signal is detected by a 
pump restart relay providing a 
N.O. or N.C. set of contacts for 
heat pump loop circulation 
pump or motorized valve 
control. When used with a 
system control (by others), the 
relay operation accommodates 
turning off circulation pumps 
during unoccupied periods with 
a safety override dependent, at 
minimum, on WSHP’s need. 
The IV/PR(H8) terminals may 
be “daisy chained” between  
200 units.
Figure 15: Location of configuration jumpers on the 
MicroTech III unit controller