Specifications
Page 26 of 32 / IM 1060-3
Troubleshooting
The in and outs of R-410A
R-410A is a non-ozone depleting blend of two refrigerants 
-HFC-125andHFC-32inaftypercentmixture.R-410A
exhibits higher operating pressure and refrigeration capacity 
than R-22. R-410A is intended for use in new air conditioning 
applications that have traditionally been used HCFC-22 (R-
22). Due to higher capacity and pressure of R-410A, it must 
not be used in existing R-22 systems.
AlthoughR-410Aisnon-ammableatambienttemperature
and atmospheric pressure, it can become combustible under 
pressure when mixed with air.
Note:  R-410A should not be mixed with air under pressure 
for leak testing. Pressure mixtures of dry nitrogen and 
R-410A can be used for leak testing.
Lubrication
R-410A should be used only with polyester (POE) oil. The 
HFC refrigerant components in R-410A will not be compat-
ible with mineral oil or alkylbenzene lubricants. R-410A sys-
tems will be charged with the OEM recommended lubricant, 
ready for use with R-410A.
Charging
Due to the zeotropic nature of R- 410A, it should be charged 
as a liquid. In situations where vapor is normally charged into 
a system, a valve should be installed in the charging line to 
ashtheliquidtovaporwhilecharging.
 Make certain that the recycle or recovery equipment used is 
designed for R-410A. The pressure of R-410A refrigerant is 
approximately 60 percent greater than that of R-22. Pressure 
gauges require a range up to 800 PSIG high side and 250 
PSIG low side. Recovery cylinders require a 400 PSIG rating 
– do not put R-410A in a 300 PSIG rated cylinder.
  Recycle/recovery  equipment  must  be  designated  for  R-410A. 
R-410A pressure is greater than R-22. Improper equipment can 
cause severe injury or death.
   WARNING
Note:  Because a water source heat pump operates under a 
wide range of water and air temperatures, the values 
printed below are to be taken as suggested pressure 
and temperatures.) All Daikin McQuay water source 
heat pumps are designed for commercial use. The 
units are designed for the cooling mode of operation 
and fail safe to cooling. The reversing valve is 
energized for the heating mode of operation.
  Superheat  Head Pressure  Water Delta T
  8 to 14 degrees  335-355 PSIG  10° to 14°
Note:  All information above is based on ISO standard 
13256-1 and tested at these conditions.
General Maintenance
1.  Normal maintenance on all units is generally limited 
tolterchanges.Unitsareprovidedwithpermanently
lubricated motors and require no oiling even though oil 
caps may be provided.
2.  Filter changes are required at regular intervals. The time 
period between changes will depend upon the project 
requirements. Some applications such as motels produce 
a lot of lint from carpeting and linen changes, and will 
requiremorefrequentlterchanges.Checkltersat60-
dayintervalsfortherstyearuntilexperienceisacquired.
Iflightcannotbeseenthroughthelterwhenheldupto
sunlight or a bright light, it should be changed. A more 
critical standard may be desirable.
3.  The condensate drain pan should be checked annually and 
cleanedandushedasrequired.
4.  Record performance measurements of volts, amps, and 
water temperature differences (both heating and cooling). 
A comparison of logged data with start-up and other 
annual data is useful as an indicator of general equipment 
condition.
5.  Periodic lockouts almost always are caused by air or 
water problems. The lockout (shutdown) of the unit is 
a normal protective result. Check for dirt in the water 
system,waterowrates,watertemperatures,airowrates
(maybeadirtylter),andairtemperatures.Ifthelockout
occurs in the morning following a return from night 
setback, entering air below machine limits may be the 
cause.










