Specifications

IM 1060-3 / Page 5 of 32
Installation
Unit Location
1. Locate the unit in an area that allows for easy removal
ofthelterandaccesspanels.Leaveaminimumof18"
of clearance around the heat pump for easy removal,
and to perform routine maintenance, or troubleshooting.
Providesufcientroomtomakewater,electricalandduct
connections.
2. The contractor should make sure that adequate ceiling
panel access exists, including clearance for hanger
brackets,ductcollarsandttingsatwaterandelectrical
connections.
3. Allow adequate room below the unit for a condensate trap
and do not locate the unit above pipes.
4. Each unit is suspended from the ceiling by four threaded
rods. The rods are attached to the unit corners by a hanger
bracket through a rubber isolator.
Do not use rods smaller than shown in Figure 3. The rods must
be securely anchored to the ceiling or to the bar joists.
CAUTION
5. Each unit is furnished with a hanger kit. The kit is shipped
unassembled and includes hanger brackets, rubber
isolators, washers, bolts and lock washers. Lay out the
threaded rods per the dimension in Figure 3.
6. When attaching the hanger rods to the unit, a double nut
is recommended since vibration could loosen a single
nut. The installer is responsible for providing the hex nuts
when installing hanger rods.
Figure 3: Hanger Brackets - Sizes 072 thru 120
By Others
By McQuay
International
44"
(1118 mm)
42"
(1067 mm)
Fan
Assembly
2"
(51 mm)
2" (51 mm)
Airflow
Coil
Comp.
Comp.
80" (2032 mm)
Control
Box
82" (2082 mm)
5/8" Threaded Rod
(By Others)
7. Leave minimum 3" (76 mm) extra threaded rod below the
double nuts or minimum 3" (76 mm) clearance between
top of unit and ceiling above to facilitate top panel
removal for servicing.
Filter Access
Eachunitisshippedwitha2"lterbracketforsidelterre-
moval.Forbottomremovalpushthelterupintotopbracket
togainclearanceofbottombracketandremovethelter.
Also,asheetmetalductlterretainercanbefabricatedwhen
return air duct work is used.
Figure 4: Filter Rack/Return Air Duct Collar