Specifications
IM 1060-3 / Page 7 of 32
Table 2: 50 Hz Unit - Sheave Adjustment
Unit Size  Motor HP  RPM Range
  Factory  Motor Sheave
        Settings (RPM)  Position
  072  1½  756-901  786  4-Turns Open
  096  1½   720-860  858  1½-Turns Open
  120  3  756-902  815  3-Turns Open
Ductwork & Attenuation
Table 3: Filter Rack/Return Air Duct Collar Dimensions
 Unit Size  A  B  C  D  E
072
  45.12"  26.53"  3.20"  1.82"  1.50"
    (1146mm)  (674mm)  (81mm)  (46mm)  (38mm)
096
  55.12"  26.53"  3.20"  1.82"  1.50"
    (1400mm)  (674mm)  (81mm)  (46mm)  (38mm)
120
  55.12"  26.53"  3.20"  1.82"  1.50"
    (1400mm)  (674mm)  (81mm)  (46mm)  (38mm)
Discharge ductwork is normally used with these conditioners. 
Return air ductwork may also be required.
All ductwork should conform to industry standards of good 
practice as described in the ASHRAE Systems Guide.
Thedischargeductsystemwillnormallyconsistofaexible
connector at the unit, a transition piece to the full duct size, 
a short run of duct and a trunk duct teeing into a branch duct 
with discharge diffusers as shown in Figure 7. The transition 
piece must not have angles totaling more than 30° or severe 
loss of air performance can result. 
Do not connect the full duct size to the unit without using a 
transition piece down to the size of the discharge collar on the 
unit. With metal duct material, the sides only of the elbow and 
entirebranchductshouldbeinternallylinedwithacoustic-
brousinsulationforsoundattenuation.Glassberductboard
material is more absorbing and may permit omission of the 
canvas connector.
Asageneralrecommendation,theacousticbrousinsulation
should be at least 1/2 inch thick over the entire duct run (Fig-
ure 7).Forbettersoundattenuation,linethelastvediam-
eters of duct before each register with a one-inch thick sound 
blanket. Elbows, tees and dampers can create turbulence or 
distortionintheairow.Placeastraightlengthofduct,5to
10timestheductwidth,beforethenextttingtosmoothout
airow.Diffusersthatarelocatedinthebottomofatrunk
duct can also produce noise. For this same reason, volume 
control dampers should be located several duct widths up-
stream from an air outlet.
For Hotel, Motel, Dormitory or Nursing Home applications 
that use a single duct discharge, a velocity of 500 to 600 fpm 
is suggested. These applications typically have static pres-
sures as low as 0.05 inches of water and duct lengths approxi-
mately six feet in length. The discharge duct must be fully 
lined and have a square elbow without turning vanes. Return 
airductworkcanbeconnectedtothestandardlterrack.See
Figure 4 on page 5(sidelterremovalshown).Thelter
rackcanbeinstalledforbottomlterremovalorsidelter
removalbylocatingthebrackets.Forsidelterremovalthe
brackets should be located on the bottom, left side, and top. 
Forbottomlterremovalthebracketsshouldbemountedon
the left side top and right side with the spring clips supporting 
thelter.
Do not use sheet metal screws directly into the unit cabinet 
for connection of supply or return air ductwork, especially 
return air ductwork which can hit the drain pan or the air coil. 
Return air for these applications should enter through a “low” 
sidewallltergrilleandrouteupthestudspacetoaceiling
plenum. For horizontal heat pumps mounted from the ceiling, 
an insulated return plenum is sometimes placed at the return 
air opening to further attenuate line-of-sight sound transmis-
sion through return openings.
Figure 7: Suggested Supply Ducting per ASHRAE and SMACNA Publications
Flexible Connector
Acoustic/Thermal 
Lining
Two 90° Turns
(Ductwork Sized Based on Airow)
Diffuser
Diffuser
Acoustic/Thermal Lining
3ft. (.9m) to 5ft. (1.5m)
Ductwork Supported 
Independent of Unit










