Specifications
Page 8 of 32 / IM 1060-3
Figure 8: Suggested Return Ducting per ASHRAE and SMACNA Publications
Two 90° Turns Prior to the Intake
(Ductwork Sized Based on Airow)
Flexible Connector
Acoustic/Thermal 
Lining 10ft. (3 meters)
Ductwork Supported 
Independent of Unit
Acoustic/Thermal 
Lining
Acoustic/Thermal 
Lining
Return Air Intake 
Located 
Away from the 
Unit Blower
Flexible Connector
Ventilation Air
Ventilation may require outside air. The temperature of the 
ventilation air must be controlled so that mixture of outside 
air and return air entering the conditioner does not exceed 
conditioner application limits. It is also typical to close off 
the ventilation air system during unoccupied periods (night 
setback).
The ventilation air system is generally a separate building 
subsystem with distribution ductwork. Simple introduction of 
the outside air into each return air plenum chamber reason-
ably close to the conditioner air inlet is not only adequate, but 
recommended. Do not duct outside air directly to the condi-
tionerinlet.Providesufcientdistanceforthoroughmixingof
outside and return air. See "Operating Limits" on page 11.
Electrical Data
General
1.  Verify the compatibility between the voltage and phase 
of the available power and that shown on the unit serial 
plate. Line and low voltage wiring must comply with local 
codes or the National Electrical Code, whichever applies.
2. Applycorrectlinevoltagetotheunit.A7⁄8"(22mm)hole
and/ora1-1⁄8"(29mm)knockoutissuppliedontheside
of the unit. A disconnect switch near the unit is required 
by code. Power to the unit must be sized correctly and 
have dual element (Class RK5) fuses or an HACR circuit 
breaker for branch circuit overcurrent protection. See the 
nameplate for correct ratings.
3.  Three phase 50 cycle units, 380/50-3, require a neutral 
wire for 230/50-1 power to the fan circuit.
4.  Connect the thermostat/subbase wiring with the power 
“off ” to the unit.
5.  Field supplied relays installed on the input terminals 
W1, W2, Y1, Y2 or G may introduce electrical noise. 
Never install relay coils in series with the inputs.
230-Volt Operation
All 208/230-volt three-phase units are factory wired for 208-
volt operation. For 230-volt operation, the line voltage tap on 
the 24-volt transformer must be changed. Disconnect and cap 
the red lead wire and interchange it with the orange lead wire 
on the primary of the 24-volt transformer.
Table 4: Electrical Data
Unit Size  Voltage/Hz/Phase
Fan
   Compressor 1 
  Compressor 2
  Fan Motor  Total Unit 
Minimum
Minimum 
Maximum
Motor (HP)
RLA LRA
RLA  LRA
  FLA  FLA  Voltage  Circuit Amps  Fuse Size
88.0
44.0
30.0
46.0
83.1
41.0
33.0
43.0
110.0
52.0
38.9
51.5
5.6
2.8
2.3
3.4
5.6
2.8
2.0
3.4
9.5
4.5
3.4
4.8
14.7
6.6
4.6
6.6
15.3
6.9
5.4
6.8
17.4
8.6
6.5
8.6
14.7
6.6
4.6
6.6
15.3
6.9
5.4
6.8
17.4
8.6
6.5
8.6
88.0
44.0
30.0
46.0
83.1
41.0
33.0
43.0
110.0
52.0
38.9
51.5
208/230-60-3
460-60-3
575-60-3
380-50-3
208/230-60-3
460-60-3
575-60-3
380-50-3
208/230-60-3
460-60-3
575-60-3
380-50-3
072
096
120
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
3
3
3
3
35.0
16.0
11.5
16.6
36.2
16.6
12.8
17.0
44.3
21.7
16.4
22.0
187.0
416.0
520.0
342.0
187.0
416.0
520.0
342.0
187.0
416.0
520.0
342.0
38.7
17.7
12.7
18.3
40.0
18.3
14.2
18.7
48.7
23.9
18.0
24.2
50
20
15
20
50
25
15
25
60
30
20
30










