Specifications
IM 1049-4 / Page 13 of 36
Table 2: MicroTech III unit controller terminals locations 
and descriptions
  H1 - 1  24  24 VAC Power Input
  H1 - 2  C  24 VAC Common
  H2 - 1  SL1  Fan Output - Switched L1
  H2 - 2    Blank Terminal
  H2 - 3  N  Fan Neutral 
  H3 - 1  HP1-1  High Pressure Switch 1 Input Terminal 1
  H3 -2  HP1-2  High Pressure Switch 1 Input Terminal 2
  H4 - 1    Discharge Air Temp Common
  H4 - 2    Discharge Air Temp Signal
  H4 - 3    Leaving Water Temp Common
  H4 - 4    Leaving Water Temp Signal
  H5 - 1  1  I/O Exp Module Common (Gnd)
  H5 - 2    I/O Exp Module Common (Gnd)
  H5 - 3    I/O Exp Module +5 VDC
  H5 - 4    I/O Exp Module SPI CE1
  H5 - 5    I/O Exp Module SPI CLK
  H5 - 6    I/O Exp Module SPI OUT
  H5 - 7    I/O Exp Module SPI IN
  H5 - 8    I/O Exp Module +12 VDC
  H5 - 9    I/O Exp Module 24 VAC
  H5 - 10    I/O Exp Module 24 VAC
  H5 - 11    Spare
  H5 - 12    Spare
  H6 - 1  1  Condensate Overow Signal Input
  H6 - 2    Low Temp 1 Sensor Common
  H6 - 3    Low Temp 1 Sensor Signal
  H6 - 4    Low Pressure Switch 1 Source Voltage
  H6 - 5    Low Pressure Switch 1 Signal
  H6 - 6    Reversing Valve 1 Common
  H6 - 7    Reversing Valve 1 Output 
  H7 - 1  1  Dummy Terminal
  H7 - 2    Dummy Terminal
  H7 - 3    Red LED Output
  H7 - 4    Green LED Output
  H7 - 5    Yellow LED Output
  H7 - 6    Red-Green-Yellow LED Common
  H8 - 1  1  Isolation Valve/Pump Request Relay N/O
  H8 - 2    Isolation Valve/Pump Request Relay N/C
  H8 - 3    24 VAC Common
  H9 - 1  1  Return Air Temperature Signal
  H9 - 2    Return Air Temperature Common
  TB1 - 1  1  Room Sensor LED Output
  TB1 - 2  2  Fan Mode / Heat-Cool-Auto Input
  TB1 - 3  3  Setpoint Adjust Input
  TB1 - 4  4  Room Temperature Sensor / Tenant Override
  TB1 - 5  5  DC Signal Common
  Test-1  R  24 VAC
  Test-2  W2  Heat Stage 2 Input
  Test-3  W1  Heat Stage 1 Input
  Test-4  Y2  Cool Stage 2 Input
  Test-5  Y1  Cool Stage 1 Input
  Test-6  G  Fan 
  TB2 - 1  R  24 VAC 
  TB2 - 2  A  Alarm Output
  TB2 - 3  W2  Heat Stage 2 Input
  TB2 - 4  W1  Heat Stage 1 Input
  TB2 - 5  Y2  Cool Stage 2 Input
  TB2 - 6  Y1  Cool Stage 1 Input
  TB2 - 7  G  Fan Input
  TB2 - 8  O  Tenant Override Input
  TB2 - 9  C  24 VAC Common 
  TB3 - 1  E  Mark IV Emergency Shutdown Input
  TB3 - 2  U  Mark IV Unoccupied/Occupied Input
  L1 - 1  L1 - 1  Line Voltage Terminal 1
  L1 - 2  L1 - 2  Line Voltage Terminal 2
  L1 - 3  L1 - 3  Line Voltage Terminal 3
  N1  N1  Neutral Terminal 1
  N2  N2  Neutral Terminal 2
  N3  N3  Neutral Terminal 3
Table 3: Configuration jumper settings
  Jumper  Description  Options
JP1  Mode
  Open for normal operation mode
      Shorted for service/test operation mode
  JP2  Fan operation only applies to  Open for continuous fan operation
    network controls  Shorted for cycling fan operation
JP3  Freeze protection
  Open for water freeze protection
      Shorted for antifreeze protection
  JP4  Future spare  Future spare
  JP5  Set point adjustment range only  Open for adjustment range of -3.0° to +3.0° F 
    applies to network controls with a  Shorted for 50° to 90° F adjustment range
    room temperature sensor   
JP6  Room control type
  Open for thermostatic room control
      Shorted for room temperature sensor control, MicroTech III only
  JP7  Future spare  Future spare
  JP8  Future spare  Future spare