Specifications
IM 1049-4 / Page 15 of 36
MicroTech® III Unit Controller
TheMicroTechIIIUnitControllerincludesbuilt-infeatures
such as random start, compressor time delay, shutdown,
condensateoverowprotection,defrostcycle,brownout,and
LED/faultoutputs.Table4 shows the LED and fault output
sequences.
Theunithasbeendesignedforoperationwithamicroelec-
tronicwallthermostatselectedbythemanufacturer.Donot
operate the unit with any other type of wall thermostat.
Eachunithasaprintedcircuitboardcontrolsystem.Thelow
voltage output from the low voltage terminal strip is AC volt-
agetothewallthermostat.RisA/Cvoltageoutputtothewall
stat.
The24voltlowvoltageterminalstripissetupsoR-G
energizesthefan,R-Y1energizesthecompressorforcool-
ingoperation,R-W1energizesthecompressorandreversing
valveforheatingoperation.Thereversingvalveisenergized
intheheatingmode.Thecircuitboardhasafaninterlock
circuittoenergizethefanwheneverthecompressorisonif
the thermostat logic fails to do so.
The output to the wall stat is AC current. Terminal (R) on the
wallstatcanbeconnectedtoterminal(R)onthePCboardfor
AC voltage.
R = AC current
R to G = fan only
R to Y1 = cooling
R to W1 = heat
TheMicroTechIIIunitcontrollerhasalockoutcircuittostop
compressor operation if any one of its safety switches opens
(highpressureswitchandlowpressureswitchonunitsizes
024 through 060). If the low temperature switch opens, the
unit will go into the cooling mode for 60 seconds to defrost
anyslushinthewater-to-refrigerantheatexchanger.After60
secondsthecompressorislockedout.Ifthecondensatesen-
sordetectsalleddrainpan,thecompressoroperationwill
besuspendedonlyinthecoolingmode.Theunitisresetby
opening and closing the disconnect switch on the main power
supply to the unit in the event the unit compressor opera-
tionhasbeensuspendedduetolowtemperature(freezestat)
switch, high pressure switch, or low pressure switch on unit
sizes048thru060.Theunitdoesnothavetoberesetona
condensateoverowdetection.
The MicroTech III unit controller fault output sends a signal
to an LED on a wall thermostat. Table4 shows for which
functionsthefaultoutputis“on”(sendingasignaltothe
LED).
Table 4: MicroTech III unit controller LED & fault outputs
Mode / Fault
Status LED’s Thermostat Alarm Light
Yellow Green Red Output-Terminal “A”
Occupied, Bypass,
Standby, or Tenant Off On Off Energized
Override
Unoccupied On On Off Energized
Condensate Overow On Off Off De-engergized
High Pressure 1 Fault Off Off Flash De-energized
Low Pressure 1 Fault Off Off On De-energized
Low Temperature 1 Fault Flash Off Off De-energized
Brownout
Off Flash Off De-energized
Emergency Shutdown Off Flash Off De-energized
Room/Return Air or Low
Flash Flash On De-engergized
Temp Sensor 1 Failure
Service Test Mode
On On Off De-energized
Enabled
1
Serial EEPROM
On On On De-energized
Corrupted
Network “Ofine”
Off Off Off De-enegized
Received
1
Compressor relay/compressor terminal is labeled COMP, switched line of the
same electric input as any of the L1 terminals.
Remote Reset Feature
The Remote Reset feature provides the means to remotely
resetautomaticlockoutsgeneratedbyhigh-pressureand/
orlow-temperature(inheating)faults.WhentheMicroTech
IIIunitcontrollerisinautomaticlockoutduetooneofthese
faults,andthecauseofthefaultconditionhasbeenalleviated,
energizingtheO-terminalfor10secondsormorewillforce
theMicroTechIIIunitcontrollertoclearthelockout.Aunit
powercyclecanalsobeusedtoclearanautomaticlockoutif
theconditionscausingthefaulthavebeenalleviated.
TheIntelligentresetfeaturehelpstominimizenuisancetrips
ofautomaticresetlockoutscausedbyhigh-pressureand/or
low-temperature(inheating)faults.Thisfeatureclearsfaults
thersttwotimestheyoccurwithina24-hourperiodand
triggersanautomaticlockoutonthe3rdfault.Theretrycount
isresettozeroevery24hours.
TheMicroTechIIIunitcontrollerhasbuilt-innightsetback
operation.A“grounded’signaltothe“U”terminalonTB3
of the unit control puts the unit into the unoccupied mode for
nightsetbackoperation.Fanoperationterminatesandunit
control will only respond to signal at the W2 terminal. Day-
timeheatingandcoolingoperationislockedout.+24VACto
W2energizesthecompressorandreversingvalveforheating
operation.Nightsetbackoperationcanbeoverriddenfortwo
hoursbyenergizingtheOontheTB2terminaloftheunit
control for 3 seconds. Day thermostat setpoints then control
the heating and cooling operation. The MicroTech III unit
controller also accommodates shutdown operation on receipt
ofa“grounded”signaltothe“E”input,respectively,onTB3
input terminal of the unit control.