Specifications
Page 26 of 36 / IM 1049-4
Thermostat Connections
Figure 33: 7-Day Programmable Electronic Thermostat
(P/N 668375301)
MicroTech III Unit Control Board
Low Voltage Terminal Strip (Circuit 1)
W1
Y1
W2
Y2
G
Thermostat
Terminals
-
C
TB2
24VAC
Alarm Output
Heat 2
Heat 1
Cool 2
Cool 1
Fan
Tenant Override
24VAC Common
C
O
G
Y1
Y2
W1
W2
A
R
+
R
Ferrite Core Suppressor
(See NOTICE)
Notes: IncludesThermostatandWallPlate.
Refertotheinstallation,operation&applicationguide
(LIA265)forthermostat668375301.
Figure 34: Non-Programmable Electronic Thermostat
(P/N 668375401)
MicroTech III Unit Control Board
Low Voltage Terminal Strip (Circuit 1)
W1
Y1
W2
Y2
G
Thermostat
Terminals
-
C
TB2
24VAC
Alarm Output
Heat 2
Heat 1
Cool 2
Cool 1
Fan
Tenant Override
24VAC Common
C
O
G
Y1
Y2
W1
W2
A
R
+
R
O
Ferrite Core Suppressor
(See NOTICE)
*Override (Optional)
Notes: IncludesThermostatandWallPlate.
Refertotheinstallation,operation&applicationguide
(LIA266)forthermostat668375401.
* When remote reset of a lockout condition is required
at the wall thermostat, it will be necessary to utilize a
conductorbetweenterminal"O"onthewallthermostat
toterminal"O"ontheMicroTechIIIunitcontroller(non-
programmablestatonly).
For 50Hz units, it may be necessary to install a Ferrite Core
Noise Suppresor on the thermostat cord cable where it enters
the unit “Low Voltage” opening (see Figure 35). The Installer
is responsible for checking local codes to determine if a Noise
Suppressor is necessary to meet CE compliance.
NOTICE
Figure 35: Ferrite Core Noise Suppressor on Thermostat
Cord Cable
Ferrite Core Noise Suppressor
on thermostat cable
Low voltage, themostat wiring entry
Optional Remote Sensor (P/N 66720401)
1. Remove cover from remote sensor housing.
2. Select an appropriate location for mounting the remote
sensor.
3. Mount remote sensor unit using hardware provided.
4. Installtwostrandshieldedwirebetweenremotesensor
andthermostat.Shieldedwiremustbeused.
Do not run remote sensor wire in conduit with other wires.
• Wire1shouldrunbetweentheS1terminalonthe
thermostat and the S1 terminal on the remote sensor
• Wire2shouldrunbetweentheS2terminalonthe
thermostat and the S2 terminal on the remote sensor
• ConnecttheshieldingofthewiretotheS2terminalon
the thermostat
5. Disablethemainsensor(R12)onthethermostatby
cuttingitfromthecircuitboard.
Figure 36: Optional Remote Sensor Wiring
S1
S2
S1
S2
Cut R12 from
circuit board
Remote Sensor
Thermostat
Wire 1
Wire 2