Specifications
IM 1049-4 / Page 29 of 36
Troubleshooting
The in and outs of R-410A
R-410Aisanon-ozonedepletingblendoftworefrigerants
-HFC-125andHFC-32inaftypercentmixture.R-410A
exhibitshigheroperatingpressureandrefrigerationcapacity
thanR-22.R-410Aisintendedforuseinnewaircondition-
ingapplicationsthathavetraditionallybeenusedHCFC-22
(R-22).DuetohighercapacityandpressureofR-410A,it
mustnotbeusedinexistingR-22systems.
AlthoughR-410Aisnon-ammableatambienttemperature
andatmosphericpressure,itcanbecomecombustibleunder
pressure when mixed with air.
Note: R-410Ashouldnotbemixedwithairunderpressure
forleaktesting.Pressuremixturesofdrynitrogenand
R-410A can be used for leak testing.
Lubrication
R-410Ashouldbeusedonlywithpolyester(POE)oil.The
HFCrefrigerantcomponentsinR-410Awillnotbecompat-
iblewithmineraloiloralkylbenzenelubricants.R-410Asys-
temswillbechargedwiththeOEMrecommendedlubricant,
readyforusewithR-410A.
Charging
DuetothezeotropicnatureofR-410A,itshouldbecharged
as a liquid. In situations where vapor is normally charged
intoasystem,avalveshouldbeinstalledinthechargingline
toashtheliquidtovaporwhilecharging.
Makecertainthattherecycleorrecoveryequipmentusedis
designedforR-410A.ThepressureofR-410Arefrigerantis
approximately60percentgreaterthanthatofR-22.Pressure
gauges require a range up to 800 PSIG high side and 250
PSIG low side. Recovery cylinders require a 400 PSIG rating
–donotputR-410Aina300PSIGratedcylinder.
Recycle/recovery equipment must be designated for R-410A.
R-410A pressure is greater than R-22. Improper equipment can
cause severe injury or death.
WARNING
Note: Because a water source heat pump operates under a
wide range of water and air temperatures, the values
printed below are to be taken as suggested pressure
andtemperatures.)AllDaikinMcQuaywatersource
heat pumps are designed for commercial use. The
units are designed for the cooling mode of operation
and fail safe to cooling. The reversing valve is
energized for the heating mode of operation.
Superheat Head Pressure Water Delta T
8to14degrees 335-355PSIG 10°to14°
Note: AllinformationaboveisbasedonISOstandard
13256-1andtestedattheseconditions.
General Maintenance
1. Normal maintenance on all units is generally limited
tolterchanges.Unitsareprovidedwithpermanently
lubricatedmotorsandrequirenooilingeventhoughoil
capsmaybeprovided.
2. Filter changes are required at regular intervals. The time
periodbetweenchangeswilldependupontheproject
requirements. Some applications such as motels produce
a lot of lint from carpeting and linen changes, and will
requiremorefrequentlterchanges.Checkltersat60-
dayintervalsfortherstyearuntilexperienceisacquired.
Iflightcannotbeseenthroughthelterwhenheldupto
sunlightorabrightlight,itshouldbechanged.Amore
criticalstandardmaybedesirable.
3. Thecondensatedrainpanshouldbecheckedannuallyand
cleanedandushedasrequired.
4. Record performance measurements of volts, amps, and
watertemperaturedifferences(bothheatingandcooling).
Acomparisonofloggeddatawithstart-upandother
annual data is useful as an indicator of general equipment
condition.
5. Periodiclockoutsalmostalwaysarecausedbyairorwater
problems.Thelockout(shutdown)oftheunitisanormal
protectiveresult.Checkfordirtinthewatersystem,water
owrates,watertemperatures,airowrates(maybea
dirtylter),andairtemperatures.Ifthelockoutoccurs
inthemorningfollowingareturnfromnightsetback,
enteringairbelowmachinelimitsmaybethecause.