Specifications
Page 4 of 36 / IM 1049-4
Filter Access
Eachunitisshippedwithalterbracketforsidelterremov-
al.Forbottomremovalpushthelterupintotopbracketto
gainclearanceofbottombracketandremovethelter.Also,
asheetmetalductlterretainercanbefabricatedwhenreturn
airductworkisused.
Figure 1: Hanger bracket location dimensions - sizes 007
thru 060
B
Coil
Airflow
E
C
D
Comp
Control
Box
Fan
Assembly
A
Table 1: Hanger bracket dimensions
UNIT DIMENSIONS (mm)
SIZE A B C D E
007 – 009 445 864 559 864 508
012 445 1016 559 1016 508
015 – 024 445 1067 559 1067 508
030 – 036 470 1168 584 1168 533
042 – 070 648 1321 762 1321 711
UNIT DIMENSIONS (INCHES)
SIZE A B C D E
007 – 009 17.5 34 22
34
20
012 17.5 40 22
40
20
015 – 024 17.5 42 22 42 20
030 – 036 18.5 46 23 46 21
042 – 070 25.5 52 30 52 28
Figure 2: Hanger bracket detail - sizes 007 thru 060
3/8" Threaded Rod
(By Others)
Vibration Isolator
Washer
Hex Nuts
(By Others)
Bolt & Lock
Washer
Unit Location
1. Locate the unit in an area that allows for easy removal
ofthelterandaccesspanels.Leaveaminimumof18"
of clearance around the heat pump for easy removal
of the entire unit (if necessary), and to perform routine
maintenance,ortroubleshooting.Providesufcientroom
tomakewater,electricalandductconnections.
2. Thecontractorshouldmakesurethatadequateceiling
panel access exists, including clearance for hanger
brackets,ductcollarsandttingsatwaterandelectrical
connections.
3. Allowadequateroombelowtheunitforacondensatetrap
anddonotlocatetheunitabovepipes.
4. Eachunitissuspendedfromtheceilingbyfourthreaded
rods.Therodsareattachedtotheunitcornersbyahanger
bracketthrougharubberisolator.
Do not use rods smaller than shown in Figure 2. The rods must
be securely anchored to the ceiling or to the bar joists.
CAUTION
5. Eachunitisfurnishedwithahangerkit.Thekitis
shippedunassembledandincludeshangerbrackets,
rubberisolators,washers,boltsandlockwashers.Layout
the threaded rods per the dimension in Figure 1 and the
detail in Figure 2.
6. Whenattachingthehangerrodstotheunit,adoublenut
isrecommendedsincevibrationcouldloosenasingle
nut.Theinstallerisresponsibleforprovidingthehexnuts
when installing hanger rods.
7. Leaveminimum3"(76mm)extrathreadedrodbelowthe
doublenutsorminimum3"(76mm)clearancebetween
topofunitandceilingabovetofacilitatetoppanel
removal for servicing.