Specifications

Page 6 of 36 / IM 1049-4
6. Liftthefanassemblyoutrotatingit180degreesand
position it within the opening at the end of the unit (Figure
5). With the fan motor in the end discharge position the
fanandhousingorientationistop-horizontal.Astraight
airdischargearrangement,thehousingisinthebottom-
horizontalorientation.
7. Securethefanassemblytotheunitframewiththescrews
removed previously.
Figure 5: Lift out the fan assembly, turn 90 degrees and rotate 180 degrees
Remove screws securing the fan assembly to
the cabinet. Note bottom-horizontal orientation
of fan assembly
Position the fan assembly in the
end opening with the fan in the “top-
horizontal” orientation
Rotate the Fan Assembly 180º
Straight Discharge Arrangement
(Bottom-Horizontal) Orientation
End Discharge
Arrangement
(Top-Horizontal) Orientation
8. Reinstall the access panel in the fan motor access opening
(Figure 6).
9. Reinstall the top panel and secure with screws removed
previously.
Note: If installed correctly the fan motor should be
accessible when the fan motor access panel is
removed.
Figure 6: Reinstall the top and access panel
Reinstall Access Panel to Fan Motor
Reinstall Top
Completed End Discharge Assembly