Specifications
IM 1049-4 / Page 9 of 36
Figure 11: CCH, CCW sizes 007 thru 060 (factory wired)
Figure 12: CCH, CCW Sizes 042 thru 060 (Factory wired, 
460 volt motor only)
Piping
1. Allunitsshouldbeconnectedtosupplyandreturnpiping
inatwo-pipereversereturnconguration.Areverse
returnsystemisinherentlyself-balancingandrequires
onlytrimbalancingwheremultiplequantitiesofunits
withdifferentowandpressuredropcharacteristics
existinthesameloop.Checkforproperwaterbalance
bymeasuringdifferentialtemperaturereadingacross
thewaterconnections.Toinsureproperwaterow,the
differentialowshouldbe10°Fto14°F(5°Cto8°C)for
units in cooling mode.
 Adirectreturnsystemmayalsoworkacceptably,but
properwaterowbalancingismoredifculttoachieve
and maintain.
2. Thepipingcanbesteel,copperorPVC.
3. Supplyandreturnrunoutsusuallyjointheunitviashort
lengthsofhighpressureexiblehosewhicharesound
attenuatorsforbothunitoperatingnoiseandhydraulic
pumping noise. One end of the hose should have a swivel 
ttingtofacilitateremovalforservice.Hardpipingcan
alsobebroughtdirectlytotheunit.Thisoptionisnot
recommendedsincenovibrationornoiseattenuationcan
beaccomplished.Thehardpipingmusthaveunionsto
facilitate unit removal. See Figure 13 for typical piping 
setup.
Electrical Data
General
1. Verifythecompatibilitybetweenthevoltageandphase
oftheavailablepowerandthatshownontheunitserial
plate. Line and low voltage wiring must comply with 
local codes or the National Electrical Code, whichever 
applies.
2. Applycorrectlinevoltagetotheunit.A7⁄8"(22mm)hole
and/ora1-1⁄8"(29mm)knockoutissuppliedontheside
of the unit. A disconnect switch near the unit is required 
bycode.Powertotheunitmustbesizedcorrectlyand
have dual element (Class RK5) fuses or an HACR circuit 
breakerforbranchcircuitovercurrentprotection.Seethe
nameplate for correct ratings.
3. Threephase50cycleunits,380/50-3,requireaneutral
wirefor230/50-1powertothefancircuit.
4. Connectthethermostat/subbasewiringwiththepower
“off”totheunit.
5.  Field supplied relays installed on the input terminals 
W1, W2, Y1, Y2 or G may introduce electrical noise. 
Never install relay coils in series with the inputs.
230 Volt Operation
All208-230voltsingle-phaseandthree-phaseunitsarefacto-
ry wired for 208 volt operation. For 230 phase operation, the 
linevoltagetaponthe24volttransformermustbechanged.
Disconnect and cap the red lead wire and interchange it with 
the orange lead wire on the primary of the 24 volt transform-
er(sizes007-060).
Fan Assembly
Allfanmotorsaremulti-speedPSCoroptionalECM(sizes
015-070)typewithintegralmountingbracketsandther-
mal overload protection. The motor is isolated from the 
fanhousingforminimumvibrationtransmission.PSCFan
motorshaveaterminalstriponthemotorbodyforsimple
motorspeedchangewithoutgoingbacktothecontrolbox.
Tochangefanmotorspeedtohighonsize015through048,
interchangetheredwirewiththeblackwire.Forlowspeed,
sizes012,024,030,036,042and060,interchangetheblack
wire with the red wire. To change the 460 volt motor from 
hightolowspeed,interchangeBlackandRedwires,then
addjumperbetweenBlackandBluewires.Allthefan/motor
assemblieshavearemovableoriceringonthehousingto
accommodate motor and fan wheel removal without discon-
nectingtheductwork.Thefanhousingprotrudesthroughthe
cabinetallowingadequatematerialforconnectionofexible
duct. Each model unit is shipped from the factory for maxi-
mum performance and minimum sound requirements. Fan 
soundlevelsandperformancecanbeaffectedbyexternal
static pressure. 