Catalog Air-Cooled Chiller (R410A Inverter Series) Models: M5ACV 030 CR M5ACV 055 CR M5ACV 075 CR M5ACV 100 CR M5ACV 135 CR M5ACV 210 CR M5ACV-2009
Table of Contents Nomenclature .................................................................................................................... 1 - Product Line up Features ............................................................................................................................ 3 Application Information ......................................................................................................
Nomenclature Production spec variation Type of ref.
Wired handset WCCH Gold Fin Terminal block Scroll compressor 030CR AXAA X X X X X X X 055CR FXAA X X X X X X X 075CR FXAA X X X X X X X 100CR FXAA X X X X X X X X 135CR FXAA X X X X X X X X 210CR FXAA X X X X 2 X X X Brass adaptor BSPT 1 1/2 Brass adaptor BSPT 1 Brass adaptor BSPT 1 1/4 Pump only EXV (Normal & Inverter circuit) EXV (Inverter circuit) Capillary tube (Normal & Inverter circuit) Capillary tube (Normal circuit) Isolator Switch Nomenclature M5ACV Heat pump model Product Line
Features True Dual Circuits BPHE The true dual BPHE puts the secondary circuit (water) in contact with 2 primary circuits (refrigerant). So even if one primary circuit is shut off, each secondary channel is still in contact with a primary channel. Inverter Compressor Inverter compressor is programmed to run at the optimum speed, which is regulated by the input frequency as it can varies according to the heat load requirement.
Application Information Refrigerant Circuit Diagram Model : M5ACV 030CR M5ACV030CR Water / Refrigerant Circuit Diagram EXV FILTER IL ILTER DRIER BPHE WATER A ATER OUT CHARGE COMPENSAT A OR AT SUCTION ACCUMULAT A OR AT COMPRESSOR WATER WA ATER IN P WA WA ATER TER PUMP EXPANSION PANSION T P TANK ANK Model : M5ACV 055/075CR M5ACV055CR Water / Refrigerant Circuit Diagram FILTER IL ILTER DRIER EXV BPHE WATER A ATER OUT LIQUID RECEIVER SUCTION ACCUMULAT A OR AT COMPRESSOR WA WA ATER TER PUMP P EXPA
Model : M5ACV 100CR FIN TUBE HEAT EXCHANGER (SYSTEM 1) M5ACV 100CR Refrigerant Circuit Diagram HEATING CAP TUBE 4-WAY VALVE FILTER DRIER CHECK VALVE FIN TUBE HEAT EXCHANGER (SYSTEM 2) 4-WAY VALVE FILTER DRIER EXV VARIABLE SPEED COMPRESSOR COOLING CAP TUBE SUCTION ACCUMULATOR LIQUID RECEIVER COMPRESSOR CHECK VALVE SUCTION ACCUMULATOR LIQUID RECEIVER EXPANSION TANK WATER OUT WATER IN P WATER PUMP Model : M5ACV 135CR FIN TUBE HEAT EXCHANGER (SYSTEM 1) M5ACV 135CR Refrigerant Circuit Diagr
Model : M5ACV 210CR FIN TUBE TUBE HEAT FIN EXCHANGER HEAT(SYSTEM EXCHANGER 1) (SYSTEM 1) TWIN TWIN TUBEJOINT JOINT TUBE M5ACV 210CR Refrigerant Circuit Diagram 4-WAY VALVE 4-WAY VALVE OIL OIL SEPARATOR SEPARATOR OIL OIL SEPARATOR SEPARATOR FILTER FILTER DRIER DRIER FILTER FILTER DRIER DRIER CHECK VALVE VALVE CHECK CHECK VALVE VALVE FIN TUBE TUBE HEATFIN EXCHANGER HEAT(SYSTEM EXCHANGER 2) (SYSTEM 2) 4-WAY VALVE 4-WAY VALVE EXV EXV EXV EXV OIL OIL RETURN RETURN TUBE TUBE COMPRESSOR COMPRESSOR
Chiller Panel Controller 1. Safety Consideration Only specially trained and technicians and installers are authorized to install and service this equipment. 1.1 General Installation Recommendations • Only supply DC voltage (9-17V, typically 12V, maximum current 200mA) as a power source to the device. • Input contact voltage supply should limit to 12VDC or 24VAC. • Isolated all the low voltage wiring (communication bus, etc) from high voltage power supply wiring. 2. General Description 2.
3. Hardware Description Legend 1&2 3 4 5 6 7 8 9 10 Navigation key Execute instruction key Cancel instruction key Switching to heat mode shortcut key Switching to cool mode shortcut key Toggle ON/OFF shortcut key Show alarm key Graphical LCD display ON/OFF indicator Legend 1&2 3 4 5 6 7 8 9 10 Chiller terminal unit connection Not available CMOS reset jumper (JH2) Chiller bus resistor or configuration (JH3) Not available Not available Not available Not available Backup battery 3.
4. Installation 4.1 Chiller Bus Supported up to 50 units of Chiller Chiller 0 Chiller Panel 0 (Master) Chiller 1 Chiller 2 5 way wire (CN8) Chiller Communication bus Chiller Panel 1 (Slave) Chiller Network Chiller panel needs to be energized with +12Vdc. The 5 way wires that provided is once on the easiest solution to establish a communication between the panel and chiller main board (CN8-JP13).
4.2 Others Configuration • • • JH2 in chiller panel should let it open (put the jumper header on one pin only) all the time unless user need to do CMOS reset to that particular panel. JH3 should let it open (put the jumper header on one pin only) all the time as well. Remember to put in the coin cell battery on the panel. Without the backup battery, the panel will always reset the time to 12:00am, 1st Jan 2000. 4.
5. Software Description 5.1 Introduction The Chiller Panel Controller can be used to control / display the status of Chiller.
5.
5.3 Chiller Menu Structure 5.3.1 Summary Pages There are 4 pages in [Summary Pages]. Press UP or DOWN for page scrolling. Press ENTER to go to [Main Menu]. Time and date are shown on top of each page. Beside that, the bottom of each page shows current control unit of the Chiller.
5.3.2 Main Menu Press ENTER in [Summary Pages] to go into this menu MAIN MENU Operating Menu Setting Menu Timer Menu Alarm Menu Display Menu There are 5 sub menus in [Main Menu]. Press UP or DOWN to select sub menus, ENTER to enter into the sub menu or press ESC to exit to [Summary Pages] 5.3.2.1 OPERATION MENU Select [Operation Menu] in [Main Menu] and press ENTER to go into this menu. OPERATION MENU Status : ON Mode : Cooling Cool Temperature : 12.0°C Heat Temperature : 40.
5.3.2.2 Settings Menu Select [Settings Menu] in [Main Menu] and press ENTER to go into this menu. SETTINGS MENU Set Parameter Change Passw ord Panel Option Set Panel ID Some advance settings can be found here. Press UP or DOWN to select settings, ENTER to start the setting or press ESC here to exit to [Main Menu]. Settings - Set Parameter - Password Changing - Panel Option - Set Panel ID 5.3.2.2.1 Set Parameter Select [Set Parameter] in [Settings Menu] and press ENTER to go into this menu. 1. 2. 3. 4. 5.
5.3.2.2.3 Panel Option Select [Panel Option] in [Setting Menu] and Press ENTER to go into this menu. Backlight Buzzer Screen Saver Timeout Contrast Brightness Temp Unit : Norm al : : On : Disable : 5m : 50% : Medium :°C User can do some miscellaneous for the panel. These settings would not affect whole system performance.
5.3.2.3 Timer Menu Select [Timer Menu] in [Main Menu] and press ENTER to go into this menu. TIMER MENU Clock Setting Date Setting Time Schedule Timer : Disable : All the timer/ schedule settings are included in this menu. Press UP or DOWN to select each settings. ENTER to start the setting or press ESC here to exit to [Main Menu]. Settings: - Set Clock - Set Date - Set Schedule ( 7 days Programmable Timer) - Enable/ Disable Timer Schedule 5.3.2.3.
5.3.2.3.2 Set Date Select [Date Setting] in [Timer Menu] and press ENTER to go into this menu. Set Date : yyyy mm dd 2000 / 01 / 01 User can set the date in this menu. The date is set according to sequence below: (year) / (month) / (day) Press [ESC] to exit to [Timer Menu]. 5.3.2.3.3 Set Schedule Select [Schedule Timer] in [Timer Menu] and press ENTER to go into this menu.
5.3.2.4.1 Show Alarms Select [Show Alarms] in [Alarm Menu] and press ENTER to go into this menu. [Ch 0] Alarm 1 Comp 1 overload 01/ 01/ 00 12:00am User can view all the fault/ alarm records in this menu. The record shows - Alarm type - Alarm occurred date - Alarm occurred time - Alarm occurred unit (Chiller ID) Beside that, user can erase the alarm record in this menu. Press [ESC] to exit to [Alarm Menu]. 5.3.2.4.
5.3.2.5.1 Defrost Sensor Select [Defrost Sensor] in [Display Menu] and press ENTER to go into this menu. Defrost Sensor Comp 1 : 12.8°C User can view the defrost sensor temperature for each compressor in the Chiller. Press [ESC] to exit to [Display Menu] 5.3.2.5.2 Discharge Sensor Select [Discharge Sensor] in [Display Menu] and press ENTER to go into this menu. Discharge Sensor Comp 1 : 36.5°C User can view the discharge sensor temperature for each compressor in the Chiller.
6. Operation User Manual 6.1 Starting Chiller panel can be set as Master or Slave panel unit. When the Panel ID is set to ‘0’, it acts like a Master panel, whereas it is Slave panel if Panel ID is set to others number (1-50). Chiller panel can control the Chiller if both ID no. (Panel ID and Chiller ID) are same. For example: Panel ID 1 can only control Chiller ID 1 Master Panel can choose to control each Chiller or control all Chiller at once in the network.
6.2 CHILLER OPERATION CONTROL 6.2.1 STARTING During power on for the Chiller Panel, it needs to take several times to collect information from the Chiller. At this time, all the status will show “--”. Please ensure the particular Chiller exists in the network. When the process is completed, user can start to control the Chiller using the panel.
6.2.3 Switching On/Off There are several ways to switch ON/OFF for the Chiller. i) [Summary Pages] Press and hold ON/OFF button (hold 1 second). Please note that the ON/OFF button will only function in [Summary Pages]. ii) [Operation Menu] Summary Pages Main Menu Operation Menu OPERATION MENU Status : ON Mode : Cooling Cool Temperature : 12.0°C Heat Temperature : 40.0°C In [Operation Menu], select “Status” and press ENTER.
6.2.4 Switching Mode There are several ways to switch the mode for the Chiller. Please take note that some mode cannot be set due to current Chiller model settings. Chiller Model Chiller Heat Pump Chiller / Boiler Heat Pump / Boiler Chiller + Boiler Heat Pump + Boiler Cooling √ √ √ √ √ √ Mode Heating x √ x √ x √ Boiling x x √ √ Auto Auto √ - Allow to set x - Not Allow to set Auto - Turn ON automatically i) [Summary Pages] Cooling - Press and hold COOL button.
6.2.5 Changing Mode Set Temperature There are 2 ways to change the mode set temperature for the Chiller. i) [Operation Menu] Summary Pages Main Menu OPERATION MENU Status : ON Mode : Cooling Cool Temperature : 12.0° C Heat Temperature : 40.0° C OPERATION MENU Status : ON Mode : Cooling Cool Temperature : 12.0° C Heat Temperature : 40.0° C 1. General 2. Regulator 3. Compressor 4. Defrost 5. Antifreeze 6. Inverter 7. Alarm and Contact R1 Cool SP : 12.0°C R2 Cool Diff : 3.
6.2.6 Manual Defrost User can choose which compressor will go into manual defrost cycle by using the Chiller Panel, as long as the condition is fulfilled with defrost condition. This can be done in [Operation Menu]. Summary Pages Main Menu Operation Menu Please take note that “Manual Defrost” option will only available in HEATING mode. It will disappear in COOLING/ BOILING mode. OPERATION MENU OPERATION MENU Status : ON Mode : Heating Cool Temperature : 12.
6.2.7 Advance Parameter Settings The Chiller Panel provide user a lot of advance parameter settings for the Chiller. The parameters are divided into 7 groups. There all are stored in [Set Parameter] menu and it is password-protected layer in the panel. * CAUTION : INPROPER SETTINGS WILL CAUSE PERMANENT DAMAGE TO THE CHILLER !!! Summary Pages Main Menu Settings Menu Key in Password Set Parameter 7 groups of Advance Parameter: 1) General G1 Mode G2 No.
3) Compressor C1 Min Run : 12s C2 Min Stop : 240s C3 2On Interval : 360s C4 2Cp ON Dly : 15s C5 P-Cp ON Dly : 60s C6 Cp-P OFF Dly: 40°C C7 Cp Cut Off : 120°C 4) Condenser Defrost D1 Start Temp D2 End Temp D3 Max Dura D4 Interval D5 Dly Bfr Def D6 Dly Aft Def : -3°C : 14°C : 10m : 45m : 0s : 0s 5) Cool Mode Antifreeze A1 Heater SP A2 Heater Diff A3 Sensor A4 Alarm SP A5 Alarm Diff : 5°C : 2.0°C : Leave : 3°C : 2.
6.2.8 Changing Password For security purpose, some places in the panel are password-proctected. User can change the password at anytime. Summary Pages Main Menu Settings Menu Change Password Please enter the Old password ----------0 ---- User needs to enter the old password in order to change the password. Change the 1st digit value via UP or DOWN. Press ENTER to start enter 2nd digit and the rest, or ESC to exit at anytime. Password accepted . . .
6.2.9 Clock Setting User can set the clock for the panel. Summary Pages Main Menu Timer Menu Set Time UP or DOWN to change ‘hour’. ENTER to set ‘minute’ or ESC to exit to [Timer Menu]. Set Time : hh mm UP or DOWN to change ‘minute’. ENTER to confirm or ESC to set ‘hour’again. 00 : 00 6.2.10 DATE SETTING User can set the date for the panel.
6.2.11 7 Days Programmable Setting The are 2 ON/OFF events in one day for the schedule. This schedule is applicable to all the chillers in the network.
6.2.12 Viewing Alarm / Erase Alarm Record Whenever a new fault/ alarm is occurred, there will be a message pop up to show the fault/ alarm. Backlight will blinking with beeping sound (if “Alarm Buzzer” is set ON). If the fault/ alarm has not been dissolved from the Chiller, a sign [A] will be shown in the [Summary Pages].(from pop up menu) automatically if the fault/ alarms have been dissolved.
6.2.13 Viewing Defrost Sensor Temperature The Chiller Panel displays defrost sensor temperature for each compressor in [Defrost Sensor] in [Display Menu]. Defrost Sensor Comp 1 : 12.8°C Press ESC to exit to [Display Menu] 6.2.14 Viewing Compressor Discharge Temperature The Chiller Panel displays compressor discharge temperature for each compressor in [Discharge Sensor] in [Display Menu]. Discharge Sensor Comp 1 : 36.
6.2.15 Viewing / Clear Compressor Run Time User can view/ clear the compressor run time for the Chiller in [Comp Run Time] in [Display Menu]. Comp Run Time Press UP or DOWN to select the compressor. ENTER to start clear the run time, or ESC to exit to [Display Menu]. Comp 1 : 13579h Clear Run Time ? Press Enter to Clear Or ESC to exit. Press ENTER and key in the password to confirm or ESC to cancel 6.2.
Parameter Value Description Backlight Normal Always ON OFF Enable Disable 1-30m 0-100% OFF Low, Medium, High °C °F Turn ON backlight for 30s via key press Always ON backlight Enable beeping sound when fault/ alarm occurred Disable beeping sound when fault/ alarm occurred Show screen saver when timeout No screen save Timeout for showing screen saver Adjust the contrast setting for the LCD panel No backlight Adjust the backlight intensity Display temperature in degree Celsius Display temperature in degre
7.
8. Appendix Unit Flag Default 4 (Chiller+Boiler) Min 0 Max 2 Resolution 1 Flag 1 1 4 1 Flag 0 (disable) 0 1 1 Flag 0 (disable) 0 1 1 Flag 0 (disable) 0 1 1 Flag 0 (disable) 0 1 1 Flag 0 0 50 1 Unit °C (F) °C (F) °C (F) °C (F) °C (F) °C (F) °C (F) °C (F) °C (F) Default 12 (53.6) 1.5* (2.7) 40 (104) 1.5* (2.7) 7 (44.6) 20 (68) 30 (86) 50 (122) 5 (9) Min 7(44.6) 0.4 (0.7) 30(86) 0.4 (0.7) -20 (-4) 7(44.
A1 A2 A3 A4 A5 P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P13 P14 P15 P16 P17 P18 P19 V1 V2 V3 V4 V5 COOL MODE ANTIFREEZE Antifreeze heater set-point Antifreeze heater differential Antifreeze sensor select 0=Leaving water, 1=Entering water Antifreeze alarm set-point Antifreeze alarm differential Unit °C (F) °C (F) Flag Default 5 (41) 2 (3.6) 0 (leaving) 3 (37) 2 (3.6) Min -40 (-40) 0.4 (0.7) 0 Max 40 (104) 10 (18) 1 Resolution 1 0.1 1 -40 (-40) 0.4 (0.7) 40(104) 10 (18) 1 0.
Special Precautions When Dealing with Refrigerant R410A Unit 1) What is New Refrigerant R410A? R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is essential. 2) Components Mixture of composition by weight : R32(50%) and R125(50%) 3) Characteristic • R410A liquid and vapor components have different compositions when the fluid evaporates or condenses.
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to ensure that only the original composition of R410A is being delivered into the system. The liquid composition can be different from the vapor composition. Dip-pipe Invert cylinder without dip-pipe Liquid withdrawal e) Normally, the R410A cylinder or can is being equipped with a dip-pipe for liquid withdrawal.
Installation M5ACV 030/ 055/ 075CR 41
M5ACV 030CR M5ACV 055CR / 075CR 42
M5ACV 100 / 135 / 210CR 700 500 500 1100 Safety Precautions Before installing the air conditioner unit, please read the following safety precautions carefully ! Warning • • • • • • • Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance. All field wiring must be installed in accordance with the national wiring regulation.
Caution Please take note of the following important points when installing. • Do not install the unit where leakage of flammable gas may occur. If gas leaks and accumulates around the unit, it may cause fire ignition. • Ensure that the drainage piping is connected properly. ! • If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture. Do not overcharge the unit. This unit is factory pre-charged.
M5ACV 030 / 055 / 075CR M5ACV 030 CR AIR V E NT (INS TALL HIG HE S T P OS IT ION) P R E S S UR E G AUG E G AT E VALV E G AT E VALV E G AT E B ALANC ING VALV E VALV E THE R MOME TE R THE R MOME TE R FAN C OIL UNIT /AIR HANDLING UNIT B ALANC ING G AT E VALVE VALVE G AT E VALVE B Y PAS S VALVE P (DIF F E R E NT P R E S S UR E T Y P E ) S TR AINE R C HE C K VALV E F LE XIB LE G AT E VALVE (LOWE R P OS IT ION F OR DR AINAG E ) MAK E UP VALV E M5ACV 055CR / 075CR AIR V E NT (INS TALL HIG HE S T P
M5ACV 100 / 135 / 210CR AIRVENT (INSTALL HIGHEST POSITION) PRESSURE GAUGE GATE VALVE GATE VALVE GATE VALVE THERMOMETER BALANCING VALVE FAN COIL UNIT/AIR HANDLING UNIT FLEXIBLE THERMOMETER GATE VALVE BALANCING VALVE STRAINER GATE VALVE FLEXIBLE CHECK VALVE PRESSURE DIFFERENTIAL VALVE GATE VALVE (LOWER POSITION FOR DRAINAGE) MAKE UP VALVE ! Figure 2 CAUTION • Do not allow water to remain in the water pipes if the unit is not operating for a long period.
! WARNING • All terminals and connection must be tightened. • Avoid any wires from touching the refrigerant pipe. Apply insulation if necessary. • Avoid any wires from touching the moving components such as, fan motor, pump & compressor. Water Piping System Setup • • Fill up the water circuit after connecing all the pipes and equipment. Perform leak checks for all connections and joints. Do not start the unit when the system is leaking.
Control Operation Guide The unit is equipped with a microprocessor controller board. The microprocessor controller is provided to give temperature control for the system by accurately measuring and controlling the water entering and water leaving temperature. The temperature setting in the unit is preset in the factory. It is not recommended to change the setting unless necessary. A wired contoller handset is connected to the microprocessor board.
Sound Data Sound Pressure Level Model M5ACV030CR M5ACV055CR M5ACV075CR M5ACV100CR M5ACV135CR M5ACV210CR 125Hz 56 60 65 61 66 68 1/1 Octave Sound Pressure Level (dB, ref 20µPa) 250Hz 500Hz 1kHz 2kHz 4kHz 60 59 53 48 43 63 61 56 52 46 65 63 61 57 51 58 57 58 56 53 58 58 62 60 58 68 62 61 59 56 8kHz 38 42 42 53 52 55 Overall (dBA) 59 62 65 63 67 67 8kHz 48 55 53 68 66 65 Overall (dBA) 71 72 76 78 81 78 .
Selection Pr ocess Process Water Pressure Drop VS Flow Rate Model : M5ACV030CR - Cooling Water Flow m3/hr 1.26 1.30 1.32 1.36 1.39 1.43 1.49 Pump Head kPa 109.00 108.40 108.20 108.00 107.20 106.00 105.00 System Head kPa 26.56 26.59 28.94 31.54 31.39 31.81 32.30 Available Head Presure kPa 82.44 81.81 79.26 76.46 75.81 74.19 72.70 Model : M5ACV 030CR - Heating Water Flow m3/hr 1.89 1.80 1.66 1.44 1.12 Pump Head kPa 95.00 96.60 101.00 106.00 111.80 System Head kPa 38.34 35.40 32.45 28.64 18.
Model : M5ACV075CR - Cooling / Heating Water Flow 3 m /hr 2.20 2.60 3.00 3.40 3.80 Pump Head kPa 315.00 300.00 285.00 275.00 265.00 System Head kPa 21.78 31.81 41.17 52.17 65.60 Available Head Presure kPa 293.22 268.19 243.83 222.83 199.40 Model : M5ACV100CR - Cooling Water Flow 3 m /hr 3.98 4.25 4.40 4.79 4.83 4.86 4.90 Pump Head kPa 260.00 250.00 240.00 235.00 230.00 227.50 225.00 System Head kPa 42.46 46.67 45.10 62.30 59.54 59.30 59.07 Available Head Presure kPa 217.54 203.33 194.90 172.70 170.
Correction Factors with GLYCOL Use CAPACITY FACTOR GLYCOL LWT/ deg C 10 20 30 40 -5 0.89 0.87 0.77 -3.9 0.9 0.876 0.781 -1.1 0.925 0.925 0.892 0.796 1.7 0.945 0.938 0.906 0.809 4.4 0.956 0.949 0.918 0.82 7.2 0.965 0.958 0.927 0.829 10 0.962 0.957 0.926 0.828 GLYCOL % WATER FLOW PRESSURE DROP 10 1.015 1.06 20 1.04 1.12 30 1.08 1.18 40 1.135 1.
Engineering and Physical Data General Data - Heat pump R410A Inverter MODEL M5ACV030CR M5ACV055CR Btu/h 27000 50000 W 7913 14654 Btu/h 33000 55000 W 9663 16119 COOLING W 5370 7350 HEATING W 4510 5850 COOLING A 266.0 15.8 HEATING A 21.5 13.
General Data - Heat pump R410A Inverter MODEL M5ACV075CR Btu/h 70000 W 20515 Btu/h 75000 W 21980 COOLING W 9050 HEATING W 7900 COOLING A 16.6 HEATING A 15.4 V/Ph/Hz 380-415 / 3 / 50 NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT POWER SOURCE REFRIGERANT TYPE R410A CONTROL ELECTRONIC EXPANSION VALVE HEIGHT mm/in 1460 / 57.5 WIDTH mm/in 1150 / 45.3 DEPTH mm/in 550 / 21.7 HEIGHT mm/in 1626 / 64.0 WIDTH mm/in 1309 / 51.
General Data - Heat pump R410A Inverter MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT M5ACV100CR M5ACV135CR Btu/h 95000 131500 W 27840 38540 Btu/h 100000 141500 W 29310 41470 COOLING W 12000 15750 HEATING W 11400 16250 COOLING A 24.4 30.0 HEATING A 23.8 POWER SOURCE 31.1 380-415 / 3 / 50 V/Ph/Hz REFRIGERANT TYPE R410A CONTROL ELECTRONIC EXPANSION VALVE / CAPILLARY TUBE HEIGHT mm/in 1245 / 49.0 1245 / 49.
General Data - Heat pump R410A Inverter MODEL M5ACV210CR Btu/h NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT 200000 W 58620 Btu/h 210000 W 61550 COOLING W 22300 HEATING W 21800 COOLING A 44.6 HEATING A 44.6 V/Ph/Hz 380-415 / 3 / 50 POWER SOURCE REFRIGERANT TYPE R410A CONTROL UNIT DIMENSION PACKING DIMENSION ELECTRONIC EXPANSION VALVE HEIGHT mm/in 1786 / 70.3 WIDTH mm/in 2093 / 82.4 1192 / 46.
Components Data MODEL M5ACV030CR TYPE CONDENSER FAN Q'TY 1 2 MATERIAL METAL DRIVE DIRECT DIAMETER CONDENSER FAN MOTOR 457.2 / 18 mm/in TYPE INDUCTION Q'TY INDEX OF PROTECTION (IP) 1 2 NA NA TYPE COMPRESSOR AC INVERTER SCROLL OIL TYPE POE POE OIL AMOUNT TYPE INVERTER SCROLL TUBE DIAMETER mm/in 9.52 / 3/8 THICKNESS mm/in 0.372 / 0.015 3 cm / fl.oz. 1700 / 57.
Components Data MODEL M5ACV100CR TYPE CONDENSER FAN Q'TY 2 MATERIAL METAL DRIVE DIRECT DIAMETER CONDENSER FAN MOTOR mm/in 600 / 24 660 / 26 TYPE INDUCTION Q'TY 2 INDEX OF PROTECTION (IP) TYPE IP44 IP44 AC INVERTER SCROLL AC INVERTER SCROLL COMPRESSOR 1 OIL TYPE ME56 OIL AMOUNT cm3 / fl.oz. 2300 / 77.8 TYPE POE OIL AMOUNT cm3 / fl.oz. 1952 / 66.0 TYPE CONDENSER COIL INNER GROOVED COPPER DIAMETER mm/in 9.52 / 3/8 THICKNESS mm/in 0.28 / 0.
Components Data MODEL M5ACV210CR TYPE CONDENSER FAN PROPELLER Q'TY 2 MATERIAL METAL DRIVE DIRECT DIAMETER CONDENSER FAN MOTOR mm/in 812 / 32 TYPE INDUCTION Q'TY 2 INDEX OF PROTECTION (IP) NA TYPE AC INVERTER SCROLL COMPRESSOR 1 OIL TYPE ME56 OIL AMOUNT cm3 / fl.oz. 2300 / 77.8 TYPE SCROLL COMPRESSOR 2 OIL TYPE ME56 OIL AMOUNT cm3 / fl.oz. 1700 / 57.5 TYPE SCROLL COMPRESSOR 3 OIL TYPE POE OIL AMOUNT cm3 / fl.oz. 3257 / 110.
Safety Devies MODEL M5ACV030CR HIGH PRESSURE SWITCH LOW PRESSURE SWITCH SAFETY DEVICE TYPE M5ACV055CR NC NC OPEN Pa / psi 4140 / 600 4140 / 600 CLOSE Pa / psi 3312 / 480 3312 / 480 TYPE OPEN Pa / psi CLOSE Pa / psi PHASE PROTECTION NC NC 124 / 18 124 / 18 193 / 28 193 / 28 BUILT IN ON BOARD BUILT IN ON BOARD DIFFERENTIAL PRESSURE SWITCH YES YES ANTI-FREEZE PROTECTION SENSOR YES YES DISCH.
MODEL M5ACV210CR HIGH PRESSURE SWITCH LOW PRESSURE SWITCH SAFETY DEVICE TYPE NC OPEN Pa / psi 4140 / 600 CLOSE Pa / psi 3312 / 480 OPEN Pa / psi 124 / 18 CLOSE Pa / psi TYPE NC 193 / 28 PHASE PROTECTION BUILT IN ON BOARD DIFFERENTIAL PRESSURE SWITCH YES ANTI-FREEZE PROTECTION SENSOR DISCH.
Performance Data MODEL LEAVING WATER TEMP (°C Model : M5ACV 030CR / 055CR - Cooling MODEL LEAVING WATER TEMP (°C) 4 5 6 M5ACV030CR 7 8 9 10 4 5 6 M5ACV055CR 7 8 9 10 MODEL LEAVING WATER TEMP (°C 4 5 6 M5ACV030CR 7 8 9 10 4 5 6 M5ACV055CR 7 8 9 10 4 5 6 M5ACV030CR 7 8 9 10 4 5 6 M5ACV055CR 7 8 9 10 AMBIENT TEMPERATURE ON CONDENSOR (°C) 19 20 25 28 WATER AVAIL. PUMP PUMP COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT INPUT CAP.
MODEL LEAVING WATER TEMP (°C Model : M5ACV075CR - Cooling MODEL LEAVING WATER TEMP (°C) 4 5 6 M5ACV075CR 7 8 9 10 MODEL LEAVING WATER TEMP (°C 4 5 6 M5ACV075CR 7 8 9 10 4 5 6 M5ACV075CR 7 8 9 10 AMBIENT TEMPERATURE ON CONDENSOR (°C) 19 20 25 28 WATER AVAIL. PUMP PUMP COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS.
MODEL LEAVING WATER TEMP (°C) Model : M5ACV100 / 135CR - Cooling MODEL LEAVING WATER TEMP (°C) 4 5 6 M5ACV100CR 7 8 9 10 4 5 6 M5ACV135CR 7 8 9 10 MODEL LEAVING WATER TEMP (°C 4 5 6 M5ACV100CR 7 8 9 10 4 5 6 M5ACV135CR 7 8 9 10 4 5 6 M5ACV100CR 7 8 9 10 4 5 6 M5ACV135CR 7 8 9 10 AMBIENT TEMPERATURE ON CONDENSOR (°C) 19 20 25 28 WATER AVAIL. PUMP PUMP COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP.
MODEL LEAVING WATER TEMP (°C) Model : M5ACV 210CR - Cooling MODEL LEAVING WATER TEMP (°C) 4 5 6 M5ACV210CR 7 8 9 10 MODEL LEAVING WATER TEMP (°C 4 5 6 M5ACV210CR 7 8 9 10 4 5 6 M5ACV210CR 7 8 9 10 AMBIENT TEMPERATURE ON CONDENSOR (°C) 19 20 25 28 PUMP PUMP COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING COOL POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT WATER RATE PRESS.
MODEL LEAVING WATER TEMP (°C) Model : M5ACV 030 / 055CR - Heating MODEL LEAVING WATER TEMP (°C) 35 40 M5ACV030CR 45 50 55 35 40 M5ACV055CR 45 50 55 MODEL LEAVING WATER TEMP (°C) 35 40 M5ACV030CR 45 50 55 35 40 M5ACV055CR 45 50 55 35 40 M5ACV030CR 45 50 55 35 40 M5ACV055CR 45 50 55 AMBIENT TEMPERATURE ON CONDENSOR (°C) -7 -5 0 WATER AVAIL. PUMP PUMP HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP.
MODEL LEAVING WATER TEMP (°C) Model : M5ACV 075CR - Heating MODEL LEAVING WATER TEMP (°C) 35 40 M5ACV075CR 45 50 55 MODEL LEAVING WATER TEMP (°C) 35 40 M5ACV075CR 45 50 55 35 40 M5ACV075CR 45 50 55 AMBIENT TEMPERATURE ON CONDENSOR (°C) -7 -5 0 WATER AVAIL. PUMP PUMP HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS.
MODEL LEAVING WATER TEMP (°C) Model : M5ACV100 / 135CR - Heating MODEL LEAVING WATER TEMP (°C) 35 40 M5ACV100CR 45 50 55 35 40 M5ACV135CR 45 50 55 MODEL LEAVING WATER TEMP (°C) 35 40 M5ACV100CR 45 50 55 35 40 M5ACV135CR 45 50 55 35 40 M5ACV100CR 45 50 55 35 40 M5ACV135CR 45 50 55 AMBIENT TEMPERATURE ON CONDENSOR (°C) -7 -5 0 WATER AVAIL. PUMP PUMP HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP.
MODEL LEAVING WATER TEMP (°C) Model : M5ACV 210CR - Heating MODEL LEAVING WATER TEMP (°C) 35 40 M5ACV210CR 45 50 55 MODEL LEAVING WATER TEMP (°C) 35 40 M5ACV210CR 45 50 55 35 40 M5ACV210CR 45 50 55 AMBIENT TEMPERATURE ON CONDENSOR (°C) -7 -5 0 WATER AVAIL. PUMP PUMP HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS.
Dimensional Da ta Data Model : M5ACV 030CR 1051,6 10,0 10,0 1010,0 22,3 22,3 All Dimensions are in mm 81,4 479,0 283,3 789,5 50,0 WATER WA OUTLET WA W ATER INLET 147,3 94,2 15,0 1029,0 15,0 300,0 80,6 Model : M5ACV 055CR 85,0 79,4 406,5 70,5 WATER A OUT 70,0 452,0 724,9 ELECTRICAL CABLE 36,5 281,5 8 All Dimensions are in mm 70 882,9 , 982,9 , 50,0 WATER IN WA
205,8 741,4 205,8 553,0 15,0 592,4 15,0 Model : M5ACV 075CR 84,0 1153,0 210,0 244,0 WATER OUT WA AIR VENT 180,0 1462,4 WATER IN WA All Dimensions are in mm 71 265,2 510,7 1 70,6 1 433,1 749,6 1019,6 70,0 ELECTRICAL CABLE
Model : M5ACV100 / 135CR C D A WATER OUTLET M I J WATER INLET H L K L G E F B All Dimensions are in mm Model A B C D F G Base Leg Hole E M5ACV100CR 1500 900 1245 1190 297.5 307.5 1446 M5ACV135CR 1800 1150 1245 1190 347.5 416 1766 H I J K L M M5ACV100CR 100 265 385 60 200 170 M5ACV135CR 10 265 385 60 200 170 Model DETAIL A 128.0 WATER OUTLET 256.0 WATER INLET 1998.4 2092.5 38.0 70.0 1683.3 1786.3 1199.2 50.0 1992.5 174.0 100.0 624.
Electrical Data Electrical Data - Heat Pump R410A Inverter MODEL M5ACV030CR INSULATION GRADE POWER SOURCE CONDENSER FAN MOTOR V/Ph/Hz RATED INPUT POWER W 135 270 RATED RUNNING CURRENT A 0.6 1.3 MOTOR OUTPUT W - - 6 6 INSULATION GRADE POWER SOURCE V/Ph/Hz E F 220 - 240 / 1 / 50 380 - 415 / 3 / 50 CAPACITOR mF NA NA RATED INPUT POWER (COOLING) W 4945 6630 5130 RATED INPUT POWER (HEATING) W 4077 RATED RUNNING CURRENT (COOLING) A 18.3 13.
Electrical Data - Heat pump R410A Inverter MODEL M5ACV100CR INSULATION GRADE POWER SOURCE CONDENSER FAN MOTOR F RATED INPUT POWER W 500 RATED RUNNING CURRENT A 2.2 6.0 MOTOR OUTPUT W 200 x2 450 x2 INSULATION GRADE POWER SOURCE 1430 8 6 NA NA 380 - 415 / 3 / 50 V/Ph/Hz CAPACITOR µF NA NA RATED INPUT POWER (COOLING) W 10500 13520 RATED INPUT POWER (HEATING) W 9900 14020 RATED RUNNING CURRENT (COOLING) A 21.9 25.9 RATED RUNNING CURRENT (HEATING) A 21.3 27.
Electrical Data - Heat pump R410A Inverter MODEL M5ACV210CR INSULATION GRADE POWER SOURCE CONDENSER FAN MOTOR 220 - 240 / 1 / 50 RATED INPUT POWER W 820 x2 RATED RUNNING CURRENT A 3.6 x2 MOTOR OUTPUT W 550 x2 POLES 8 INSULATION GRADE E POWER SOURCE COMPRESSOR B V/Ph/Hz V/Ph/Hz µF NA RATED INPUT POWER (COOLING) W 20200 RATED INPUT POWER (HEATING) W 19700 RATED RUNNING CURRENT (COOLING) A 38.7 RATED RUNNING CURRENT (HEATING) A 38.7 LOCKED ROTOR AMP.
Wiring Diagrams PA R T NO : 50 13 9 026086 Model : M5ACV 030CR 76
Model : M5ACV 055CR 77
PA R T NO : 50 13 4 083602 Model : M5ACV 075CR 78
RED WHITE FTR1 (50A) L3 U CP1 V W T3 L2 T2 T1 L1 A A' G BLUE PE 22 21 CP1 A2 A1 U L3 TB4 CP2 V W T3 L2 T2 L1 T1 21 PE 22 CP2 A2 A1 A TB5 A' BLACK RED + L1 L3 W PUMP V T3 L2 T2 U - T1 FR FTR (25A) B' B B' WHITE B BR-3P C C' BLACK N A2 A1 96 95 98 97 L2 L3 TB2 OR BL BR LB BL ALARM H/C ON/OFF ON/OFF ALARM ALARM BL A2 A1 L HEAT/COOL ON/OFF H/C RD T1 T2 T3 L1 BR-1P LA + JK8 FSC1 PHASE FSC2 FAN-2-1 FAN-1-1 FAN-1-2
V W COMP 1 U T3 T2 T1 L3 RED L2 WHITE L1 22 21 CP1 A2 A1 V W 22 21 G A2 A1 TB5 + T FTR2 (25A) GROUND PLATE CP2 A’ TB4 COMP 2 U T3 L3 T2 L2 T1 L1 BR-3P V PUMP W T3 T2 T1 U L3 L2 L1 PFC A1 1 2 A2 96 95 PUMP 98 97 TB2 T1 L1 BR BL OR LB BL ALARM H/C ON/OFF ON/OFF ALARM ALARM BL A2 A1 L HEAT/COOL ON/OFF H/C RD T2 T3 L2 L3 BR-1P LA JK8 FSC1 PHASE FSC2 FAN-2-1 FAN-1-1 FAN-1-2 R_PHASE FAN-2-2 N R S T PE JP14 FM2 N 8 ON/O
Servicing and Maintenance Servicing Servicing or maintenance of these unit must be carried out by experienced personnel with specific training in refrigeration. Repeated check the safety devices and continuous cycling of control components must be analyzed and corrected before being reset. The simple design of the refrigeration circuit totally eliminates potential problems during normal unit operation. No maintenance work is needed on the refrigeration circuit as long as the unit is operating normally.
Troubleshooting When a malfunction of the unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures. The following are common fault conditions and simple troubleshooting tips. If any other fault conditions that are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.
Diagnostic flow chart : Faulty : Check : Cause : Remedy No response after power-on Is LED main board lit? Yes Input conditions faulty To check & rectify Incorrect Input power supply To check & rectify No Is R,S,T Input voltage normal? No Yes Is Power board DC-IN voltage normal? No Incorrect DC rectifier circuit To rectify Yes Is JP-power/DCOUT output normal? Yes Main board faulty To replace Main board or IPM short circuit To replace No Is connection between main board and IPM normal? Ye
LED on main board normal, but no output. Is output condition ok? No Incorrect output condition To check & rectify Incorrect load.
Water flow error Short JK4 on main board Is water flow error persists? No Flow switch faulty or pump stopped Yes Main board faulty To check & rectify To replace Main board Over voltage protection (OV/UN Voltage) Yes Is Power supply > 490VAC? Power supply failure To rectify No No Is Power supply < 460VAC? Yes Power board faulty 85 To replace Power board
Under voltage protection (OV/UN Voltage) Yes Is Power supply < 310VAC? Power supply failure To rectify No No Is Power supply > 340VAC? Yes Power board faulty To replace Power board Pump overload Is voltage of 97, 98 on heat relay VDC= 0 V ? No Yes Remove * JK8, 97 & 98, is it still conducting? No Main board faulty To replace Main board Yes Pump overload * JK8 on main board 86 To rectify
Phase missing No Is voltage between R,S,T 415VAC±20% Incorrect incoming supply To check & rectify Yes Yes Is J-RST on Main board 415VAC±20%? Main board faulty To replace Main board Main board faulty To replace Main board No Disconnect power, remove J-RST, is voltage of socket 415VAC±20%? Yes No EMI filter faulty To check & replace EMI filter Variable compressor overload (Comp 1 overload) Restart, Set freq. with handset.
IPM Error No IPM faulty Is IPM ok? To replace IPM Yes No Is current at rated frequency ok? Compressor faulty To check & rectify Yes Is IPM Error persists? No Normal Yes Is heat sink temperature >100°C? Yes Heat sink condition improper To rectify No Is IPM temperature >100°C? No Main board faulty or wrong signal To rectify / replace Yes Is heat compound dried out? No To replace IPM IPM faulty Yes Heat compound dried out 88 To replace and re-apply
Variable drive high pressure (High pressure 1) Is high pressure switch ok? No High pressure switch faulty To replace Yes Check the AirCond. system for high pressure Yes System high pressure To rectify Variable drive low pressure (Low pressure 1) Is low pressure switch ok? No Low pressure switch faulty To replace Yes Check the AirCond.
Variable compressor high discharge temperature (Comp 1 discharge overheat) Yes > 110°C? Compressor stops To check & rectify Sensor faulty To replace sensor Yes Is Temp. sensor ok? (<100°C?) No Yes Check the AirCond. system for high discharge temp. Yes System high discharge pressure To rectify Fixed compressor over-current (Comp.
Exploded View and Part Lists Model : M5ACV 030CR No 1 2 3 4 5 6 7 Description ASSY, BASE PAN ASSY, PANEL PARTITION ASSY, COIL PANEL, SUPPORT PILLAR STRUCTURE REAR RIGHT PANEL TOP STRUCTURE FRONT RIGHT Part no R50 01 4 079444 R50 01 4 079447 R50 02 4 082968 R01 01 4 058974 R01 01 4 069935 R01 01 4 064936 R01 01 4 069936 No 19 20 21 22 23 24 25 8 ASSY, PANEL ORIFICE R50 01 4 060810 26 9 10 11 PANEL RIGHT COIL GUARD, BACK COIL GUARD, LEFT R01 01 4 079475 R01 02 4 058986 R01 02 4 058985 27 28 29 12
Model : M5ACV 055CR No 1 ASSY, PANEL BASE R50 01 4 079682 25 2 ASSY, PANEL PARTITION R50 01 4 080005 26 3 ASSY, COIL R50 02 4 079683 27 4 5 COMP. ASSY ANV47FKBMT CLAMP, BPHE R50 04 9 024220 R01 01 4 061748 28 29 6 CLIP, FILTER DRIER R01 01 4 071226 30 7 8 FILTER DRIER SUPPORT, ACCUMULATOR R02 16 4 034987 R01 01 4 079828 31 32 9 ACCUMULATOR, R65W R02 11 9 016393 33 10 - 34 R01 01 4 059624 35 BUSH, RUBBER R11 01 4 001876 12 13 14 15 16 INS, ACCUMULATOR BODY SUPPORT, ACCU.
Model : M5ACV 075CR No 1 2 3 4 5 Part no R50 01 4 078737 R50 01 4 078744 R50 02 4 078902 R50 04 9 024220 R02 20 9 024775 No 27 28 29 30 31 Description STRUCTURE REAR RIGHT COIL GUARD, BACK COIL GUARD RIGHT INS.
Model : M5ACV100CR NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 DESCRIPTIONS ASSY, PANEL BASE MAIN COIL SUPPORT ASSY, COIL RIGHT ASSY, COIL LEFT ASSY, PARTITION PANEL LEFT PANEL RIGHT PANEL ACCUMULATOR LIQUID RECEIVER COMPRESSOR ASSY FILTER DRIER COMP.
Model : M5ACV135CR NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 DESCRIPTIONS ASSY, PANEL BASE MAIN ASSY, PARTITION PANEL RIGHT PANEL LEFT PANEL COIL SUPPORT ASSY, COIL LEFT ASSY, COIL RIGHT COMPRESSOR ASSY COMP.
Model : M5ACV210CR NO DESCRIPTION 1 2 3 4 5 6 7 8 9 10 11 12 R50 01 4 084901 R01 01 4 083984 R50 01 4 083980 R50 02 4 084041 R50 02 4 084040 R01 01 4 084911 R01 01 4 087701 R50 02 4 084902 R01 01 4 084910 R50 04 9 024220 R50 04 9 026991 R50 04 9 026989 13 14 15 ASSY, PANEL BASE MAIN PANEL, COIL SUPPORT ASSY, PANEL PARTITION ASSY, COIL RIGHT (GOLD FIN) ASSY, COIL LEFT (GOLD FIN) BRACKET, BPHE PANEL, SUPPORT BPHE ASSY, BPHE CLAMP, BPHE ASSY, COMP.ANV47FKBMT MIT. ASSY, COMP. BN65YFAMT SIAM ASSY. COMP.
Products manufactured in an ISO certified facility. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com. © 2009 McQuay International +1 (800) 432-1342 www.mcquay.