Charge operation
This operation must be done by using a gas cylinder and a precise weighing machine. The additional charge
is topped up into the outdoor unit using the suction valve via the service port.
Remove the service port cap.
Connect the low pressure side of the charging gauge to the suction service port center of the cylinder tank
and close the high pressure side of the gauge. Purge the air from the service hose.
Start the air conditioner unit.
Open the gas cylinder and low pressure charging valve.
When the required refrigerant quantity is pumped into the unit, close the low pressure side and the gas
cylinder valve.
Disconnect the service hose from service port. Put back the service port cap.
Open
Open
Suction
Valve
Discharge
Valve
Indoor Unit
Outdoor Unit
Liquid side
Gas side
Check
Valve
Close
Hi
Low
Caution
R410A must be charged as liquid. Usually R410A cylinder is equipped with a dip-pipe for liquid withdrawal. If there is
nodip-pipe, the cylinder should be inverted so as to withdraw liquid R410A from the valve.
Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit thoroughly and then
charge the unit with fresh R410A according to the amount recommended in the specification.