Specifications
Electrical Data - R22 Cooling only
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
MAC080C MAC100C
FF
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 565 565
RATED RUNNING CURRENT A 2.40 2.40
MOTOR OUTPUT W 120 x2 120 x2
88
NA NA
POWER SOURCE V/Ph/Hz 380 - 415 / 3 / 50 380 - 415 / 3 / 50
CAPACITOR
µF
NA NA
RATED INPUT POWER W
7052 8560
RATED RUNNING CURRENT A 14.00 14.70
LOCKED ROTOR AMP. (COMP1/COMP2) A 66 / 66 74 / 74
FF
POWER SOURCE V/Ph/Hz 380 - 415 / 3 / 50 380 - 415 / 3 / 50
RATED INPUT POWER W 1050 1050
RATED RUNNING CURRENT A 1.50 1.50
MAC120C MAC150C
FF
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 772 1532
RATED RUNNING CURRENT A
3.60 6.80
MOTOR OUTPUT W 200 x2 450 x2
86
NA NA
POWER SOURCE V/Ph/Hz 380 - 415 / 3 / 50 380 - 415 / 3 / 50
CAPACITOR
µ
F
NA NA
RATED INPUT POWER W 9433 11447
RATED RUNNING CURRENT A
19.70 22.40
LOCKED ROTOR AMP. (COMP1/COMP2) A 101 / 101 95 / 95
FF
POWER SOURCE V/Ph/Hz
380 - 415 / 3 / 50 380 - 415 / 3 / 50
RATED INPUT POWER W 800 800
RATED RUNNING CURRENT A
2.00 2.00
COMPRESSOR
INSULATION GRADE
WATER PUMP
INSULATION GRADE
MODEL
CONDENSER FAN
MOTOR
INSULATION GRADE
POLES
MODEL
INSULATION GRADE
INSULATION GRADE
CONDENSER FAN
MOTOR
COMPRESSOR
WATER PUMP
POLES
INSULATION GRADE
137