Specifications

Electrical Data - R22 Heat pump
MAC020CR MAC025CR
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W
135 135
RATED RUNNING CURRENT A
0.67 0.67
MOTOR OUTPUT W
145 145
66
ENA
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
CAPACITOR
µF
45 50
RATED INPUT POWER (COOLING) W
2289 2455
RATED INPUT POWER (HEATING) W
2379 2285
RATED RUNNING CURRENT (COOLING) A
10.90 11.20
RATED RUNNING CURRENT (HEATING) A
11.20 10.50
LOCKED ROTOR AMP. A
67 82
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER (COOLING) W
175 189
RATED INPUT POWER (HEATING) W
186 194
RATED RUNNING CURRENT (COOLING) A
0.77 0.83
RATED RUNNING CURRENT (HEATING) A
0.82 0.85
MAC030CR MAC040CR
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W
135 270
RATED RUNNING CURRENT A
0.67 1.34
MOTOR OUTPUT W
145 145 x2
66
NA NA
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 380 - 415 / 3 / 50
CAPACITOR
µF
60 NA
RATED INPUT POWER (COOLING) W
3205 3970
RATED INPUT POWER (HEATING) W
3215 4030
RATED RUNNING CURRENT (COOLING) A
16.7 7.4
RATED RUNNING CURRENT (HEATING) A
16.8 7.6
LOCKED ROTOR AMP. A
114 66
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 380 - 415 / 3 / 50
RATED INPUT POWER (COOLING) W
201 320
RATED INPUT POWER (HEATING) W
211 329
RATED RUNNING CURRENT (COOLING) A
0.88 0.71
RATED RUNNING CURRENT (HEATING) A
0.93 0.73
MAC050CR MAC060CR
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W
270 270
RATED RUNNING CURRENT A
1.34 1.34
MOTOR OUTPUT W
145 x2 145 x2
66
NA NA
POWER SOURCE V/Ph/Hz
380 - 415 / 3 / 50 380 - 415 / 3 / 50
CAPACITOR µ
F
NA NA
RATED INPUT POWER (COOLING) W
4440 5930
RATED INPUT POWER (HEATING) W
4380 5620
RATED RUNNING CURRENT (COOLING) A
7.7 12.2
RATED RUNNING CURRENT (HEATING) A
7.7 11.8
LOCKED ROTOR AMP. A
74 101
FF
POWER SOURCE V/Ph/Hz
380 - 415 / 3 / 50 380 - 415 / 3 / 50
RATED INPUT POWER (COOLING) W
336 351
RATED INPUT POWER (HEATING) W
349 357
RATED RUNNING CURRENT (COOLING) A
0.75 0.78
RATED RUNNING CURRENT (HEATING) A
0.77 0.79
MODEL
INSULATION GRADE
INSULATION GRADE
CONDENSER FAN
MOTOR
POLES
INSULATION GRADE
COMPRESSOR
WATER PUMP
MODEL
CONDENSER FAN
MOTOR
INSULATION GRADE
POLES
COMPRESSOR
INSULATION GRADE
WATER PUMP
INSULATION GRADE
MODEL
CONDENSER FAN
MOTOR
INSULATION GRADE
POLES
COMPRESSOR
INSULATION GRADE
WATER PUMP
INSULATION GRADE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.