Service manual

64 Service Manual SM-MDS_(i)
EC
TH12 open/short circuit
(suction)
Outdoor suction temperature sensor TH12 broken or loose
73
EF
Emergency run
On the premise that part of the indoor unit communication malfunction and either one (or
both) of the following error occurs (unit will shut down):
1. System sub heat <1ºC for 15 minutes
2. TH12 malfunctions
87
F0
Outdoor storage
malfunction
Outdoor PCB chip read faulty at the very beginning when power on
Outdoor PCB chip broken
82
F1
Indoor inlet coil sensor
malfunction
Indoor units T
in
sensor broken or loose
F2
Indoor midlet coil
sensor malfunction
Indoor units T
mid
sensor broken or loose
F3
Indoor outlet coil sensor
malfunction
Indoor units T
out
sensor broken or loose
F4
Indoor return air sensor
broken
Indoor units T
room
sensor broken or loose
F5
Indoor supply air sensor
broken
Indoor units T
room
sensor broken or loose
73
F6
Indoor and controller
communication
malfunction
Wired controller communication wire not connected or loose
Wired controller broken
Outdoor PCB broken
83
F7
Ambient temperature
exceed running range
Outdoor ambient temperature exceed running range
1. cooling running range 0 – 43ºC
2. heating running range -15 – 16 ºC
Outdoor circulating air short
1. Cause outdoor ambient temperature rising to exceed running range when cooling.
2. Cause outdoor ambient temperature falling to exceed running range when heating.
84
FA
Wired controller storage
broken
Data read faultily at the very beginning when power on
Chip broken
85
FB
Pump malfunction
(indoor drain pump)
Overflow switch broken
Pump broken
75
FC
Indoor and outdoor
communication
malfunction
Indoor and outdoor communication wire broken
Indoor and outdoor communication wire loose
Indoor and outdoor communication wire A and B reversed
Communication wire too long, should less than 1000m
Outdoor PCB not power on
Indoor and outdoor jump wire not correct, still on update status
Last indoor unit terminal resistance of communication wire not short-circuit
Indoor and outdoor PCB program not compatible
Indoor and outdoor PCB abnormal
76
6