Description Default  Range 
Unit  Ft/Lb  SI 
Clear Ice Timer  No  No,Yes 
SSS Communication  No  No, Yes 
PVM  Multi Point  Single Point, Multi Point , None(SSS) 
Noise Reduction  Disabled  Disabled, Enabled 
Noise Reduction Start Time  21:00  18:00 – 23:59 
Noise Reduction End Time  6:00  5:00 – 9:59 
Noise Reduction Condenser 
Offset 
10.0 °F 
5 °C 
0.0 to 25.0 °F 
BAS Protocol  None  None, BACnet, LonWorks, Modbus 
Ident number  1  0-???? 
Baud Rate  19200  1200,2400,4800,9600,19200 
Evap LWT sensor offset  0°F  0°C  -5.0 to 5.0°C / -9.0 to 9.0°F 
Evap EWT sensor offset  0°F  0°C  -5.0 to 5.0°C / -9.0 to 9.0°F 
OAT sensor offset  0°F  0°C  -5.0 to 5.0°C / -9.0 to 9.0°F 
Compressors-Global  Ft/Lb  SI 
Start-start timer  20 min  15-60 minutes 
Stop-start timer  5 min  3-20 minutes 
Pumpdown Pressure  14,3 PSI  100 kPa  10 to 40 PSI / 70 to 280 kPa 
Pumpdown Time Limit  120 sec  0 to 180 sec 
Light Load Stg Dn Point  50%  20 to 50% 
Load Stg Up Point  50%  50 to 100% 
Stage Up Delay  5 min  0 to 60 min 
Stage Down Delay  3 min  3 to 30 min 
Stage Delay Clear  No  No, Yes 
Max # Comps Running  4  1-4 
Sequence # Cir 1  1  1-4 
Sequence # Cir 2  1  1-4 
Sequence # Cir 3  1  1-4 
Number of Pulses 10% to 
50% 
10 10 to 20 
Slide Load Delay Mininum  30 seconds  10 to 60 seconds 
Slide Load Delay 
Maximum 
150 seconds  60 to 300 seconds 
Slide Unload Delay 
Minimum 
10 seconds  5 to 20 seconds 
Slide Unload Delay 
Maximum 
50 seconds  30 to 75 seconds 
Liquid Injection Activation  185°F  85°C  75 to 90°C 
Liquid Line Solenoid 
Valves 
No No, Yes 
Alarm Limits 
Low Evap Pressure-Unload  23.2 PSI  160 kPa  See section 0 
Low Evap Pressure-Hold  27.5 PSI  190 kPa  See section 0 
Oil Press Delay   30 sec  10-180 sec 
Continued next page. 