Instruction manual
KOMAC00607-09EN  19 
Description Default  Range 
Unit  Ft/Lb  SI 
Oil Press Differential  35 PSI  250 kPa  0-60 PSI / 0 to 415 kPa 
Low Oil Level Delay  120 sec  10 to 180 sec 
High Discharge Temperat. 
230 °F 
110 °C  150 to 230 °F / 65 to 110 °C 
High Lift Pressure Delay  5 sec  0 to 30 sec 
Low Pressure Ratio Delay  90 sec  30-300 sec 
Start Time Limit  60 sec  20 to 180 sec 
Evaporator Water Freeze 
36 °F 
2,2 °C  See section 0 
Evaporator Flow Proof  15 sec  5 to 15 sec 
Recirculate Timeout  3 min  1 to 10 min 
Low Ambient Lockout 
Enable 
Disable Disable, Enable 
Low Ambient Lockout 
55 °F 
12°C  See section 0 
The following set points exist individually for each circuit: 
Description Default 
Range 
PW 
  Ft/Lb  SI 
Circuit mode  Enable  Disable, enable, test  S 
Compressor Size  To be Verified    M 
Capacity Control  Auto  Auto, Manual  S 
Manual Capacity 
See note 1 below table 
0 to 100%  S 
Clear Cycle Timers  No  No, yes  M 
EXV control  Auto  Auto, manual  S 
EXV position 
See note 2 below table  0% to 100% 
S 
Oil Sump Check  Enable  Enable, Disable  S 
Service Pumpdown  No  No,Yes  S 
Evap pressure offset  0PSI  0kPa  -14.5 to 14.5 PSI /-100 to 100 kPa S 
Cond pressure offset  0PSI  0kPa  -14.5 to 14.5 PSI /-100 to 100 kPa S 
Oil pressure offset  0PSI  0kPa  -14.5 to 14.5 PSI /-100 to 100 kPa S 
Suction temp offset  0°F  0°C  -5.0 to 5.0 deg  S 
Discharge temp offset  0°F  0°C  -5.0 to 5.0 deg  S 
Fans 
Fan VFD enable  On  Off, On  M 
N
umber of fans  5  5 to 12  M 
Saturated Condenser Temp 
Target Min 
90 °F  32°C 
80.0-110.0
 o
F / 26.0 to 43.0 °C 
M 
Saturated Condenser Temp 
Target Max 
110 °F  43°C 
90.0-120.0 
o
F / 32.0 to 50 °C 
M 
Fan Stage Up Deadband 0  5 °F  2.5 °C  1-20 
o
F / 1-10 °C  M 
Fan Stage Up Deadband 1  5 °F  2.5 °C  1-20 
o
F / 1-10 °C  M 
Fan Stage Up Deadband 2  8 °F  4 °C  1-20 
o
F / 1-10 °C  M 
Fan Stage Up Deadband 3  10 °F  5 °C  1-20 
o
F / 1-10 °C  M 
Fan Stage Up Deadband 4  8 °F  4 °C  1-20 
o
F / 1-10 °C  M 
Fan Stage Up Deadband 5  8 °F  4 °C  1-20 
o
F / 1-10 °C  M 
Fan Stage Down Deadband 2  8 °F  4 °C  1-25 
o
F / 1-13 °C  M 
Fan Stage Down Deadband 3  7 °F  3.5 °C  1-25 
o
F / 1-13 °C  M 
Fan Stage Down Deadband 4  6 °F  3 °C  1-25 
o
F / 1-13 °C  M 
Fan Stage Down Deadband 5  5 °F  2.5 °C  1-25 
o
F / 1-13 °C  M 
Fan Stage Down Deadband 6  5 °F  2.5 °C  1-25 
o
F / 1-13 °C  M 
VFD Max Speed  100%  90 to 110%  M 
VFD Min Speed  25%  20 to 60%  M 
Note 1 – This value will follow the actual capacity while Capacity Control = Auto. 
Note 2 – This value will follow the actual EXV position while EXV Control = Auto. 










