Unit Functions 
Calculations 
LWT Slope 
LWT slope is calculated such that the slope represents the change in LWT over a time frame 
of one minute with at least five samples per minute. 
Pulldown Rate 
The slope value calculated above will be a negative value as the water temperature is 
dropping. For use in some control functions, the negative slope is converted to a positive 
value by multiplying by –1. 
Unit Enable 
Enabling and disabling the chiller is accomplished using set points and inputs to the chiller. 
The unit switch, remote switch input, and Unit Enable Set Point all are required to be on for 
the unit to be enabled when the control source is set to local. The same is true if the control 
source is set to network, with the additional requirement that the BAS request must be on. 
Unit is enabled according to the following table. 
NOTE: An x indicates that the value is ignored. 
Unit 
Switch 
Control 
Source Set 
Point 
Remote 
Switch Input
Unit Enable 
Set Point 
BAS 
Request 
Unit 
Enable 
Off x  x  x  x Off 
x x  x  Off x Off 
x x Off  x x Off 
On Local  On  On  x  On 
x Network  x  x  Off Off 
On Network  On  On  On  On 
All of the methods for disabling the chiller, discussed in this section, will cause a normal 
shutdown (pumpdown) of any running circuits. 
When the controller is powered up, the Unit Enable Set Point will be initialized to ‘off’ if the 
Unit Status After Power Failure Set Point is set to ‘off’. 
Unit Mode Selection 
The operating mode of the unit is determined by setpoints and inputs to the chiller. The 
Available Modes Set Point determines what modes of operation can be used. This setpoint 
also determines whether the unit is configured for glycol use. The Control Source Set Point 
determines where a command to change modes will come from. A digital input switches 
between cool mode and ice mode if they are available and the control source is set to local. 
The BAS mode request switches between cool mode and ice mode if they are both available 
and the control source is set to network. 