Unit Status 
The displayed unit status is determined by the conditions in the following table: 
Enum Status  Conditions 
0  Auto  Unit State = Auto 
1  Off:Ice Mode Timer 
Unit State = Off, Unit Mode = Ice, and Ice Delay = 
Active 
2  Off:OAT Lockout  Unit State = Off and Low OAT Lockout is active 
3  Off:All Cir Disabled  Unit State = Off and all compressors unavailable 
4  Off:Emergency Stop  Unit State = Off and Emergency Stop Input is open 
5  Off:Unit Alarm  Unit State = Off and Unit Alarm active 
6  Off:Keypad Disable  Unit State = Off and Unit Enable Set Point = Disable 
7  Off:Remote Switch  Unit State = Off and Remote Switch is open 
8 Off:BAS Disable 
Unit State = Off, Control Source = Network, and BAS 
Enable = false 
9  Off:Unit Switch  Unit State = Off and Unit Switch = Disable 
10  Off:Test Mode  Unit State = Off and Unit Mode = Test 
11  Auto:Noise Reduction  Unit State = Auto and Noise Reduction is active 
12  Auto:Wait for load 
Unit State = Auto, no circuits running, and LWT is 
less than the active set point + startup delta 
13  Auto:Evap Recirc  Unit State = Auto and Evaporator State = Start 
14  Auto:Wait for flow 
Unit State = Auto, Evaporator State = Start, and Flow 
Switch is open 
15  Auto:Pumpdown  Unit State = Pumpdown 
16 Auto:Max Pulldown 
Unit State = Auto, max pulldown rate has been met or 
exceeded 
17  Auto:Unit Cap Limit 
Unit State = Auto, unit capacity limit has been met or 
exceeded 
18 Auto:Current Limit 
Unit State = Auto, unit current limit has been met or 
exceeded 
Ice Mode Start Delay 
An adjustable start-to-start ice delay timer will limit the frequency with which the chiller 
may start in Ice mode. The timer starts when the first compressor starts while the unit is 
in ice mode. While this timer is active, the chiller cannot restart in Ice mode. The time 
delay is user adjustable. 
The ice delay timer may be manually cleared to force a restart in ice mode. A set point 
specifically for clearing the ice mode delay is available. In addition, cycling the power 
to the controller will clear the ice delay timer. 
Evaporator Pump Control 
Three evaporator pump control states for control of the evaporator pumps: 
•  Off - No pump on. 
•  Start – Pump is on, water loop is being recirculated. 
•  Run – Pump is on, water loop has been recirculated. 
The control state is Off when all of the following are true: 
•  Unit state is Off 
•  LWT is higher than the Evap Freeze set point or LWT sensor fault is active 
•  EWT is higher than the Evap Freeze set point or EWT sensor fault is active 
The control state is Start when any of the following are true: 
•  The unit state is auto 
•  LWT is less than the Evap Freeze set point minus 0.6 °C and LWT sensor fault 
isn’t active 