Instruction manual
24 KOMAC00607-09EN 
•  EWT is less than the Evap Freeze set point minus 0.6 °C and EWT sensor fault 
isn’t active 
The control state is Run when the flow switch input has been closed for a time greater 
than the Evaporator Recirculate set point. 
Pump Selection 
The pump output used is determined by the Evap Pump Control set point. This setting 
allows the following configurations: 
•  #1 only – Pump 1 will always be used 
•  #2 only – Pump 2 will always be used 
•  Auto – The primary pump is the one with the least run hours, the other is used 
as a backup 
•  #1 Primary – Pump 1 is used normally, with pump 2 as a backup 
•  #2 Primary – Pump 2 is used normally, with pump 1 as a backup 
Primary/Standby Pump Staging 
The pump designated as primary will start first. If the evaporator state is start for a time 
greater than the recirculate timeout set point and there is no flow, then the primary pump 
will shut off and the standby pump will start. When the evaporator is in the run state, if 
flow is lost for more than half of the flow proof set point value, the primary pump will 
shut off and the standby pump will start. Once the standby pump is started, the flow loss 
alarm logic will apply if flow cannot be established in the evaporator start state, or if 
flow is lost in the evaporator run state. 
Auto Control 
If auto pump control is selected, the primary/standby logic above is still used. When the 
evaporator is not in the run state, the run hours of the pumps will be compared. The 
pump with the least hours will be designated as the primary at this time. 
Noise Reduction 
Noise Reduction is enabled only when the Noise Reduction set point is enable. Noise 
Reduction is in effect when enabled via the set point, the unit mode is cool, and the unit 
controller clock time is between the Noise Reduction start time and end time. 
When Noise Reduction is in effect, the Maximum Reset is applied to the cool LWT set 
point. However, if any reset type is selected, that reset will continue to be used rather 
than the maximum reset. Also, the saturated condenser target for each circuit will be 
offset by the Noise Reduction Condenser Target Offset. 
Leaving Water Temperature (LWT) Reset 
LWT Target 
The LWT Target varies based on settings and inputs and is selected as follows: 
Control Source 
Set Point 
Mode 
Input 
BAS 
Request 
Available Modes 
 Set Point 
Base LWT Target 
Local  OFF  X  COOL  Cool Set Point 1 
Local  ON  X  COOL  Cool Set Point 2 
Network  X  X  COOL  BAS Cool Set Point 
Local OFF X COOL w/Glycol  Cool Set Point 1 
Local ON X COOL w/Glycol  Cool Set Point 2 
Network X X COOL w/Glycol  BAS Cool Set Point 
Local OFF x COOL/ICE w/Glycol  Cool Set Point 1 
Local ON x COOL/ICE w/Glycol  Ice Set Point 
Network x COOL COOL/ICE w/Glycol  BAS Cool Set Point 
Network  x  ICE  COOL/ICE w/Glycol  BAS Ice Set Point 
Local  x  x  ICE w/Glycol  Ice Set Point 
Network  x  x  ICE w/Glycol  BAS Ice Set Point 










