Leaving Water Temperature (LWT) Reset 
The base LWT target may be reset if the unit is in Cool mode and it is configured for a 
reset. The type of reset to be used is determined by the LWT Reset Type set point. 
When the active reset increases, the Active LWT Target is changed at a rate of 
0.1 degrees
F every 10 seconds. When the active reset decreases, the Active LWT 
Target is changed all at once. 
After resets are applied, the LWT target can never exceed a value of 60°F. 
Reset Type – None 
The Active Leaving Water variable is set equal to the current LWT set point. 
Reset Type – Return 
The Active Leaving Water variable is adjusted by the return water temperature. 
Start Reset Delta T
 LWT set Point+Max Reset
(54)
LWT Set Point
(44)
Return Reset
0
Max Reset
(10)
Evap Delta T (
o
F)
Active
LWT
(
o
F)
The active set point is reset using the following parameters: 
1.  Cool LWT set point 
2.  Max Reset set point 
3.  Start Reset Delta T set point 
4.  Evap Delta T 
Reset varies from 0 to Max Reset set point as the Evaporator EWT – LWT (Evap delta t) 
varies from the Start Reset Delta T set-point to 0. 
4-20 mA External Signal Reset 
The Active Leaving Water variable is adjusted by the 4 to 20 mA reset analog input. 
Parameters used: 
1.  Cool LWT set point 
2.  Max Reset set point 
3.  LWT Reset signal 
Reset is 0 if the reset signal is less than or equal to 4 mA. Reset is equal to the Max 
Reset Delta T set point if the reset signal equals or exceeds 20 mA. The amount of reset 
will vary linearly between these extremes if the reset signal is between 4 mA and 20 
mA. An example of the operation of 4-20 reset in Cool mode follows. 
20
(54)
Cool LWT Set
Point (44)
4
4-20 mA Reset - Cool Mode
0
Max Reset
(10)
Active
LWT
(
o
F)
Reset Signal (mA)