Instruction manual
28 KOMAC00607-09EN 
The compressor capacities are adjusted one at a time while maintaining a capacity 
imbalance that does not exceed 12.5%. 
Load/Unload Sequence 
This section defines which compressor is the next one to load or unload. 
Next To Load 
The next compressor to load meets the following requirements: 
Lowest capacity of the running compressors that can load up 
•  if capacities are equal, it must have the highest sequence number of the 
compressors that are running 
•  if the sequence numbers are equal, it must have the least run hours 
•  if run hours are equal, it must have the most starts 
•  if starts are equal, it must be the highest numbered compressor 
Next To Unload 
The next compressor to unload must meet the following requirements: 
Highest capacity of the running compressors 
•  if capacities are equal, it must have the lowest sequence number of the compressors 
that are running 
•  if sequence numbers are equal, it must have the most run hours 
•  if run hours are equal, it must have the least starts 
•  if starts are equal, it must be the lowest numbered compressor 
Compressor Capacity Control In Ice Mode 
In Ice mode, running compressors are loaded up simultaneously at the maximum 
possible rate that allows for stable operation of the individual circuits. 
Unit Capacity Overrides 
Unit capacity limits can be used to limit total unit capacity in Cool mode only. Multiple 
limits may be active at any time, and the lowest limit is always used in the unit capacity 
control. 
Soft load, demand limit, and network limit use a deadband around the actual limit value, 
such that unit capacity increase is not allowed within this deadband. If unit capacity is 
above the deadband, capacity is decreased until it is back within the deadband. 
•  For 2 circuit units, the deadband is 7%. 
•  For 3 circuit units, the deadband is 5%. 
•  For 4 circuit units, the deadband is 4%. 
Soft Load 
Soft Loading is a configurable function used to ramp up the unit capacity over a given 
time. The set points that control this function are: 
•  Soft Load – (ON/OFF) 
•  Begin Capacity Limit – (Unit %) 
•  Soft Load Ramp – (seconds) 
The Soft Load Unit Limit increases linearly from the Begin Capacity Limit set-point to 
100% over the amount of time specified by the Soft Load Ramp set-point. If the option 
is turned off, the soft load limit is set to 100%. 
Demand Limit 
The maximum unit capacity can be limited by a 4 to 20 mA signal on the Demand Limit 
analog input at the unit controller. This function is only enabled if the Demand Limit set 
point is set to ON. 