Instruction manual
KOMAC00607-09EN  45 
Action Taken: Action Taken: Unload the compressor by decreasing the capacity 
by one step every 5 seconds until the evaporator pressure rises above the Low 
Evaporator Pressure Unload set point. 
Reset: While still running, the event will be reset if evaporator pressure > (Low 
Evaporator Pressure Hold SP + 2psi). The event is also reset if the unit mode is 
switched to Ice, or the circuit is no longer in the run state. 
High Condenser Pressure - Hold 
Event description (as shown on screen): CondPressHigh Hold N 
Trigger:  While the compressor is running and unit mode is Cool, if saturated 
condenser temperature >= High Saturated Condenser Hold Value, the event is 
triggered. 
Action Taken: Inhibit loading. 
Reset: While still running, the event will be reset if saturated condenser 
temperature < (High Saturated Condenser Hold Value – 10
o
F). The event is also 
reset if the unit mode is switched to Ice, or the circuit is no longer in the run state. 
High Condenser Pressure - Unload 
Event description (as shown on screen): CondPressHighUnloadN 
Trigger: While the compressor is running and unit mode is Cool, if saturated 
condenser temperature >= High Saturated Condenser Unload Value, the event is 
triggered. 
Action Taken: Unload the compressor by decreasing the capacity by one step 
every 5 seconds until the evaporator pressure rises above the High Condensing 
Pressure Unload set point. 
Reset: While still running, the event will be reset if saturated condenser 
temperature < (High Saturated Condenser Unload Value – 10
o
F). The event is 
also reset if the unit mode is switched to Ice, or the circuit is no longer in the run 
state. 
Failed Pumpdown 
Event description (as shown on screen): Pumpdown Fail Cir N 
Trigger: Circuit state = pumpdown for time > Pumpdown Time set point 
Action Taken: Shutdown circuit 
Reset: N/A 
Power Loss While Running 
Event description (as shown on screen): Run Power Loss Cir N 
Trigger: Circuit controller is powered up after losing power while compressor 
was running 
Action Taken: N/A 
Reset: N/A 
Alarm Logging 
When an alarm occurs, the alarm type, date, and time are stored in the active alarm 
buffer corresponding to that alarm (viewed on the Alarm Active screens) also in the 
alarm history buffer (viewed on the Alarm Log screens). The active alarm buffers hold 
a record of all current alarms. 
A separate alarm log stores the last 25 alarms to occur. When an alarm occurs, it is put 
into the first slot in the alarm log and all others are moved down one, dropping the last 
alarm. In the alarm log, the date and time the alarm occurred are stored, as well as a list 
of other parameters. These parameters include unit state, OAT, LWT, and EWT for all 
alarms. If the alarm is a circuit alarm, then the circuit state, refrigerant pressures and 
temperatures, EXV position, compressor load, number of fans on, and compressor run 
time are also stored. 










