Troubleshooting guide
Page 16 of 28 / OM 931-3
Initial Power up
Figure 8: I/O Expansion Board Configuration Jumper Terminals
Table 6: I/O Expansion Board Configuration Jumper Settings
  Jumper  Description  Options
JP1  Number of Compressors
  Open for single compressor
      Shorted for dual compressor
JP2
Hot Gas/Water Reheat 
  Open to disable reheat
      Shorted to enable reheat
      JP3 and JP4 open for no supplemental heat
  JP3 & JP4  Supplemental Heat Type   JP3 open, JP4 shorted for boilerless electric heat
      JP3 and JP4 shorted is an invalid setting
      JP5 and JP6 open for single-speed fan 
JP5 & JP6  Fan Speed Selection
  JP5 open, JP6 shorted for three-speed fan
      JP5 shorted and JP6 open for two-speed fan
      JP 5 and JP6 shorted is an invalid setting
JP7  Compressor Speed Type
  Open for single-speed compressor
      Shorted for two-speed compressor
  JP8  Future Spare