Troubleshooting guide
OM 931-3 / Page 17 of 28
Three-Speed Fan Operations
Table 7: Three-Speed Fan
Continuous Fan
Compressor On
Electric Heat
  Space Temp Satised 
Low Speed
Of
f 
Of
f
  Compressor 
Of
f   
Med. Speed
Of
f
Heating/Cooling 
Electric Heat Enabled 
Of
f    Off 
High Speed
Two-Speed Fan Operations
Table 8: Two-Speed Fan
Continuous Fan
Compressor On
Electric Heat
  Space Temp Satised 
Low Speed
Of
f 
Of
f
  Compressor 
Of
f   
High Speed
Of
f
Heating/Cooling 
Electric Heat Enabled 
Of
f    Off 
High Speed
Circuit Two, Additional Operating 
Modes
The I/O Expansion Module controls the second circuit high 
pressure, low pressure, and low suction line temperature 
operating conditions in the same manner as the main board 
controls the rst circuit.
Table 9: I/O Expansion Module LED & Fault Outputs
Status LED's   
Thermostat Alarm 
Mode / Fault
  Yellow Green  Red 
Light Output 
           Terminal “A”
  Invalid Conguration 
Flash  Flash  Off  De-energized
  Jumper Setting   
  Base Board   
Off  Flash  Flash  N/A
  Communication Fail
   High Pressure #2 Fault  Off  Off  Flash  De-energized
  Low Pressure #2 Fault  Off  Off  On  De-energized
Low Suction Temp #2 Fault
Flash  Off  Off  De-energized
Sensor Failures Low Suction
Low Suction Temp #2,  Flash  Flash  On  De-energized
1
EWT (w/ Boilerless EH only)
2 
Service Test Mode Enabled  Flash  Flash  Flash  De-energized
  Unoccupied Mode  On  On  Off  Energized
  Occupied, Bypass, 
  Standby, or Tenant 
Off  On  Off  Energized
  Override Modes       
Note:  Mode / Faults are listed in order of priority. 
1
  Boilerless electric heat only
2
  Alarm/fault LED indications take precedence over 
service test mode LED indication. The controller shall 
use service test mode if the service test mode jumper 
is installed, even if the LED’s indicate an alarm/fault.
Operation
Dual Circuit Units
•  Provides standard lead / lag operation for two compressors 
in dual circuit units
•  Circuit one will come on rst when there is any call for 
heating or cooling at the main board
•  The second circuit will be enabled after the interstage 
timer has expired. The interstage timer defaults to 300 
seconds
•  HP, LP, SLTS fault for either circuit one or circuit two, 
will lockout the entire unit and subject for intelligent reset
Thermostat Inputs (Y2, W2)
•  The Y2 terminal which is cooling mode stage two, 
energizes the second compressor
•  If Y1 and Y2 thermostat inputs are active at the same time, 
interstage timers will be used to stage the compressor up 
and down
•  The W2 terminal which is heating mode stage two, 
energizes the second reversing valve followed 30 seconds 
later by the second compressor
•  If W1 and W2 thermostat inputs are active at the 
same time, interstage timers will be used to stage the 
compressors up and down
Electric Heat Controls
Boilerless Heat Coil Control
•  Turns on the factory installed heater when the entering 
water temperature is less than 55°F, the temperature set 
point is not adjustable
•  For geothermal applications the factory installed electric 
heater turns on when the entering water temperature is less 
than 30°F
Note:  In both cases the compressor is shut down.
Multiple Speed Fan Control
•  When the Water Source Heat Pump is equipped with an 
I/O Expansion Module and factory installed electric heat, 
three speed fan control is possible.
•  If the thermostat is calling for continuous fan operation 
and the compressor is not running the fan motor will run 
in low speed.
•  If there is a call for heating or cooling (compressor is 
running) the fan motor will run in medium speed.
•  If the electric heater is enabled the fan motor does not run 
in high speed.
Note:  On units with an I/O Expansion Module and no electric 
heat, it is possible to congure the I/O Expansion 
Module for a two speed fan. If there is a call for 
continuous fan (compressor off) the fan motor runs 
in low speed. If there is a call for heating or cooling 
(compressor on) the fan motor runs at high speed.