Troubleshooting guide
Page 18 of 28 / OM 931-3
Second Circuit Faults
With the addition of the second circuit the fault recovery and 
reset table has new faults for the second circuit (Table 10).
Table 10: Second Circuit Faults
  ● = Applies  – = Does not apply
Fault
Auto Recovery 
Remote Reset  Reset (Network
            (Tenant Override)  Command or Power)
  Invalid Conguration Jumper Setting  –  –  ● 
  Brownout      ●  –  ●
  HP2        –  ●  ●
  LP1        ●*  ●  ●
  LT2 (In Heating)    ●*  ●  ● 
  LT2 (In Cooling)    –  ●  ●
Sensor  Room Temperature, LT1, LT2,
  –  –  ●
Failure  EWT  (w/Boilerless EH Only)
  –  –  ●
  Condensate Overow  ●  –  ●
EEPROM Failure    –  –  –
* Auto Recover for the first two occurrences, lockout on the third occurrence within 24 hours, i.e., subject to “Intelligent Reset.” 
Table 11: I/O Expansion Module Connections & Descriptions
  H8  Description
  Pin 1  Fan high speed normally open output
  Pin 2  No connection
  Pin 3  24 VAC Common
  H3
  Pin 1
  Pin 2
  Pin 3  For future development
  Pin 4
  Pin 5
  Pin 6
  H8
    Dual compressor: compressor 2 normally
  Pin 1  open output, all others fan medium speed
    normally open
  Pin 2  24 VAC common
  Pin 3  No connection
Pin 4
  Dual compressor: reversing valve for 
    circuit 2, all others electric heat
  Pin 5  24 VAC common
  H4 
  Pin 1  Entering water temperature sensor signal
  Pin 2  Entering water temperature sensor common
  HP6
  HP2-1  High pressure switch for circuit 2
  HP2-2  High pressure switch for circuit 2
  H7
  Pin 1  Suction line temperature sensor circuit 2 signal
  Pin 2  Suction line temperature sensor circuit 2 common
  Pin 3  Low pressure switch circuit 2 signal
  Pin 4  Low pressure switch circuit 2 source
  H5  LED Annunciator
 TB1  For future use