Troubleshooting guide
Page 6 of 28 / OM 931-3
Initial Power-Up
Pre start check list:
A random start delay time between 180 and 240 seconds is 
generated at power up.
Figure 2: Location of Configuration Jumpers on the Base 
Board Controller
 CAUTION
  The MicroTech III circuit board incorporates static sensitive de-
vices. A static charge from touching the device can damage the 
electronic components. To help prevent damage during service, 
use  static  discharge  wrist  straps.Static  discharge  wrist  straps 
are grounded to the heat pump chassis through a 1 Mohm resistor. 
Replacing a MicroTech III circuit 
board:
1. Connect wrist strap to unit.
2.  Remove faulty board and place on static protected surface.
3.  Remove replacement board from static protected bag.
Do not touch circuit board; hold by edges.
4.  Holding board in grounded hand, install board in unit.
5.  Insert faulty board in empty static bag for return.
Table 2: Configuration Jumper Settings
  Jumper  Description  Options
JP1  Mode
  Open for normal operation mode
      Shorted for service/test operation mode
  JP2  Fan operation only applies to  Open for continuous fan operation
    network controls  Shorted for cycling fan operation
JP3  Freeze protection
  Open for water freeze protection
      Shorted for antifreeze protection
  JP4  Future spare  Future spare
  JP5  Set point adjustment range only  Open for adjustment range of -3.0° to +3.0° F 
    applies to network controls with a  Shorted for 50° to 90° F adjustment range
    room temperature sensor   
JP6  Room control type
  Open for thermostatic room control
      Shorted for room temperature sensor control, MicroTech III only
  JP7  Future spare  Future spare
  JP8  Future spare  Future spare