Catalog MMS - 2008 Multi-Split Systems Models: MMSD-A/AR MMST-A/AR MMSH-A M4MSD-A/AR M4MST-A/AR MSD MST MSH http://splitoff.ru/tehn-doc.html , , , .
Table of Contents Nomenclature ................................................................................................................. 1 - Product Line-up ................................................................................................... 2 Features ......................................................................................................................... 4 Application Information ........................................................................................
Nomenclature Production spec. variation Type of refrigerant connection F : Flare Electrical A : 220 - 240V/1Ph/50Hz M 4 MS D 1010 A R - A F AA Model Type R : Heatpump Blank : Cooling only Series A : A series Capacity 1010 : 10,000 Btu/h each Circuit D : Dual circuit T : Triple circuit Model Name MS : Multi Split Refrigerant 4 : R407C Blank : R22 Brand M : McQuay 1 : http://splitoff.ru/tehn-doc.
Product Line Up M(4)MS-A Cooling Only MMSD M4MST 101010A 101015A 101020A 101025A MMST 101515A 101520 101525A 151515A MMSH 151520A 151525A 66K555A 66K66A 8K66A 8K8A K77A X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 2 : http://spl
M(4)MS-AR Heatpump MMST X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X Multiple hole drain pan Inclusive drain elbow Multisplit resistor X Handling handle X X X X X X X X X X X X X X X X X X X X X X X X Valve cover X X X X Rotary Compressor Gold (NA549) Fin Blue (NA510) Fin X X X X X X X X X X X X X X X X X X X X X X X Normal Fin X X X X X X X X X X X X X X X X X X X X X X X Add Accumulator AFAL AFAL AFAL AFAL AFAQ AFAL AFAQ AFAL AFAQ AFAD AFAP AFAD AFAD A
Features Triple S (Slim - Short - Stable) Slim and short outdoor unit can be easily installed even in a narrow balcony and passageway, and yet have a stable profile. MODEL A (cm) B (cm) MMSD/M4MSD 1010 / 1015 / 1515 A/AR 64.6 33.5 MMSD 1020A / 1520A/AR / 2020A 65.0 43.7 65.0 43.7 MMSH 8K8A / 8K66A / 66K66A / 66K555A 64.6 33.5 MMSHK77A 49.4 27.5 MMST/M4MST 101010 / 101015 / 101515 / 151515 A/AR MMST 101020 / 101025 / 101520 / 101525 / 151520 / 151525 A 4 : http://splitoff.ru/tehn-doc.
Coupling Versatility OUTDOOR INDOOR Cooling : MWM 010/015G Heatpump : MWM 010/015/020GR Cooling : MWM 010/015G Heatpump : MWM 010/015GR Cooling MMSD / M4MSD 1010/1015/1515A Heatpump MMSD / M4MSD 1010/1015/1515AR MMSD 1520AR Cooling : MWM 020G Cooling : MWM 010/015G Cooling MMSD 1020/1520A Cooling : MWM 020G Cooling : MWM 020G Cooling MMSD 2020A 5 : http://splitoff.ru/tehn-doc.
OUTDOOR INDOOR Cooling : MWM 010/015G Heatpump : MWM 010/015GR Cooling : MWM 010/015G Heatpump : MWM 010/015GR Cooling MMST 101010 / 101015 / 101515 / 151515A/AR MMST 101020A M4MST 101010 / 101015 / 101515 / 151515 A/AR Cooling : MWM 010/015/020G Heatpump : MWM 010/015GR Cooling : MWM 025G Cooling : MWM 010/015G Cooling MMST 101025 / 101525 / 151525A Cooling : MWM 010/015G A1 : MWM 015G Cooling MMSHK77A A2 : MWM 015G Single Compressor 2-Indoor Split System A1 A2 6 : http://splitoff.
OUTDOOR INDOOR A1 : MWM 010G Cooling MMSH8K8A B1 : MWM 010G Double Compressor 2-Indoor Split System A1 B1 A1 : MWM 010G A2 : MWM 010G Cooling MMSH8K66A Double Compressor 3-Indoor Split System B1: MWM 010G A1 A2 B1 A1 : MWM 010G A2 : MWM 010G Cooling MMSH66K66A B1 : MWM 010G Double Compressor 4-Indoor Split System B2 : MWM 010G A1 A2 B1 B2 7 : http://splitoff.ru/tehn-doc.
OUTDOOR INDOOR A1 : MWM 010G A2 : MWM 010G Cooling MMSH66K555A A3 : MWM 010G B1 : MWM 010G B2 : MWM 015G Double Compressor 5-Indoor Split System A1 A2 A3 B1 B2 8 : http://splitoff.ru/tehn-doc.
Application Infor ma mation tion Refrigerant Circuit Diagram MODEL : MMSD 1010 / 1015 / 1515 / 1020 / 1520 / 2020 A M4MSD 1010 / 1015 / 1515 A 9 : http://splitoff.ru/tehn-doc.
MODEL : MMST/M4MST 101010 / 101015 / 101515 / 151515 A MMST 101020 / 101025 / 101520 / 101525 / 151520 / 151525 A 10 : http://splitoff.ru/tehn-doc.
MODEL : MMSHK77A 11 : http://splitoff.ru/tehn-doc.
MODEL : MMSH8K8A 12 : http://splitoff.ru/tehn-doc.
MODEL : MMSH8K66A 13 : http://splitoff.ru/tehn-doc.
MODEL : MMSH66K66A 14 : http://splitoff.ru/tehn-doc.
MODEL : MMSH66K555A 15 : http://splitoff.ru/tehn-doc.
MODEL : MMSD/M4MSD 1010 / 1015 / 1515 AR MMSD 1520AR 16 : http://splitoff.ru/tehn-doc.
MODEL : MMST / M4MST 101010 / 101015 / 101515 / 151515 AR 17 : http://splitoff.ru/tehn-doc.
Controllers G7 Remote Controller 1 2 Transmission source • The source where the signal will be transmitted Signal transmission indication • Blink to confirm the last setting has been send to the unit. 4 Temperature setting • To set the desired • • 3 room temperature, press the button to increase or decrease the set temperature. The temperature setting range is from 16°C to 30°C (Optional setting 18°C to 30°C). Press both buttons simultaneously to toggle the temperature setting between °C and °F.
G11 Remote Controller Temperature Setting On/Off Button • • Press Once to start the air conditioner • Press again to stop the unit • • To set the desired room temperature, press the button to increase or decrease the set temperature. The temperature setting range is from 16°C to 30°C Personalised Setting Press both buttons simultaneously to toggle the temperature setting between °C and °F • Press and hold the button for 3s to initiate personalized setting. • Set the individual setting e.g.
SLM Operating Instructions SLM AC-5300 (OPTIONAL) 1. “ON/OFF” switch • Press to start the air conditioner unit. • Press again to stop the unit. 6. “Sleep” mode • Press button to activate the sleep function can only be activated under “cool” or heating mode operation. When it is activated under “cool” mode operation, the set temperature will increase 0.5°C after 30 minutes, 1°C after 1 hour and 2°C after 2 hours. If it is actiaved under “HEAT” mode operation, the set temperature will be descreased 0.
Indicator Lights IR signal receiver When an operating signal is sent via the infrared remote control, the signal receiver in the indoor unit will make a beep sound signaling acceptance confirmation. IR Receiver LED indicator lights The table below shows the LED indicator lights for air conditioner unit under normal operation and fault condition. The LED indicator lights are located at the middle of the air conditioner unit.
Operating State and Fault Table Wireless Remote Control Cooling : LED Indicator Light Display POWER TIMER Heatpump : LED Indicator Display SLEEP POWER TIMER HEAT Normal Operation / Fault Indication POWER TIMER SLEEP HEAT Cool Mode Timer On Sleep Mode On Heat Mode Auto Mode - Cool Auto Mode - Heat Compressor - Overload 1 Time Pump Fault 2 Times Gas Leak 3 Times Room Sensor Open Or Short 1 Time Indoor Coil Sensor Open Or Short 2 Times Outdoor Coil Sensor Open Or Short 3 Times - ON / -
Precaution And Installation Location For Installation Of The Condensing Units As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected for outdoor unit should fulfill the following requirements : Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air).
Installation In Zone Exposed To Strong Wind Or High Snow Falls (For Heatpump Model) Installation Clearance Single Condensing Unit Installation Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air flow. Select the coolest possible place where intake air should not be hotter than the outside temperature (max.
Maximum Pipe Length And Maximum Number Of Bends When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases, system piping resistance to the refrigerant flow increases, lowering the cooling capacity. As a result of this, the compressor may become defective. Always choose the shortest path and follow the recommendations as tabulated below : MODEL DATA Max. Length (L) m Max. elevation (H) m Max. No. of Bends MODEL DATA Max. Length (L) m Max.
2) MMST / M4MST 3) MMSH 26 : http://splitoff.ru/tehn-doc.
Flaring Technique (For Flare Connection) Cut the pipe stages by stages, advancing the blade of pipe cutter slowly. Extra force and a deep cut will cause more distortion of pipe and therefore, extra burr. Remove burr with the burr remover. This will avoid unevenness on the flare face which will cause gas leak. Hold the flaring end down to prevent burr from dropping inside pipe. The exact length of pipe protruding from the face of the flare die is determined by the flaring tool.
Diagram 1 Diagram 2 Additional Charge (For Flare Connection) The refrigerant gas is charged in the outdoor unit and, if the piping length to every indoor is 7.62m, additional charge of the refrigerant after vacuuming is not necessary. When the piping length to every indoor is more than 7.62m, please add 15g of refrigerant for every addition of 1m pipe length. Diagram 3 shows typical charging method. Diagram 3 28 : http://splitoff.ru/tehn-doc.
Special Precautions When Dealing With Refrigerant R407C Unit 1) What is new refrigerant R407C? R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0) and thus conformed to the Montreal Protocol regulation. It requires Polyol-ester oil (POE) oil for its compressor’s lubricant. Its refrigerant capacity and performance are about the same as the refrigerant R22.
c) Ensure that the compressor is not expose to open air for more than the recommended time specified by its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is about to be brazed. d) The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level is more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
Special Precautions When Dealing With Refrigerant R410A Unit 1) What is new refrigerant R410A? R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is essential. 2) Components Mixture weight composition R32(50%) and R125(50%) 3) Characteristic • R410A liquid and vapor components have different compositions when the fluid evaporates or condenses.
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is to ensure that only the original composition of R410A is being delivered into the system. The liquid composition can be different from the vapor composition. Invert cylinder without dip-pipe Dip-pipe Liquid withdrawal f) Normally, the R410A cylinder or can is being equipped with a dip pipe for liquid withdrawal.
Electrical Connections Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICAL CODES for field wiring rules. Be sure that installation comply with such rules and regulations. General Precautions Ensure that the rated voltage of the unit corresponds to the name plate before carrying out proper wiring according to the wiring diagram. Provide a power outlet to be used exclusively for each unit.
Engineering and Ph ysical Data Physical MMSD General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 35 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 36 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 37 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 38 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMSD1010A MMSD1515A INDOOR UNIT 2 x MCC010C 2 x MCC015C Btu/h 2 x 9500 2 x 12700 NOMINAL CAPACITY W 2 x 2780 2 x 3720 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 1059 1525 TWO UNITS RUNNING W 1946 2888 NOMINAL RUNNING CURRENT ONE UNIT RUNNING A 4.7 6.7 TWO UNITS RUNNING A 8.7 12.7 W/W 2.86 2.
General Data - Cooling Only (R22) MODEL MMSD1015A OUTDOOR UNIT INDOOR UNIT NOMINAL CAPACITY MCC010C MCC015C Btu/h 9500 12700 3270 W 2780 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 1059 TWO UNITS RUNNING W NOMINAL RUNNING CURRENT ONE UNIT RUNNING A TWO UNITS RUNNING A 10.7 W/W 2.69 EER POWER SOURCE 4.
General Data - Cooling Only (R22) MODEL MMSD1020A OUTDOOR UNIT INDOOR UNIT NOMINAL CAPACITY MCC010C MCC020C Btu/h 9500 18000 5280 W 2780 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 1111 TWO UNITS RUNNING W NOMINAL RUNNING CURRENT ONE UNIT RUNNING A TWO UNITS RUNNING A 15.0 W/W 2.53 EER POWER SOURCE 4.
General Data - Cooling Only (R22) MODEL MMSD1520A OUTDOOR UNIT INDOOR UNIT NOMINAL CAPACITY MCC015C MCC020C Btu/h 12700 18000 5280 W 3720 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 1577 TWO UNITS RUNNING W NOMINAL RUNNING CURRENT ONE UNIT RUNNING A TWO UNITS RUNNING A 16.9 W/W 2.56 EER POWER SOURCE 7.
General Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMSD2020A INDOOR UNIT 2 x MCC020C Btu/h 2 x 18000 W 2 x 5280 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 2173 TWO UNITS RUNNING W 4762 NOMINAL RUNNING CURRENT ONE UNIT RUNNING A 10.6 TWO UNITS RUNNING A 22.7 NOMINAL CAPACITY EER POWER SOURCE W/W 2.
General Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMSD1010A MMSD1515A INDOOR UNIT 2 x MCK010C 2 x MCK015C Btu/h 2 x 9500 2 x 12700 NOMINAL CAPACITY W 2 x 2780 2 x 3720 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 1047 1492 TWO UNITS RUNNING W 1922 2822 NOMINAL RUNNING CURRENT ONE UNIT RUNNING A 4.6 6.6 TWO UNITS RUNNING A 8.6 12.4 W/W 2.90 2.
General Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMSD1015A INDOOR UNIT NOMINAL CAPACITY MCK010C MCK015C Btu/h 9500 12700 3270 W 2780 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 1047 TWO UNITS RUNNING W NOMINAL RUNNING CURRENT ONE UNIT RUNNING A TWO UNITS RUNNING A 10.5 W/W 2.74 EER POWER SOURCE 4.
General Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMSD1020A INDOOR UNIT NOMINAL CAPACITY MCK010C MCK020C Btu/h 9500 18000 5280 W 2780 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 1099 TWO UNITS RUNNING W NOMINAL RUNNING CURRENT ONE UNIT RUNNING A TWO UNITS RUNNING A 14.6 W/W 2.59 EER POWER SOURCE 4.
General Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMSD1520A INDOOR UNIT NOMINAL CAPACITY MCK015C MCK020C Btu/h 12700 18000 5280 W 3720 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 1544 TWO UNITS RUNNING W NOMINAL RUNNING CURRENT ONE UNIT RUNNING A TWO UNITS RUNNING A 16.4 W/W 2.63 EER POWER SOURCE 6.
General Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMSD2020A INDOOR UNIT 2 x MCK020C Btu/h 2 x 18000 W 2 x 5280 NOMINAL TOTAL INPUT POWER ONE UNIT RUNNING W 2106 TWO UNITS RUNNING W 4628 NOMINAL RUNNING CURRENT ONE UNIT RUNNING A 10.3 TWO UNITS RUNNING A 22.1 NOMINAL CAPACITY EER POWER SOURCE W/W 2.
General Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 52 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 53 : http://splitoff.ru/tehn-doc.
General Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 56 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 57 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 58 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 59 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 60 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMSD1010A MMSD1515A INDOOR UNIT 2 x MCC010C 2 x MCC015C CENTRIFUGAL TYPE 1 QUANTITY INDOOR FAN 2 GALVANIZED STEEL MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 202 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRYL STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 406.
Components Data - Cooling Only (R22) MODEL MMSD1015A OUTDOOR UNIT INDOOR UNIT MCC010C MCC015C CENTRIFUGAL TYPE 1 QUANTITY INDOOR FAN 2 GALVANIZED STEEL MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 202 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 406.
Components Data - Cooling Only (R22) MODEL MMSD1020A OUTDOOR UNIT INDOOR UNIT MCC010C MCC020C CENTRIFUGAL TYPE 1 QUANTITY INDOOR FAN 2 GALVANIZED STEEL MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 202 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY 2 N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL MMSD1520A OUTDOOR UNIT INDOOR UNIT MCC015C MCC020C CENTRIFUGAL TYPE INDOOR FAN QUANTITY 2 MATERIAL GALVANIZED STEEL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 203 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY 2 N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMSD2020A INDOOR UNIT 2 x MCC020C CENTRIFUGAL TYPE INDOOR FAN QUANTITY 2 MATERIAL GALVANIZED STEEL DIRECT DRIVE DIAMETER mm/in 162 / 6.30 LENGTH mm/in 204 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 2 QUANTITY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMSD1010A MMSD1515A OUTDOOR UNIT 2 x MCK010C 2 x MCK015C TURBO FAN TYPE 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 330 / 13.0 178 / 7.0 INDUCTION TYPE INDOOR FAN MOTOR 1 Q'TY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRYL STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 406.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMSD1015A OUTDOOR UNIT MCK010C MCK015C TURBO FAN TYPE 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 330 / 13.0 178 / 7.0 INDUCTION TYPE INDOOR FAN MOTOR 1 Q'TY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 406.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMSD1020A OUTDOOR UNIT MCK010C MCK020C TURBO FAN TYPE 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 330 / 13.00 178 / 7.00 INDUCTION TYPE INDOOR FAN MOTOR 1 Q'TY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMSD1520A OUTDOOR UNIT MCK015C MCK020C TURBO FAN TYPE 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 330 / 13.00 178 / 7.00 INDUCTION TYPE INDOOR FAN MOTOR 1 Q'TY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMSD2020A OUTDOOR UNIT 2 x MCK020C TYPE TURBO FAN 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 330 / 13.00 178 / 7.00 INDUCTION TYPE INDOOR FAN MOTOR 1 Q'TY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 71 : http://splitoff.ru/tehn-doc.
Components Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 72 : http://splitoff.ru/tehn-doc.
Components Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 73 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 74 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 75 : http://splitoff.ru/tehn-doc.
Components Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 76 : http://splitoff.ru/tehn-doc.
Components Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 77 : http://splitoff.ru/tehn-doc.
MMST General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 78 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 79 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 80 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 81 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 82 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 83 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 84 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 85 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 86 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) INDOOR UNIT MMST101010A MODEL OUTDOOR UNIT 3 x MCC010C 3 x MCC015C Btu/h 28500 (9500 - 28500) 38100 (12700 - 38100) W 8350 (2780 - 8350) 11170 (3720 - 11170) W 2808 (1092 - 2808) 4386 (1680 - 4386) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 13.1 (5.0 - 13.1) 19.3 (7.4 - 19.3) W/W 3.04 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST101015A MODEL OUTDOOR UNIT 2 x MCC010C MCC015C Btu/h 31700 (9500 - 31700) W 9280 (2780 - 9270) W 3290 (1065 - 3290) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 15.2 (4.6 - 15.2) W/W 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST101515A MODEL OUTDOOR UNIT MCC010C 34900 (9500 - 34900) W 10220 (2780 - 10220) W 3813 (1065 - 3813) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE 2 x MCC015C Btu/h A 17.0 (4.6 - 17.0) W/W 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST101020A MODEL OUTDOOR UNIT 2 x MCC010C 37000 (9500 - 37000) W 10840 (2780 - 10840) W 4208 (1152 - 4208) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE MCC020C Btu/h A 18.9 (5.1 - 18.9) W/W 2.
General Data - Cooling Only (R22) MMST101525A OUTDOOR UNIT MODEL INDOOR UNIT MCC010C MCC015C Btu/h 44500 (9500 - 23000) W 13040 (2780 - 6740) NOMINAL TOTAL INPUT POWER W 5004 (1166 - 5004) NOMINAL RUNNING CURRENT A 23.6 (5.3 - 23.6) NOMINAL CAPACITY EER POWER SOURCE W/W 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST151525A MODEL OUTDOOR UNIT 2 x MCC015C 47000 (12000 - 47000) W 13780 (3520 - 13780) W 5531 (1614 - 5531) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE MCC025C Btu/h A 26.1 (7.4 - 26.1) W/W 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST101010A MODEL OUTDOOR UNIT 3 x MCK010C 3 x MCK015C Btu/h 28500 (9500 - 28500) 38100 (12700 - 38100) W 8350 (2780 - 8350) 11170 (3720 - 11170) W 2772 (1080 - 2772) 4287 (1647 - 4287) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 12.98 (4.98 - 12.98) 18.86 (7.23 - 18.86) W/W 3.01 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST101015A MODEL OUTDOOR UNIT 2 x MCK010C MCK015C Btu/h 31700 (9500 - 31700) W 9280 (2780 - 9270) W 3233 (1053 - 3233) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 14.91 (4.50 - 14.91) W/W 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST101515A MODEL OUTDOOR UNIT MCK010C 2 x MCK015C Btu/h 34900 (9500 - 34900) W 10220 (2780 - 10220) W 3756 (1053 - 3756) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 16.72 (4.50 - 16.72) W/W 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST101020A MODEL OUTDOOR UNIT 2 x MCK010C 37000 (9500 - 37000) W 10840 (2780 - 10840) W 4035 (1111 - 4035) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 18.10 (4.93 - 18.10) W/W 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST101025A MODEL OUTDOOR UNIT 2 x MCK010C 42000 (9500 - 42000) W 12300 (2780 - 12300) W 4416 (1146 - 4416) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 20.79 (5.06 - 20.79) W/W 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST101025A MODEL OUTDOOR UNIT 2 x MCK010C 42000 (9500 - 42000) W 12300 (2780 - 12300) W 4416 (1146 - 4416) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 20.79 (5.06 - 20.79) W/W 2.
General Data - Cooling Only (R22) OUTDOOR UNIT MMST101525A MODEL INDOOR UNIT MCK010C 44500 (9500 - 23000) W 13040 (2780 - 6740) W 4938 (1154 - 4938) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 23.27 (5.23 - 23.27) W/W 2.
General Data - Cooling Only (R22) INDOOR UNIT MMST151525A MODEL OUTDOOR UNIT 2 x MCK015C 47000 (12000 - 47000) W 13780 (3520 - 13780) W 5444 (1548 - 5444) NOMINAL CAPACITY NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT EER POWER SOURCE A 25.73 (7.11 - 25.73) W/W 2.
General Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 104 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 105 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 106 : http://splitoff.ru/tehn-doc.
General Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
General Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 110 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 111 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 112 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 113 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 114 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 115 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 116 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 117 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 118 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMST101010A INDOOR UNIT 1 QUANTITY 2 GALVANIZED STEEL MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 202 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRYL STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMST101015A INDOOR UNIT 2 x MCC010C 1 QUANTITY INDOOR FAN 2 GALVANIZED STEEL MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 202 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMST101515A INDOOR UNIT MCC010C 1 QUANTITY INDOOR FAN 2 GALVANIZED STEEL MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 202 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMST101020A INDOOR UNIT 2x MCC010C 1 QUANTITY INDOOR FAN 2 GALVANIZED STEEL MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 202 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY 2 N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMST101025A INDOOR UNIT 2x MCC010C 1 QUANTITY INDOOR FAN 2 GALVANIZED STEEL MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 202 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMST151525A INDOOR UNIT 2 x MCC015C INDOOR FAN QUANTITY 2 MATERIAL GALVANIZED STEEL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 203 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL OUTDOOR UNIT MMST101525A INDOOR UNIT MCC010C MCC015C 2 1 QUANTITY INDOOR FAN GALVANIZED STEEL MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 160 / 6.30 202 / 7.95 INDUCTION TYPE INDOOR FAN MOTOR 1 QUANTITY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 QUANTITY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 609.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101010A OUTDOOR UNIT 1 Q'TY ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 330 / 13.0 178 / 7.0 INDUCTION TYPE INDOOR FAN MOTOR 1 Q'TY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRYL STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101015A OUTDOOR UNIT 2 x MCK010C 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 330 / 13.0 178 / 7.0 INDUCTION TYPE INDOOR FAN MOTOR 1 Q'TY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101515A OUTDOOR UNIT MCK010C 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 330 / 13.0 178 / 7.0 INDUCTION TYPE INDOOR FAN MOTOR 1 Q'TY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101020A OUTDOOR UNIT 2x MCK010C 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in LENGTH mm/in 330 / 13.00 178 / 7.00 INDUCTION TYPE INDOOR FAN MOTOR 1 Q'TY N/A INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL INDOOR FAN INDOOR UNIT MMST101025A OUTDOOR UNIT 2x MCK010C TURBO FAN Q'TY 1 MATERIAL DIRECT DRIVE DIAMETER mm/in 330 / 13.0 LENGTH mm/in 178 / 7.0 170 / 6.67 1 Q'TY IP22 INDEX OF PROTECTION (IP) PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMST151525A OUTDOOR UNIT 2 x MCK015C 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in 330 / 13.0 LENGTH mm/in 178 / 7.0 170 / 6.67 1 Q'TY N/A INDEX OF PROTECTION (IP) IP22 PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 482.
Components Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101525A OUTDOOR UNIT MCK010C MCK015C 1 Q'TY INDOOR FAN ASG20 MATERIAL DIRECT DRIVE DIAMETER mm/in 330 / 13.0 LENGTH mm/in 178 / 7.0 N/A IP22 PROPELLER TYPE 1 Q'TY GLASS REINFORCED ACRLY STYRENE RESIN OUTDOOR FAN MATERIAL DIRECT DRIVE DIAMETER 609.6 / 24 mm/in INDUCTION TYPE OUTDOOR FAN Q'TY MOTOR INDEX OF PROTECTION (IP) 1 N/A ROTARY TYPE QUANTITY 1 OIL TYPE ATMOS M60 / SUNISO 4GDID 350 / 11.
Components Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 133 : http://splitoff.ru/tehn-doc.
Components Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 134 : http://splitoff.ru/tehn-doc.
Components Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 135 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 136 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 137 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 138 : http://splitoff.ru/tehn-doc.
Components Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 139 : http://splitoff.ru/tehn-doc.
Components Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 140 : http://splitoff.ru/tehn-doc.
Components Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 141 : http://splitoff.ru/tehn-doc.
Capacity Data - Cooling Only (R22) OUTDOOR OPERATING UNIT (MMST) NOMINAL INDIVIDUAL CAPACITY INDOOR OPERATING UNIT (MWM) 010G 101010A 151515A 101015A 101515A 101020A 101025A 151525A 101525A A B NOMINAL TOTAL CAPACITY C NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT Btu/h W Btu/h W Btu/h W Btu/h W W A 9000 2640 - - - - 9000 2640 1117 4.93 010G + 010G 9000 2640 9000 2640 - - 18000 5280 2006 8.
Capacity Data - Heatpump (R22) Cooling Capacity OUTDOOR OPERATING UNIT (MMST) NOMINAL INDIVIDUAL CAPACITY (COOLING) INDOOR OPERATING UNIT (MWM) 101010AR A B NOMINAL TOTAL CAPACITY C Btu/h W Btu/h W Btu/h W Btu/h W 010GR 9000 2640 - - - - 9000 2640 5280 010GR + 010GR 9000 2640 9000 2640 - - 18000 010GR + 010GR + 010GR 9000 2640 9000 2640 9000 2640 27000 7910 015GR 12000 3520 - - - - 12000 3520 151515AR 015GR + 015GR 12000 3520 12000 3520 - - 24000 70
Capacity Data - Cooling Only (R407C) OUTDOOR OPERATING UNIT (M4MST) NOMINAL INDIVIDUAL CAPACITY INDOOR OPERATING UNIT (MWM) 010G 101010A 151515A 101015A 101515A A B NOMINAL TOTAL CAPACITY C NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT Btu/h W Btu/h W Btu/h W Btu/h W W A 9000 2640 - - - - 9000 2640 1236 5.42 010G + 010G 9000 2640 9000 2640 - - 18000 5280 2138 9.38 010G + 010G + 010G 9000 2640 9000 2640 9000 2640 27000 7920 2943 12.
Capacity Data - Heatpump (R407C) OUTDOOR OPERATING UNIT (M4MST) NOMINAL INDIVIDUAL CAPACITY (COOLING) INDOOR OPERATING UNIT (MWM) 101010AR A B NOMINAL TOTAL CAPACITY C Btu/h W Btu/h W Btu/h W Btu/h W 010GR 9000 2640 - - - - 9000 2640 5280 010GR + 010GR 9000 2640 9000 2640 - - 18000 010GR + 010GR + 010GR 9000 2640 9000 2640 9000 2640 27000 7920 015GR 12000 3520 - - - - 12000 3520 151515AR 015GR + 015GR 12000 3520 12000 3520 - - 24000 7040 015GR + 01
Capacity Data - Cooling Only (R22) OUTDOOR OPERATING UNIT (MMST) NOMINAL INDIVIDUAL CAPACITY INDOOR OPERATING UNIT (MCK) 10C 101010A 151515A 101015A 101515A 101020A 101025A 151525A 101525A A B NOMINAL TOTAL CAPACITY C NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT Btu/h W Btu/h W Btu/h W Btu/h W W A 9500 2780 - - - - 9500 2780 1080 4.98 10C + 10C 9500 2780 9500 2780 - - 19000 5560 1932 8.
Capacity Data - Cooling Only (R22) OUTDOOR OPERATING UNIT (MMST) NOMINAL INDIVIDUAL CAPACITY INDOOR OPERATING UNIT (MCC) 10C 101010A 151515A 101015A 101515A 101020A 101025A 151525A 101525A A B NOMINAL TOTAL CAPACITY C NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT Btu/h W Btu/h W Btu/h W Btu/h W W A 9500 2780 - - - - 9500 2780 1092 5.03 10C + 10C 9500 2780 9500 2780 - - 19000 5560 1956 9.
MMSH General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 148 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 149 : http://splitoff.ru/tehn-doc.
General Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT. 150 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 151 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 152 : http://splitoff.ru/tehn-doc.
Components Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) S.I.G.C. - SEAMLESS INNER GROOVED COPPER. 153 : http://splitoff.ru/tehn-doc.
Capacity Data - Cooling Only (R22) NOMINAL INDIVIDUAL CAPACITY OUTDOOR OPERATING UNIT (MMSH) INDOOR OPERATING UNIT (MWM) 010G 8K8A K77A 8K66A 66K66A A1 A2 A3 B1 NOMINAL NOMINAL TOTAL TOTAL INPUT CAPACITY POWER B2 NOMINAL RUNNING CURRENT Btu/h W Btu/h W Btu/h W Btu/h W Btu/h W Btu/h W W A 8300 2430 - - - - - - - - 8300 2430 827 3.55 3.
Capacity Data - Cooling Only (R22) NOMINAL INDIVIDUAL CAPACITY OUTDOOR OPERATING UNIT (MMSH) 66K555A INDOOR OPERATING UNIT (MWM) A1 A2 A3 B1 NOMINAL NOMINAL TOTAL TOTAL INPUT CAPACITY POWER B2 NOMINAL RUNNING CURRENT Btu/h W Btu/h W Btu/h W Btu/h W Btu/h W Btu/h W W A 010G 10000 2930 - - - - - - - - 10000 2930 1233 5.38 010G - - 10000 2930 - - - - - - 10000 2930 1233 5.38 010G - - - - 10000 2930 - - - - 10000 2930 1233 5.
Dimensional Data OUTDOOR UNIT MODEL : MMSD 1010 / 1015 / 1515 A/AR MMSD 1520AR M4MSD 1010 / 1015 / 1515 A/AR Note : Dimension in mm MODEL : MMSD 1020 / 1520 A Note : Dimension in mm 156 : http://splitoff.ru/tehn-doc.
MODEL : MMSD 2020A Note : Dimension in mm MODEL : MMST 101010 / 101015 / 101515 / 151515 / 101020A M4MST 101010 / 101015 / 101515 / 151515 A/AR Note : Dimension in mm 157 : http://splitoff.ru/tehn-doc.
MODEL : MMST 101025 / 101525 / 151525 / 101520 / 151520 A Note : Dimension in mm MODEL : MMSH 8K8 A Note : Dimension in mm 158 : http://splitoff.ru/tehn-doc.
MODEL : MMSH 8K66 A Note : Dimension in mm MODEL : MMSH 66K66 A Note : Dimension in mm 159 : http://splitoff.ru/tehn-doc.
MODEL : MMSH 66K555 A Note : Dimension in mm MODEL : MMSH K77 A Note : Dimension in mm 160 : http://splitoff.ru/tehn-doc.
INDOOR UNIT MODEL : MWM 010/015 G/GR Note : Dimension in mm INDOOR UNIT MODEL : MWM 020/025 G/GR Note : Dimension in mm 161 : http://splitoff.ru/tehn-doc.
INDOOR UNIT MODEL : MCC 010C/CR Note : Dimension in mm INDOOR UNIT MODEL : MCC 015 ~ 025C/CR Note : Dimension in mm MODEL 015C/CR 020C/CR 025C/CR A 881 1041 1176 B 225 225 225 C 842 1002 1137 D 802 962 1097 E 261 261 261 F 411 411 411 G 351 351 351 162 : http://splitoff.ru/tehn-doc.
INDOOR UNIT MODEL : MCK 025 A MCK 010 / 015 / 020C Note : Dimension in mm MODEL A B C D E F G H I J K MCK-A 820 820 378 350 28 930 930 626 626 555 555 MCK-C 570 570 295 275 20 640 640 408 408 364 364 163 : http://splitoff.ru/tehn-doc.
Electrical Data MMSD Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 164 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 165 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 166 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMSD1010A MMSD1515A OUTDOOR UNIT 2 x MCC010C 2 x MCC015C CLASS E INSULATION GRADE POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 65 96 RATED RUNNING CURRENT A 0.29 0.42 MOTOR OUTPUT W 30 CLASS E INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 170 RATED RUNNING CURRENT A 0.
Electrical Data - Cooling Only (R22) MODEL MMSD1020A INDOOR UNIT OUTDOOR UNIT MCC010C POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 65 135 RATED RUNNING CURRENT A 0.29 0.6 MOTOR OUTPUT W 30 80 4 POLES POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 222 RATED RUNNING CURRENT A 0.98 MOTOR OUTPUT W 50 V/Ph/Hz 220 ~ 240 / 1 / 50 OUTDOOR MOTOR RATED INPUT POWER N/A INSULATION GRADE POWER SOURCE MODEL 30 45 W 821 1804 A 3.64 9.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMSD2020A OUTDOOR UNIT MCC020C CLASS E INSULATION GRADE V/Ph/Hz 220 ~ 240 / 1 / 50 RATED INPUT POWER W 135 RATED RUNNING CURRENT A 0.6 MOTOR OUTPUT W 80 POWER SOURCE INDOOR MOTOR 6 POLES CLASS E INSULATION GRADE V/Ph/Hz 220 ~ 240 / 1 / 50 W 222 RATED RUNNING CURRENT A 0.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMSD1010A MMSD1515A OUTDOOR UNIT 2 x MCK010C 2 x MCK015C CLASS E INSULATION GRADE POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 54 60 RATED RUNNING CURRENT A 0.23 0.27 MOTOR OUTPUT W 16 CLASS E INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 170 RATED RUNNING CURRENT A 0.
Electrical Data - Cooling Only (R22) MODEL MMSD1020A INDOOR UNIT OUTDOOR UNIT MCK010C POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 54 72 RATED RUNNING CURRENT A 0.23 0.32 MOTOR OUTPUT W 16 CLASS E INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 222 RATED RUNNING CURRENT A 0.98 MOTOR OUTPUT W 50 V/Ph/Hz 220 ~ 240 / 1 / 50 OUTDOOR MOTOR RATED INPUT POWER N/A INSULATION GRADE POWER SOURCE MODEL 30 45 W 821 1804 A 3.64 9.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMSD2020A OUTDOOR UNIT MCK020C CLASS E INSULATION GRADE POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 72 RATED RUNNING CURRENT A 0.32 MOTOR OUTPUT W 22 6 POLES CLASS E INSULATION GRADE V/Ph/Hz 220 ~ 240 / 1 / 50 W 222 RATED RUNNING CURRENT A 0.
Electrical Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 173 : http://splitoff.ru/tehn-doc.
Electrical Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 174 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 175 : http://splitoff.ru/tehn-doc.
Electrical Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 176 : http://splitoff.ru/tehn-doc.
MMST Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 177 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 178 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 179 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 180 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 181 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101010A OUTDOOR UNIT INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 65 96 RATED RUNNING CURRENT A 0.29 0.42 MOTOR OUTPUT W 30 CLASS E INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 228 RATED RUNNING CURRENT A 0.
Electrical Data - Cooling Only (R22) MODEL MMST101515A INDOOR UNIT OUTDOOR UNIT MCC010C POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 65 96 RATED RUNNING CURRENT A 0.29 0.42 MOTOR OUTPUT W 30 CLASS E INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 228 RATED RUNNING CURRENT A 0.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101025A OUTDOOR UNIT 2 x MCC010C POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 65 152 RATED RUNNING CURRENT A 0.29 0.67 MOTOR OUTPUT W 30 CLASS B INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 228 RATED RUNNING CURRENT A 0.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101525A OUTDOOR UNIT MCC010C MCC015C POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 65 96 152 RATED RUNNING CURRENT A 0.29 0.40 0.67 MOTOR OUTPUT W 30 50 100 4 POLES CLASS B INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 220 RATED RUNNING CURRENT A 1.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101010A OUTDOOR UNIT INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 54 60 RATED RUNNING CURRENT A 0.23 0.27 MOTOR OUTPUT W 16 CLASS E INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 228 RATED RUNNING CURRENT A 0.
Electrical Data - Cooling Only (R22) MODEL MMST101515A INDOOR UNIT OUTDOOR UNIT MCK010C POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 54 60 RATED RUNNING CURRENT A 0.23 0.27 MOTOR OUTPUT W 16 CLASS E INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 228 RATED RUNNING CURRENT A 0.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101025A OUTDOOR UNIT 2 x MCK010C POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 54 138 RATED RUNNING CURRENT A 0.23 0.61 MOTOR OUTPUT W 16 CLASS B INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 228 RATED RUNNING CURRENT A 0.
Electrical Data - Cooling Only (R22) MODEL INDOOR UNIT MMST101525A OUTDOOR UNIT MCK010C MCK015C POWER SOURCE INDOOR MOTOR 220 ~ 240 / 1 / 50 V/Ph/Hz RATED INPUT POWER W 54 60 138 RATED RUNNING CURRENT A 0.23 0.27 0.61 MOTOR OUTPUT W 16 18 50 6 POLES CLASS B INSULATION GRADE POWER SOURCE 220 ~ 240 / 1 / 50 V/Ph/Hz W 220 RATED RUNNING CURRENT A 1.
Electrical Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 190 : http://splitoff.ru/tehn-doc.
Electrical Data - Heatpump (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 191 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 192 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 193 : http://splitoff.ru/tehn-doc.
Electrical Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 194 : http://splitoff.ru/tehn-doc.
Electrical Data - Heatpump (R407C) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 195 : http://splitoff.ru/tehn-doc.
MMSH Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 196 : http://splitoff.ru/tehn-doc.
Electrical Data - Cooling Only (R22) 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151. 197 : http://splitoff.ru/tehn-doc.
W iring Diagrams OUTDOOR UNIT - COOLING ONLY MODEL : MMSD/M4MSD 1010A/ 1015A/ 1515A MODEL : MMSD 1020A/ 1520A MODEL : MMSD 2020A 198 : http://splitoff.ru/tehn-doc.
OUTDOOR UNIT - COOLING ONLY MODEL : MMST/M4MST 101010A/ 101015A/ 101515A/ 151515A MODEL : MMST 101020A 199 : http://splitoff.ru/tehn-doc.
OUTDOOR UNIT - COOLING ONLY MODEL : MMST 101025A/ 101525A/ 151525A 200 : http://splitoff.ru/tehn-doc.
OUTDOOR UNIT - COOLING ONLY MODEL : MMSH8K8A MODEL : MMSH8K66A MODEL : MMSH66K66A 201 : http://splitoff.ru/tehn-doc.
OUTDOOR UNIT - COOLING ONLY MODEL : MMSH66K555A MODEL : MMSHK77A 202 : http://splitoff.ru/tehn-doc.
OUTDOOR UNIT - HEATPUMP MODEL : MMSD/M4MSD 1010AR / 1015AR / 1515AR MODEL : MMSD 1520AR 203 : http://splitoff.ru/tehn-doc.
OUTDOOR UNIT - HEATPUMP MODEL : MMST / M4MST 101010AR / 101015AR / 101515AR / 151515AR 204 : http://splitoff.ru/tehn-doc.
INDOOR UNIT - COOLING ONLY MODEL : MWM 010/015G (IONIZER) MODEL : MWM 010/015G (NTP) 205 : http://splitoff.ru/tehn-doc.
INDOOR UNIT - COOLING ONLY MODEL : MWM 020/025G (IONIZER) MODEL : MWM 020/025G (NTP) 206 : http://splitoff.ru/tehn-doc.
INDOOR UNIT - HEATPUMP MODEL : MWM 010/015GR (IONIZER) MODEL : MWM 010/015GR (NTP) 207 : http://splitoff.ru/tehn-doc.
INDOOR UNIT - HEATPUMP MODEL : MWM 020/025GR (IONIZER) MODEL : MWM 020/025GR (NTP) 208 : http://splitoff.ru/tehn-doc.
INDOOR UNIT MODEL : MCK 010C MODEL : MCK 015C 209 : http://splitoff.ru/tehn-doc.
INDOOR UNIT MODEL : MCK 020C MODEL : MCK 025A 210 : http://splitoff.ru/tehn-doc.
INDOOR UNIT MODEL : MCC 010C MODEL : MCC 015C 211 : http://splitoff.ru/tehn-doc.
INDOOR UNIT MODEL : MCC 020/ 025 C 212 : http://splitoff.ru/tehn-doc.
Ser vicing and Maintenance The design of the M(4)MSD, M(4)MST, and MMSH outdoor series allows servicing to be carried out readily and easily. The removal of the top, side, front, and back panel make almost every part accessible. MODEL : Cooling - MMSD/M4MSD 1010 / 1015 / 1515 A Heatpump - MMSD/M4MSD 1010 / 1015 / 1515 AR Cooling - MMSH 8K8 / 8K66 / 66K66 / 66K555 / K77 A MODEL : Cooling - MMSD1020 / 1520A Heatpump - MMSD1520AR 213 : http://splitoff.ru/tehn-doc.
MODEL : MMSD 2020A MODEL : MMST 101010 / 101015 / 101515 / 151515 A/AR MMST 101020 / 101520 / 151520 A M4MST 101010 / 101015 / 101515 / 151515 A/AR 214 : http://splitoff.ru/tehn-doc.
MODEL : MMST 101025 / 101520 / 101525 / 151520 / 151525 A Under normal circumstance, these outdoor units require a check and cleaning of air intake coil surface once quarterly. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must be regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation. Otherwise, the system’s life span may be shortened.
Troubleshooting When any air conditioner malfunction is noted, immediately switch off the power supply to the unit and contact the local dealer, if necessary. Some simple troubleshooting tips are given below : TROUBLE PROBABLE CAUSE SUGGESTED ACTION 1. Fan does not work 1. No power supply 2. Fan capacitor faulty 3. Fan motor faulty 4. Switch faulty 1. Check power supply 2. Contact local dealer 3. Contact local dealer 4. Change switch 2. Fan works, but compressor does not work 1.
Generally, there are two kinds of common problems, i.e. starting failure and insufficient cooling. "Starting failure" is caused by electrical defect while "insufficient cooling" is caused by improper application or defects in refrigerant circuit.
Exploded View & Par ts List MODEL : MMSD / M4MSD 1010 / 1015 / 1515 A/AR No Description 1 ASSY, GRILLE BACK 2 3 4 5 6 Part No. No Description Part No. R50014043394 12 FAN MOTOR F634P80 220V/80W R03039000057 HANDLING HANDLE R12014040467 13 FAN MOTOR BRACKET R01010011398 TOP PANEL R01010011397 14 BASE PAN ASSY.
MODEL : MMSD 1020A / 1520A 219 : http://splitoff.ru/tehn-doc.
MODEL : MMSD 1020A / 1520A No Description Part No.
MODEL : MMSD 1520AR No Description 1 PANEL TOP Part No. No Description R01014020372 19 VALVE COVER Part No.
MODEL : MMSD 2020A No Description 1 COMPRESSOR Part No. No Description R04019009667 13 VALVE COVER Part No.
MODEL : MMST 101010 / 101015 / 101515 / 151515 A/AR, 101020A M4MST 101010 / 101015 / 101515 / 151515 A/AR No Description Part No.
MODEL : MMST 101010 / 101015 / 101515 / 151515 A/AR, 101020A M4MST 101010 / 101015 / 101515 / 151515 A/AR No Description Part No.
MODEL : MMST 101025 / 101525 / 151525 / 101520 / 151520 A No Description 1 ASSY. PANEL BASE Part No. No Description R50014068404 ASSY. MAIN COIL 2 Part No. 12 ASSY. TERMINAL BOX COVER R04119000045 13 ASSY.
MODEL : MMSH 8K8 A No Description Part No. No Description Part No. 1 FAN PROPELLER A03019000016 4 FRONT PANEL R01014044590 2 FAN MOTOR A03039000057 5 GRILLE BACK R50014043394 3 COMPRESSOR A04019002772 6 CONDENSER COIL A50024033574 226 : http://splitoff.ru/tehn-doc.
MODEL : MMSH 8K66A / 66K66A / 66K555A No Description Part No. 1 FAN PROPELLER R03019000016 2 FAN MOTOR R03039000057 3 COMPRESSOR R04019002774 4 COMPRESSOR No Description Part No. CONDENSER COIL 7 MSH8K66A R50024030107 MSH66K66A R50024029462 R04019002772 MSH66K555A R50024039229 Parts not in diagram 5 FRONT PANEL R50014045824 6 GRILLE BACK R50014043394 CONTROL MODULE 8 MSH8K66A R04089007573 MSH66K66A R04089003221 MSH66K555A R04089007575 227 : http://splitoff.ru/tehn-doc.
MODEL : MMSH K77 A No Description 1 FAN PROPELLER 2 3 Part No. No Description Part No. A03019004131 4 FRONT PANEL R50014045925 FAN MOTOR A03039000056 5 GRILLE BACK A50014041357 COMPRESSOR R04019006193 6 CONDENSER COIL A50024040968 228 : http://splitoff.ru/tehn-doc.
Products manufactured in an ISO certified facility. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com. © 2008 McQuay International +1 (800) 432-1342 www.mcquay.com http://splitoff.ru/tehn-doc.html , , , .