Installation manual
IM-487 Page 37
Mixing Box (RAH 47-77 only)
This section utilizes an outside air damper and a return air
damper. Use of these dampers allows outside air to be
blended with return air. Synchronized operation of the
dampers is accomplished by interconnecting rods. As one
damper section opens, the other section is being closed.
Always a total of 100% CFM is drawn from this section.
Damper positioning may be either manually or automati-
cally adjusted. With a field installed controller, automatic
operation can be obtained.
These dampers provide a similar function to the economizer
dampers. This option differs from an economizer in that no
unit mounted exhaust dampers are provided.
Figure 40. Mixing Box
Note: For good airflow control, adjust linkages so damper blades do not open beyond 70 degrees. Opening a damper blade
beyond 70 degrees has little effect on its airflow. Do not "overclose " low leak damper blades. The edge seal should just
lightly contact the adjoining blade. The blades will lock-up if they are closed so far that the seal goes over center.
OA
CLOSED
OA
OPEN
90∞
STROKE
.25" (6 mm)
.75"
(19 mm)
3.00"
(76 mm)
OA
CLOSED
OA
OPEN