Installation manual
McQuay IM 487-4 95
Check, Test, and Start Procedures
Note:
If desired, you can significantly reduce all MicroTech II 
internal control timers by the changing the entry under 
keypad menu Setup/Service\Unit Configuration\Timer 
Settings\Service= from “0 min” to “X min” where X is 
the number of minutes you want the unit to operate with 
fast timers.
Power Up
1 Close the unit disconnect switch. With the control system 
switch S1 in the OFF position, power should be available 
only to the control circuit transformer (TI) and the 
compressor crankcase heaters.
2 Turn the Switch S1 to ON. Power should now be supplied 
to the control panel, and the LEDs on MCB1 should follow 
the normal startup sequence (refer to the “MCB LED 
Power-Up Sequence” of IM 696).
Fan Start-up
1 Verify all duct isolation dampers are open. Unit mounted 
isolation dampers may be mounted in the supply or return 
sections. 
2 Place the unit into the “Fan Only” mode through the 
keypad menu System Summary\System\Ctrl Mode= Fan 
Only.
3 Turn Switch S7 to ON. The controller should enter the 
“Startup Initial” operating state. If the fan does not run:
a Check fuses F1 and F3.
b Check the manual motor protectors or that the circuit 
breakers have not tripped.
c Check the optional phase monitor.
4 If the fans are equipped with optional spring isolators, 
check the fan spring mount adjustment. When the fans are 
running they should be level. Refer to “RAH spring mount 
hold down fasteners” on page 51.
5 Verify the rotation is correct.
6 Verify the DHL safety is opening at a pressure compatible 
with duct working pressure limits.
Note: The supply and return fan drives usually are selected for 
operation in the drive's midspeed range. The return fan 
drives are usually shipped with fixed pitch sheaves that 
will provide the selected fan speed; however, the supply 
fan drives are usually shipped with variable pitch 
sheaves that are adjusted to provide the minimum fan 
speed. Both drives should be adjusted for proper airflow 
during air balancing. For more information, refer to “Air 
Balancing” on page 96.
Economizer Start-up
1 Check whether the outdoor air is suitable for free cooling 
by displaying the keypad menu Temperature\OA 
Damper\OA Ambient=. “Low” indicates low outdoor air 
enthalpy; “High” indicates high outdoor air enthalpy. See 
“Enthalpy Control” on page 84 to verify that the enthalpy 
changeover control is working properly. You may want to 
take temperature and humidity measurements.
2 Verify that switches PS1 and PS2 are at OFF. This prevents 
compressor operation during the procedure.
3 At the keypad, set the cooling setpoint low enough so the 
controller calls for cooling. Adjust the value in 
Temperature\Zone Cooling\Occ Clg Spt= below the 
temperature shown in Temperature\Zone Cooling\Control 
Temp=. In addition, on DAC units, adjust the value in 
Temperature\Discharge Cooling\DAT Clg Spt= below the 
temperature shown in Temperature\Discharge 
Cooling\Disch Air=.
4 Place the unit into cooling mode through the keypad menu 
System Summary\System\Ctrl Mode= Cool Only.
5 Observe the outdoor air dampers:
a If the outdoor enthalpy is low, the control algorithm 
should start to modulate the dampers open to maintain 
the discharge air setpoint.
b If the outdoor enthalpy is high, the dampers should 
maintain their minimum position. Look at menu 
Temperature\OA Damper\MinOA Pos=. Change this 
entry to another value. Verify that the dampers move to 
the new minimum position setpoint.
6 If the unit is equipped with the electromechanical enthalpy 
changeover control (Honeywell H205) and the outdoor air 
condition is borderline, attempt to change its input to the 
MicroTech II controller by turning the switch adjustment to 
“A” or “D.” Check enthalpy status in keypad menu 
Temperature \ OA Damper \ OA Ambient=. If this reading 
is “Low,” go to step 5a. If it is “High,” go to step 5b.
Note: It may not be possible to check the economizer 
operation in both low and high enthalpy states on the 
same day. If this is the case, repeat this procedure on 
another day when the opposite outdoor air enthalpy 
conditions exist.
CAUTION
Adjust dampers properly. Improper adjustment can damage the 
dampers.
When an economizer is ordered without an actuator, the 
linkage requires a 3.14" linear stroke to open it fully. Do not 
allow dampers to be driven beyond their normal full closed or 
full open position.










