Product data

14 Catalog 724-2
Options and Accessories
Figure 11: Factory-installed Valve & Piping Packages (right-hand shown)
REFERENCE POINT
×
×
REFERENCE POINT
B
A
4.43
5.5
3.42
5.38
Primary
Return
Primary
Return
Primary
Supply
Primary
Supply
20.25
7.0
0.56
1.5
10.42
10.8
10.58
Overflow Connection
Drain Connection
11.1
End
View
Front
View
Connecting Pipe Locations: 2-Pipe Cooling Only, Right-hand
Deluxe Package shown, see schematic (page 2) for the list of components selected for this package
Name Component Description
Primary Package Connections from Reference Point
(2- & 3-row Coil)
Supply (A)* Return (B)*
Basic 2W 2Way control valve, shut-off valves 12.2 16.2
Basic 3W 3Way control valve, shut-off valves 12.2 17.0
Enhanced 2W 2Way control valve, shut-off valves, strainer 15.8 16.3
Enhanced 3W 3Way control valve, shut-off valves, strainer 15.8 17.0
Premium 2W, auto ow 2Way control valve, shut-off valves, auto ow-setter 12.3 15.8
Premium 2W, manual ow 2Way control valve, shut-off valves, manual ow-setter 12.3 16.6
Premium 3W, auto ow 3Way control valve, shut-off valves, auto ow-setter 12.2 14.8
Premium 3W, manual ow 3Way control valve, shut-off valves, manual ow-setter 12.2 15.6
Deluxe 2W, auto ow 2Way control valve, shut-off valves, strainer, auto ow-setter 15.8 15.8
Deluxe 2W, manual ow 2Way control valve, shut-off valves, strainer, manual ow-setter 15.8 16.6
Deluxe 3W, auto ow 3Way control valve, shut-off valves, strainer, auto ow-setter 12.2 14.8
Deluxe 3W, manual ow 3Way control valve, shut-off valves, strainer, manual ow-setter 12.2 15.6
NOTE: For 4-row Primary Coils add 1" to the dimensions A and B shown
Connecting Pipe Locations: 2-Pipe Cooling or Heating
Deluxe Package shown