Product data

18 Catalog 724-2
Performance Data PSC
Performance Data PSC
Four-Pipe Systems - Hot Water Preheat or Reheat (Standard or High Capacity)
All performance measured on high speed tap, 115 V, at 0.05"
ESP for hideaway fan coils.
Cooling performance is based on 80/67°F (27/19°C)
entering air temperature, 45°F (7°C) entering chilled water
temperature with a 10°F (5.5°C) temperature rise.
Heating performance is based on 70°F (21°C) entering air
temperature, 180°F (82°C) entering hot water temperature
with a 30°F (17°C) temperature drop.
For other conditions and/or unit configurations, refer to
Daikin Tools selection program or talk to your local Daikin
Applied sales representative.
Table 3: Cooling and heating performance - four-pipe systems, hot water heat
Unit
Model
Unit
Size
Nominal
Air Flow
SCFM
Number
of
Primary
Rows
Cooling Performance Heating Performance
Total,
MBH
Sensible,
MBH
Chilled
Water
Flow
GPM
CW
Pressure
Drop, Ft
Standard
Capacity
Coil,
MBH
High
Capacity
Coil,
MBH
Hot Water
Flow
(Hi Cap),
GPM
Hot Water
Pressure
Drop
(Hi Cap), Ft
FCHH no plenum, free discharge fan
02 200
2 4.9 4.5 1.0 0.2 8.3 11.9 0.8 1.7
3 8.3 6.5 1.7 0.9 8.1 11.6 0.8 1.6
4 10.3 7.3 2.1 1.7 7.9 11.4 0.8 1.6
03 300
2 5.4 5.0 1.1 0.3 9.0 13.0 0.9 1.9
3 10.1 8.0 2.0 1.2 8.8 12.7 0.9 1.9
4 12.5 8.9 2.5 2.4 8.6 12.5 0.8 1.8
04 400
2 7.6 7.3 1.5 0.6 12.6 19.5 1.3 5.5
3 13.1 10.0 2.6 2.2 12.2 19.1 1.3 5.3
4 15.3 10.6 3.1 3.9 11.9 18.7 1.3 5.1
06 600
2 14.0 12.1 2.8 2.2 19.1 28.4 1.9 13.1
3 19.4 14.6 3.9 5.6 18.6 27.8 1.9 12.6
4 21.6 15.3 4.3 8.8 18.1 27.3 1.8 12.2
08 800
2 17.0 14.1 3.4 3.2 21.6 32.6 2.2 17.4
3 22.5 16.6 4.5 7.7 21.0 31.9 2.1 16.8
4 24.7 17.3 5.0 12.3 20.4 31.3 2.1 16.2
10 1000
2 26.2 21.2 5.3 8.1 34.6 43.8 2.9 37.6
3 33.1 24.7 6.6 12.0 33.7 42.9 2.9 36.2
4 37.5 26.0 7.5 21.7 32.9 42.0 2.8 34.4
12 1200
2 34.0 27.5 6.8 14.7 41.6 59.0 4.0 73.6
3 43.0 31.8 8.6 23.2 40.5 57.8 3.9 71.1
4 48.8 33.0 9.8 44.9 39.5 56.7 3.8 68.8
115/1/60 PSC motor at High speed setting
FCHH (w/o plenum) at 0.05” ESP
Free discharge