Product data

Catalog 724-2 21
Performance Data ECM
Performance Data ECM
Performance Cooling and Heating – 2- and 4- Pipe
Air volumes shown in the table are measured at the motor
speeds indicated with 115v/60/1 electrical power, with a 1"
throwaway lter installed, and with a stamped discharge
grille on a horizontal cabinet unit or a discharge duct collar on
a hideaway unit at approximately 0.05 inch of pressure drop.
Cooling performance is based on 80/67°F (27/19°C)
entering air temperature, 45°F (7°C) entering chilled water
temperature with a 10°F (5.5°C) temperature rise.
Heating performance is based on 70°F (21°C) entering air
temperature, 180°F (82°C) entering hot water temperature
with a 30°F (17°C) temperature drop.
For other conditions and/or unit configurations, refer to
Daikin Tools selection program or talk to your local Daikin
Applied sales representative.
Table 7: Air volume at various fan speeds ECM motors, SCFM
Table 8: Air volume for units with ECM at all congurations and external static pressures up to 0.5"
Unit
Model
Unit Size
Air Flow
1
SCFM
Number
of Primary
Rows
Cooling Performance Heating Performance
Total,
MBH
Sensible,
MBH
Primary
Coil, MBH
Secondary Std
Capacity Coil,
MBH
Secondary High
Capacity Coil,
MBH
FCHH, FCHC, FCHR any conguration
02 329
2 5.1 4.7 21.2
8.4 12.23 9.6 7.5 28.6
4 12.5 9.0 31.7
03 393
2 5.5 5.1 23.9
8.9 13.13 11.1 8.8 32.7
4 14.3 10.5 36.6
04 459
2 8.3 7.9 31.0
12.6 19.93 14.6 11.3 41.1
4 18.1 12.9 45.9
06 670
2 12.5 10.6 57.1
17.3 263 20.8 15.8 62.9
4 24.8 17.8 70.2
08 770
2 17.8 14.8 61.8
21.5 33.23 24.8 18.6 72.2
4 29.2 20.8 79.6
10 1124
2 27.1 22.1 88.6
34.4 44.43 36.0 27.2 101.2
4 43.7 30.9 114.1
12 1464
2 35.4 28.9 107.6
41.6 60.23 47.5 35.7 126.4
4 57.5 39.5 144.7
1. ECM motor at High speed setting, standard MERV 4 lter, any external static pressure up to 0.5"
Size Super High High* Medium* Low* Super Low
02 362 329 195 115 93
03 432 393 236 165 133
04 505 459 346 260 238
06 737 670 550 388 345
08 847 770 630 444 404
10 1236 1124 865 622 490
12 1610 1464 1027 701 632
* Standard speed setting from the factory. Super High setting is 10% higher than High. Super Low setting is 10% lower than Low.