Specifications

10
Use the following graph and the multimeter to verify proper
operation of the mixed air / discharge air temperature
sensor.
Measure the resistance (ohms) of the mixed air / discharge
air temperature sensor with the multimeter. Look up the
equivalent temperature on the graph. This should be the
same as temperature the mixed air / discharge air sensor is
detecting. If it is not, replace the mixed air /discharge air
sensor.
NOTES
1. The mist eliminator (Permanent Outdoor Air Filter), is
of aluminum mesh construction and should be
cleaned by flushing regularly with warm soapy water.
The replacement mist eliminator size is listed on the
first page of these instructions.
2. When diagnosing the system, the best results are
obtained by first putting the fan setting on the
Thermostat to the "Continuous Fan" mode.
3. Operation of the optional power exhaust only depends
upon the supply fan running and the damper position
(it is possible to set the minimum position high enough
to engage the power exhaust in the heating mode).
4. This economizer requires a two-stage thermostat.
5. Upon loss of power to the unit or economizer, the
outside air damper will spring close shut in about 5
seconds.
6. Compressor Time Delays, Compressor Interstage
Delays, Compressor Low Ambient Lockouts, etc. are
not provided by the economizer controller.
Page 44